Plan Review Details - Permit 14010860
Plan Review Stops For Permit 14010860
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-04 Cont ID  
Sent By jwitmer Date 2014-06-04 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2014-06-04 Time 11:31 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-03 Cont ID  
Sent By jwitmer Date 2014-02-03 Time 18:22 Rev Time 0.00
Received By jwitmer Date 2014-02-03 Time 16:30 Sent To  
Notes
2014-02-03 18:01:03BUILDING PLAN REVIEW
 PERMIT: 14010860
 ADD: 2500 METROCENTRE BLVD SUITE # 1
 CONT: TO BE DETERMINED
 TEL: (561)786-486-9513
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY FEB. 03/2014
 ACTION: DENIED
  
 TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT
 DAYCARE OCCUPANCY 5,530 SQ FT APPROX
 BLDG TYPE 3B
  
 PROVIDE A BREAK DOWN ON USE AREAS BY SQ FT:
 PRE-SCHOOL
 OPEN SUPPORT
 THEROPY ROOMS
 OFFICES
 STORAGE ROOMS
  
 CHANGE OF OCCUPANCY: BUSINESS TO DAYCARE/ 2010 EXISTING
 BUILDING CODE CHAPTER 9 : 901.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 1) WITH THIS TENANT SPACE BEING A CHANGE OF OCCUPANCY
 FROM BUSINESS TO DACARE OCCUPANCY THE DESIGNER OF
 RECORD WILL NEED TO COMPLY WITH 912.1.1 COMPLIANCE WITH
 CHAPTER 8. THE REQUIREMENTS OF CHAPTER 8 SHALL BE
 APPLICABLE THROUGHOUT THE BUILDING FOR THE NEW
 OCCUPANCY CLASSIFICATION BASED ON THE SEPARATION
 CONDITIONS SET FORTH IN SECTIONS 912.1.1.1 AND
 912.1.1.2.
  
 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS NOT
 SEPARATED FROM THE REMAINDER OF THE BUILDING WITH A
 FIRE-RATED WALL/CEILING HAVING A FIRE-RESISTANCE RATING
 AS REQUIRED IN THE FLORIDA BUILDING CODE, BUILDING FOR
 THE SEPARATE OCCUPANCY, THE ENTIRE BUILDING SHALL
 COMPLY WITH ALL OF THE REQUIREMENTS OF CHAPTER 8
 APPLIED THROUGHOUT THE BUILDING FOR THE MOST
 RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING
 AND WITH THE REQUIREMENTS OF THIS CHAPTER.
  
 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION. REQUIRES A (2) HR OCCUPANCY SEPERATION.
 WHERE A PORTION OF AN EXISTING BUILDING THAT IS CHANGED
 TO A NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS
 SEPARATED FROM THE REMAINDER OF THE BUILDING WITH FIRE
 BARRIERS HAVING A FIRE-RESISTANCE RATING AS REQUIRED IN
 THE FLORIDA BUILDING CODE, BUILDING FOR THE SEPARATE
 OCCUPANCY, THAT PORTION SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF CHAPTER 8 FOR THE NEW OCCUPANCY
 CLASSIFICATION AND WITH THE REQUIREMENTS OF THIS
 CHAPTER.
  
 2) 912.1.2 FIRE PROTECTION AND INTERIOR FINISH. THE
 PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR FIRE
 PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL
 APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
 912.3 INTERIOR FINISH. IN AREAS OF THE BUILDING
 UNDERGOING THE CHANGE OF OCCUPANCY CLASSIFICATION, THE
 INTERIOR FINISH OF WALLS AND CEILINGS SHALL COMPLY WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 FOR THE NEW OCCUPANCY CLASSIFICATION.
 SEE 2010 FBC-B TABLE 803.9 INTERIOR WALL & CEILING
 FINISHE REQUIREMENTS BY OCCUPANCY/ DAYCARE-
 NONSPRINKLERED.
  
