2014-01-21 19:00:56 | FUEL GAS PLAN REVIEW |
| PERMIT:14010792 |
| ADD: 720 HILLCREST BLVD |
| CONT: O/B AARON GONZALEZ |
| TEL: (561)856-6655 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WEDNESDAY JAN. 22/2014 |
| ACTION: DENIED |
| |
| PLEASE PROVIDE COMPLIANCE WITH THE FOLLOWING CODE ITEMS |
| MISSING FROM PLANS SUBMITTED; |
| 1). SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2010 FUEL GAS. |
| |
| 2) . TYPE OF GAS, (LP OR NATURAL). |
| |
| 3). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. |
| 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| |
| 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) |
| |
| 5) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| PSI. |
| |
| 6) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| SEC. 502 THRU 505. SEE PAGE 7 AND 50 FOR WHERE HOW |
| CLOSE TO WINDOWS AND DOORS THE UNIT CAN BE PLACED. ON |
| THE ELEVATION DRAWING PROVIDE DIMENSIONS FROM THE SIDE |
| OF THE TANKLESS WATER HEATER TO THE WINDOWS ON EACH |
| SIDE OF THE UNIT. PROVIDE THIS DIMENSION. THE SAME FROM |
| THE TOP OF THE UNIT TO THE SOFFIT. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |