Plan Review Details - Permit 14010792
Plan Review Stops For Permit 14010792
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-01-22 Cont ID  
Sent By jwitmer Date 2014-01-22 Time 16:49 Rev Time 0.00
Received By jwitmer Date 2014-01-22 Time 16:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-01-22 Cont ID  
Sent By jwitmer Date 2014-01-22 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2014-01-22 Time 16:48 Sent To  
Notes
2014-01-21 19:00:56FUEL GAS PLAN REVIEW
 PERMIT:14010792
 ADD: 720 HILLCREST BLVD
 CONT: O/B AARON GONZALEZ
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WEDNESDAY JAN. 22/2014
 ACTION: DENIED
  
 PLEASE PROVIDE COMPLIANCE WITH THE FOLLOWING CODE ITEMS
 MISSING FROM PLANS SUBMITTED;
 1). SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2) . TYPE OF GAS, (LP OR NATURAL).
  
 3). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 5) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 6) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505. SEE PAGE 7 AND 50 FOR WHERE HOW
 CLOSE TO WINDOWS AND DOORS THE UNIT CAN BE PLACED. ON
 THE ELEVATION DRAWING PROVIDE DIMENSIONS FROM THE SIDE
 OF THE TANKLESS WATER HEATER TO THE WINDOWS ON EACH
 SIDE OF THE UNIT. PROVIDE THIS DIMENSION. THE SAME FROM
 THE TOP OF THE UNIT TO THE SOFFIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-22 Cont ID  
Sent By jwitmer Date 2014-01-22 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2014-01-22 Time 13:56 Sent To  
Notes
2014-01-15 10:19:22ROUTED TO PLUMBING $5000 & UNDER