 3) 912.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. 912.8
 ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A CHANGE
 OF GROUP OR OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
  
 2010 FLBC- ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 2010 FLBC- ACCESSIBILITY CODE 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4) 912.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION
 SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 912.2.1 AND 912.2.2
 912.2.1 NOT REQUIRED- FIRE SPRINKLERS
  
 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
 436.7.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY MANUAL MEANS AND BY OPERATION OF ANY
 REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER
 SYSTEMS.
  
 436.7.1.1 OCCUPANT NOTIFICATION SIGNALS SHALL BE
 AUDIBLE AND VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72
 AND THE FLORIDA BUILDING CODE, ACCESSIBILITY. THE
 GENERAL EVACUATION ALARM SIGNAL SHALL OPERATE
 THROUGHOUT THE ENTIRE BUILDING.
 EXCEPTIONS: 1. WHERE TOTAL EVACUATION OF OCCUPANTS IS
 IMPRACTICAL BECAUSE OF BUILDING CONFIGURATION, ONLY THE
 OCCUPANTS IN THE AFFECTED ZONES SHALL BE INITIALLY
 NOTIFIED. PROVISIONS SHALL BE MADE TO SELECTIVELY
 NOTIFY OCCUPANTS IN OTHER ZONES TO AFFORD ORDERLY
 EVACUATION OF THE ENTIRE BUILDING.
 2. WHERE OCCUPANTS ARE INCAPABLE OF EVACUATING
 THEMSELVES BECAUSE OF AGE, PHYSICAL OR MENTAL
 DISABILITY OR PHYSICAL RESTRAINT, THE PRIVATE OPERATING
 MODE AS DESCRIBED IN NFPA 72 SHALL BE PERMITTED TO BE
 USED. ONLY THE ATTENDANTS AND OTHER PERSONNEL REQUIRED
 TO EVACUATE OCCUPANTS FROM A ZONE, AREA, FLOOR, OR
 BUILDING SHALL BE REQUIRED TO BE NOTIFIED. THIS
 NOTIFICATION SHALL INCLUDE MEANS TO READILY IDENTIFY
 THE ZONE, AREA, FLOOR OR BUILDING IN NEED OF
 EVACUATION.
  
 436.7.1.2 FIRE DEPARTMENT NOTIFICATION.
 THE FIRE ALARM SYSTEM SHALL BE ARRANGED TO TRANSMIT THE
 ALARM AUTOMATICALLY TO THE FIRE DEPARTMENT IN
 ACCORDANCE WITH NFPA 72 BY MEANS OF ONE OF THE
 FOLLOWING METHODS AS APPROVED BY THE BUILDING OFFICIAL:
 1. AN AUXILIARY ALARM SYSTEM, OR
 2. A CENTRAL STATION CONNECTION, OR
 3. A PROPRIETARY SYSTEM, OR
 4. A REMOTE STATION CONNECTION.
 EXCEPTION: WHERE NONE OF THE ABOVE MEANS OF
 NOTIFICATION IS AVAILABLE, A PLAN FOR NOTIFICATION OF
 THE FIRE DEPARTMENT, ACCEPTABLE TO THE BUILDING
 OFFICIAL, SHALL BE PROVIDED.
  
 436.7.2 DETECTION.
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN
 THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY.
 EXCEPTION: DAY CARE OCCUPANCIES HOUSED IN ONE ROOM.
  
 5) 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY. WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS
 MADE TO A HIGHER HAZARD CATEGORY (LOWER NUMBER) AS
 SHOWN IN TABLE 912.4, THE MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2010 FBC-B 1029.4.1
 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2
 M2) IN EDUCATIONAL OCCUPANCIES USED FOR
 CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR NORMALLY
 SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM
 OR SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER
 THAN BATHROOMS, IN GROUP D OCCUPANCIES SHALL
 HAVE NOT LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY
 RESCUE THAT COMPLIES WITH THE FOLLOWING:
 1.SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE
 FEET (0.53 M2) IN AREA.
 2.THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY
 LATCHING DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM
 NOT MORE THAN 54 INCHES (1372 MM) ABOVE
 THE FINISHED FLOOR.
 EXCEPTIONS:
 1.BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 903.3.1.1.
 2.WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO THE OUTSIDE OF THE BUILDING.
  
 6) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 7) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM
 THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
  
 6) 436.6 PROTECTION FROM HAZARDS.
 ROOMS OR SPACES FOR THE STORAGE, PROCESSING OR USE OF
 MATERIALS SPECIFIED BELOW SHALL BE PROTECTED IN
 ACCORDANCE WITH THE FOLLOWING:
  
 6A) 436.6.1
 THE FOLLOWING ROOMS OR SPACES SHALL BE SEPARATED FROM
 THE REMAINDER OF THE BUILDING BY FIRE BARRIERS HAVING A
 FIRE RESISTANCE RATING OF NOT LESS THAN 1-HOUR OR SHALL
 BE PROTECTED BY AN APPROVED AUTOMATIC EXTINGUISHING
 SYSTEM.
  
 1. BOILER AND FURNACE ROOMS.
  
 EXCEPTION: ROOMS ENCLOSING ONLY AIR-HANDLING EQUIPMENT.
  
 2. ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE
 SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
  
 3. ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS
 MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN
 QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 4. JANITOR CLOSETS.
  
 EXCEPTION: DOORS TO JANITOR CLOSETS SHALL BE PERMITTED
 TO HAVE VENTILATING LOUVERS WHERE THE SPACE IS
 PROTECTED BY AUTOMATIC SPRINKLERS.
  
 6B) 436.6.2
 THE FOLLOWING ROOMS OR SPACES SHALL BE SEPARATED FROM
 THE REMAINDER OF THE BUILDING BY FIRE BARRIERS HAVING A
 FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR AND
 SHALL BE PROTECTED BY AN APPROVED AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM.
  
 1. LAUNDRIES.
  
 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND
 PAINTING AREAS.
  
 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
  
 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 EXCEPTION: FOOD PREPARATION FACILITIES PROTECTED IN
 ACCORDANCE WITH NFPA 96 SHALL NOT BE REQUIRED TO HAVE
 OPENINGS PROTECTED BETWEEN FOOD PREPARATION AREAS AND
 DINING AREAS. WHERE DOMESTIC COOKING EQUIPMENT IS USED
 FOR FOOD WARMING OR LIMITED COOKING, PROTECTION OR
 SEGREGATION OF FOOD PREPARATION FACILITIES SHALL NOT BE
 REQUIRED IF APPROVED BY THE BUILDING OFFICIAL.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-06-04 Cont ID  
Sent By albarran Date 2014-06-04 Time 18:52 Rev Time 0.00
Received By albarran Date 2014-06-04 Time 16:35 Sent To I
Notes
2014-06-04 18:52:46ELECTRICAL PROVISOS FOR PERMIT #14010860
  
 1. THE CLASSROOM, DAYCARE, MEETING ROOM AND/OR
 PRE-SCHOOL AREAS ARE EXEMPT FROM THE LIGHTING
 REQUIREMENTS OF THE 2010 FBC-E SECTION 505.1. ALL
 OTHERS, INCLUDING THE EXTERIOR SIGN SHALL COMPLY W/THE
 FBC-E SECTION 505 REQUIREMENTS.
 2. ALL VENDING MACHINES OLDER THAN JAN. 1, 2005 AND
 ELECTRIC DRINKING FOUNTAINS SHALL BE CONNECTED TO A
 GFCI CIRCUIT.
 3. ALL EMERGENCY LIGHTING SHALL BE CONNECTED TO THE
 LIGHTING CIRCUIT OF THE AREA THEY OCCUPY.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-05-28 Cont ID  
Sent By albarran Date 2014-05-28 Time 18:14 Rev Time 0.00
Received By albarran Date 2014-05-28 Time 17:34 Sent To  
Notes
2014-05-28 18:16:20FAILED ELECTRICAL REVIEW BECAUSE THE SUBMITTED PLANS
 ARE TOO SMALL TO READ.
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-13 Cont ID  
Sent By rlecky Date 2014-02-13 Time 10:47 Rev Time 0.00
Received By rlecky Date 2014-02-13 Time 09:12 Sent To  
Notes
2014-02-13 10:48:5714010860
 2500 METRO CENTER
 CHANGE OF BUSINESS OCCUPANCY TO CHILD DAY CARE.
  
 PROVIDE AN ELECTRICAL AND LIGHTING PLAN. INCLUDE AN
 ELECTRICAL PANEL SCHEDULE SHOWING ALL FEEDERS WITH OVER
 CURRENT PROTECTION AND BRANCH CIRCUITS FOR THE NEW
 OCCUPANCY. NEC 215.5
  
 SHOW LOCATION OF PANEL BOARDS. PROVIDE A DEDICATED SAFE
 WORKING SPACE FOR THE ELECTRICAL PANEL BOARDS. NEC
 110.26
  
 SHOW THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP. FBC 1011
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND
 WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED.
 NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ELECTRIC DRINKING FOUNTAINS MUST BE GFCI PROTECTED. NEC
 422.52
  
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.12
  
 A FIRE DETECTION AND ALARM SYSTEM IS REQUIRED. FBC
 436.7
  
 A SEPARATE CIRCUIT IS REQUIRED FOR THE FIRE ALARM
 SYSTEM. NEC 760.41
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-05-16 Cont ID  
Sent By pleduc Date 2014-05-16 Time   Rev Time 0.00
Received By pleduc Date 2014-05-16 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-01-28 Cont ID  
Sent By wjolin Date 2014-01-28 Time 11:58 Rev Time 0.00
Received By wjolin Date 2014-01-28 Time 11:17 Sent To  
Notes
2014-01-28 11:58:412500 METROCENTRE BOULEVARD - #1
 PERMIT #14010860
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DAY-CARE DESIGN SHALL CONFORM TO THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 DAY-CARE OCCUPANCY WILL NEED TO BE FIRE SEPARATED FROM
 ADJACENT OCCUPANCIES WITH A 2-HOUR FIRE BARRIER.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED BARRIERS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY
 (DAY-CARE, EDUCATIONAL (PRE-SCHOOL), BUSINESS).
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 EVERY ROOM OR SPACE NORMALLY SUBJECT TO CLIENT
 OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS
 THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH THE FOLLOWING, UNLESS THE BUILDING IS
 PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM OR WHERE THE ROOM OR SPACE
 HAS A DOOR LEADING DIRECTLY TO THE OUTSIDE OF THE
 BUILDING
  
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 IN. (510 MM) IN WIDTH, 24
 IN. (610 MM) IN HEIGHT, AND 5.7 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN. (1120 MM) ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 FT2 (0.5M2) OPENING AND A DEPTH OF NOT
 LESS THAN 20 IN. (510 MM), TO PASS FULLY THROUGH THE
 OPENING.
  
 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM INSIDE THE CLOSET.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A IN STAIRWAYS, CORRIDORS, AND LOBBIES; IN ALL
 OTHER OCCUPIED AREAS, INTERIOR WALL AND CEILING FINISH
 SHALL BE CLASS A OR CLASS B.
  
 DAY-CARE OCCUPANCIES, OTHER THAN DAY-CARE OCCUPANCIES
 HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR OPENING
 DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR EXIT ACCESS BALCONY, SHALL BE PROVIDED WITH A
 FIRE ALARM SYSTEM. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM SHALL BE BY MANUAL MEANS AND BY OPERATION
 OF ANY REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER
 SYSTEMS.
  
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN DAY-CARE
 OCCUPANCIES, OTHER THAN THOSE HOUSED IN ONE ROOM HAVING
 AT LEAST ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT
 GRADE PLANE OR TO AN EXTERIOR
 EXIT ACCESS BALCONY AND SUCH SYSTEM SHALL COMPLY WITH
 BOTH OF THE FOLLOWING:(1) DETECTORS SHALL BE INSTALLED
 ON EACH STORY IN FRONT OF THE DOORS TO THE STAIRWAYS
 AND IN THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE
 DAY-CARE OCCUPANCY. (2) DETECTORS SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS, AND SLEEPING ROOMS IN THE
 DAY-CARE OCCUPANCY.
  
 PROTECTIVE COVERS FOR ALL ELECTRICAL RECEPTACLES SHALL
 BE INSTALLED IN ALL AREAS OCCUPIED BY CLIENTS.
  
 EMERGENCY PLANS SHALL BE PROVIDED.
  
 EMERGENCY EGRESS AND RELOCATION DRILLS SHALL BE
 CONDUCTED AS FOLLOWS: (1) NOT LESS THAN ONE EMERGENCY
 EGRESS AND RELOCATION DRILL SHALL BE CONDUCTED EVERY
 MONTH THE FACILITY IS IN SESSION, UNLESS BOTH OF THE
 FOLLOWING CRITERIA ARE MET: (A) IN CLIMATES WHERE THE
 WEATHER IS SEVERE, THE MONTHLY EMERGENCY EGRESS AND
 RELOCATION DRILLS SHALL BE PERMITTED TO BE DEFERRED.
 (B) THE REQUIRED NUMBER OF EMERGENCY EGRESS AND
 RELOCATION DRILLS SHALL BE CONDUCTED, AND NOT LESS THAN
 FOUR SHALL BE CONDUCTED BEFORE THE DRILLS ARE DEFERRED.
 (2) ALL OCCUPANTS OF THE BUILDING SHALL PARTICIPATE IN
 THE DRILL. (3) ONE ADDITIONAL EMERGENCY EGRESS AND
 RELOCATION DRILL, OTHER THAN FOR DAY-CARE OCCUPANCIES
 THAT ARE OPEN ON A YEAR-ROUND BASIS, SHALL BE REQUIRED
 WITHIN THE FIRST 30 DAYS OF OPERATION.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF SITE ADMINISTRATORS AND STAFF MEMBERS TO
 INSPECT ALL EXIT FACILITIES DAILY TO ENSURE THAT ALL
 STAIRWAYS, DOORS, AND OTHER EXITS ARE IN PROPER
 CONDITION. OPEN PLAN BUILDINGS SHALL REQUIRE EXTRA
 SURVEILLANCE TO ENSURE THAT EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTION AND ARE OBVIOUS.
  
 DOORS SHALL BE INSPECTED AND TESTED ANNUALLY AND A
 WRITTEN RECORD SHALL BE SIGNED AND KEPT FOR INSPECTION
 BY THE AUTHORITY HAVING JURISDICTION.
  
 ARTWORK AND TEACHING MATERIALS SHALL BE PERMITTED TO BE
 ATTACHED DIRECTLY TO THE WALLS IN ACCORDANCE WITH THE
 FOLLOWING: (1) THE ARTWORK AND TEACHING MATERIALS SHALL
 NOT EXCEED 20 PERCENT OF THE WALL AREA IN A BUILDING
 THAT IS NOT PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM (2) THE ARTWORK
 AND TEACHING MATERIALS SHALL NOT EXCEED 50 PERCENT OF
 THE WALL AREA IN A BUILDING THAT IS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-04 Cont ID  
Sent By albarran Date 2014-06-04 Time 18:53 Rev Time 0.00
Received By albarran Date 2014-05-13 Time 10:40 Sent To PC
Notes
2014-06-04 18:54:14PROCESSED AND SENT TO READY RACK "V"
2014-05-15 10:40:46RESUBMITTAL SENT TO B7 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-13 Cont ID  
Sent By skennedy Date 2014-02-13 Time 11:15 Rev Time 0.00
Received By skennedy Date 2014-01-16 Time 06:58 Sent To  
Notes
2014-01-25 14:14:40B10
  
  
2014-01-18 06:58:31SENT TO ZONING

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-06-04 Cont ID  
Sent By jwitmer Date 2014-06-04 Time 16:34 Rev Time 0.00
Received By jwitmer Date 2014-06-04 Time 16:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-06-04 Cont ID  
Sent By jwitmer Date 2014-06-04 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2014-06-04 Time 11:35 Sent To  
Notes
2014-06-04 11:35:21BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-02-03 Cont ID  
Sent By jwitmer Date 2014-02-03 Time 18:23 Rev Time 0.00
Received By jwitmer Date 2014-02-03 Time 18:23 Sent To  
Notes
2014-02-03 18:23:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-02-01 Cont ID  
Sent By skennedy Date 2014-02-01 Time 14:59 Rev Time 0.00
Received By skennedy Date 2014-02-01 Time 14:59 Sent To  
Notes
2014-02-01 15:00:03PLAN REVIEW BY JSAEZ PX 1328

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-04 Cont ID  
Sent By jwitmer Date 2014-06-04 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2014-06-04 Time 11:31 Sent To  
Notes
2014-06-04 11:34:41PLUMBING PLAN REVIEW
 PERMIT: 14010860
 ADD: 2500 METROCENTRE BLVD SUITE # 1
 CONT: TO BE DETERMINED
 TEL: (561)786-486-9513
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY 04/2014
 ACTION: PLUMBING PROVISO
  
 TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT
 DAYCARE OCCUPANCY 4911 SQ FT APPROX
 BLDG TYPE 3B
  
 1) DRINKING FOUNTAINS 2 REQUIRED, 2010 FL ACCESS CODE
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
  
 602.1 GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307
 AND 602.
  
 602.2 CLEAR FLOOR SPACE.UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL
 BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE THE
 SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND AND IS 31/2 INCHES (90 MM) MAXIMUM FROM
 THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS.
  
 602.3 OPERABLE PARTS.OPERABLE PARTS SHALL COMPLY WITH
 309.
  
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 602.5 SPOUT LOCATION.THE SPOUT SHALL BE LOCATED 15
 INCHES (380 MM) MINIMUM FROM THE VERTICAL SUPPORT AND 5
 INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE OF THE
 UNIT, INCLUDING BUMPERS.
  
 602.6 WATER FLOW.THE SPOUT SHALL PROVIDE A FLOW OF
 WATER 4 INCHES (100 MM) HIGH MINIMUM AND SHALL BE
 LOCATED 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE
 UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED
 HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT.
 WHERE SPOUTS ARE LOCATED LESS THAN 3 INCHES (75 MM) OF
 THE FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM
 SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED
 BETWEEN 3 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT OF THE UNIT, THE ANGLE OF THE WATER
 STREAM SHALL BE 15 DEGREES MAXIMUM.
  
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-03 Cont ID  
Sent By jwitmer Date 2014-02-03 Time 18:23 Rev Time 0.00
Received By jwitmer Date 2014-02-03 Time 18:01 Sent To  
Notes
2014-02-03 18:22:03PLUMBING PLAN REVIEW
 PERMIT: 14010860
 ADD: 2500 METROCENTRE BLVD SUITE # 1
 CONT: TO BE DETERMINED
 TEL: (561)786-486-9513
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY FEB. 03/2014
 ACTION: DENIED
  
 TOTAL SQ FOOTAGE OF BUILDING 17,973 SQ FT
 DAYCARE OCCUPANCY 5,530 SQ FT APPROX
 BLDG TYPE 3B
  
 2010 FBC-B TABLE 1004.1.1
 PROVIDE A BREAK DOWN ON USE AREAS BY SQ FT:
 PRE-SCHOOL
 OPEN SUPPORT
 THEROPY ROOMS
 OFFICES
 STORAGE ROOMS
  
  
 1) PLEAASE PROVIDE THE MINIMUM FIXTURE COUNT REQUIRRED
 BY 2010 FBC-PLUMBING TABLE 403.1
 WATER CLOSETS MALE/ FEMALE
 LAVATORIES MALE/ FEMALE
 DRINKING FOUNTAINS (2) SEE FOOTNOTE (E) THE MINIMUM
 NUMBER OF REQUIRED DRINKING FOUNTAINS SHALL COMPLY WITH
 TABLE 403.1 AND THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 SERVICE SINK (1) REQUIRED.
  
 2) DRINKING FOUNTAINS 2 REQUIRED, 2010 FL ACCESS CODE
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
  
 602.1 GENERAL.DRINKING FOUNTAINS SHALL COMPLY WITH 307
 AND 602.
  
 602.2 CLEAR FLOOR SPACE.UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL
 BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE THE
 SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND AND IS 31/2 INCHES (90 MM) MAXIMUM FROM
 THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS.
  
 602.3 OPERABLE PARTS.OPERABLE PARTS SHALL COMPLY WITH
 309.
  
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 602.5 SPOUT LOCATION.THE SPOUT SHALL BE LOCATED 15
 INCHES (380 MM) MINIMUM FROM THE VERTICAL SUPPORT AND 5
 INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE OF THE
 UNIT, INCLUDING BUMPERS.
  
 602.6 WATER FLOW.THE SPOUT SHALL PROVIDE A FLOW OF
 WATER 4 INCHES (100 MM) HIGH MINIMUM AND SHALL BE
 LOCATED 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE
 UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED
 HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT.
 WHERE SPOUTS ARE LOCATED LESS THAN 3 INCHES (75 MM) OF
 THE FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM
 SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED
 BETWEEN 3 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT OF THE UNIT, THE ANGLE OF THE WATER
 STREAM SHALL BE 15 DEGREES MAXIMUM.
  
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
  
  
 3) 606 LAVATORIES AND SINKS
  
 606.1 GENERAL. LAVATORIES AND SINKS SHALL COMPLY WITH
 606.
  
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY WITH
 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN OPEN
 FOR 10 SECONDS MINIMUM.
  
 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND
 DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES AND SINKS.
  
  
 4) SEE 2010 FBC-ACCESSIBILITY CODE FOR 604.9 WATER
 CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
 ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE.
 THE REQUIREMENTS IN 604.9 ARE TO BE FOLLOWED WHERE THE
 EXCEPTION FOR CHILDREN?S WATER CLOSETS IN 604.1 IS
 USED. THE FOLLOWING TABLE PROVIDES ADDITIONAL GUIDANCE
 IN APPLYING THE SPECIFICATIONS FOR WATER CLOSETS FOR
 CHILDREN ACCORDING TO THE AGE GROUP SERVED AND REFLECTS
 THE DIFFERENCES IN THE SIZE, STATURE, AND REACH RANGES
 OF CHILDREN AGES 3 THROUGH 12. THE SPECIFICATIONS
 CHOSEN SHOULD CORRESPOND TO THE AGE OF THE PRIMARY USER
 GROUP. THE SPECIFICATIONS OF ONE AGE GROUP SHOULD BE
 APPLIED CONSISTENTLY IN THE INSTALLATION OF A WATER
 CLOSET AND RELATED ELEMENTS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-23 Cont ID  
Sent By llouie Date 2014-01-24 Time 16:09 Rev Time 0.00
Received By llouie Date 2014-01-23 Time 16:09 Sent To B
Notes
2014-01-23 16:10:12ZONING PASSED. SENT TO BUILDING BOX (MISC1) FOR
 REVIEW.LL