Plan Review Details - Permit 14010620
Plan Review Stops For Permit 14010620
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 12:55 Sent To  
Notes
2014-03-03 13:56:10THIS PERMIT IS FOR LIMITED EXPLORATORY DEMOLITION ONLY
 AS STATED IN THE DESCRIPTION OF WORK ON THE
 APPLICATION. THE SCOPE OF WORK FOR THIS PERMIT IS
 LIMITED DEMOLITION TO DETERMINE THE EXISTING STRUCTURAL
 CONNECTIONS. A SEPARATE APPLICATION, PERMIT AND REVIEWS
 WILL BE REQUIRED TO SHOW THE CONVERSION OF THE GARAGE
 TO AN APARTMENT OR ACCESSORY STRUCTURE.
  
 NOTE:
  
 ACCORDING TO CITY RECORDS, THIS STRUCTURE WAS
 ORIGINALLY CONSTRUCTED AS A DETACHED GARAGE. IT WAS
 CONVERTED TO AN APARTMENT WITH A KITCHEN, BEDROOM AND
 BATHROOM WITHOUT THE REQUIRED PERMITS OR INSPECTIONS.
 UNDER THE 2010 FBC EXISTING BUILDING THIS IS CONSIDERED
 A CHANGE OF OCCUPANCY. IN ORDER FOR THIS STRUCTURE-TO
 BE BROUGHT INTO COMPLIANCE, IT WILL BE REQUIRED TO
 COMPLY WITH THE 2010 FBC EXISTING BUILDING FOR A CHANGE
 OF OCCUPANCY FROM A UTILITY TO AN R-3 OCCUPANCY. THIS
 CHANGE IS FROM A LOWER HAZARD CATEGORY TO A HIGHER ONE.
 THEREFORE, THE FOLLOWING ITEMS WILL NEED TO BE BROUGHT
 INTO COMPLIANCE. THE STRUCTURE WILL BE REQUIRED TO
 COMPLY WITH THE 2010 FBCR WINDLOAD REQUIREMENTS FOR THE
 BUILDING ENVELOPE ( IN ADDITION TO GRAVITY LOADS),
 PRODUCT APPROVALS FOR EXTERIOR DOORS AND WINDOWS,
 EGRESS REQUIREMENTS, LIGHT AND VENTILATION, SMOKE AND
 CARBON MONOXIDE ALARMS, FIRE PROTECTION REQUIREMENTS
 (SEPARATION DISTANCE AND ALLOWABLE OPENINGS), THE
 REQUIREMENTS OF THE 2010 FBC ENERGY CONSERVATION, THE
 REQUIREMENTS OF THE 2010 FBCR MECHANICAL, THE
 REQUIREMENTS OF THE 2010 FBCR PLUMBING AND THE
 ELECTRICAL SYSTEM WILL BE REQUIRED TO COMPLY WITH THE
 2008 NATIONAL ELECTRICAL CODE. THE PLANS WILL NEED TO
 SHOW HOW THE GARAGE WILL BE CONVERTED TO HABITABLE
 SPACE IN COMPLIANCE WITH THE 2010 FBC AND 2008 NEC.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 13:56 Sent To  
Notes
2014-03-03 13:58:35NO ELECTRICAL WORK IS SPECIFIED AS PART OF THIS PERMIT.
 A SEPARATE APPLICATION, PERMIT AND REVIEW IS REQUIRED
 FOR ELECTRICAL WORK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 14:53 Rev Time 0.00
Received By rmcdouga Date 2014-01-13 Time 17:34 Sent To  
Notes
2014-01-17 17:35:17TO SK DESK
  
2014-01-13 17:35:17INCOMING SENT <$5K BUILD BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 12:45 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 12:45 Sent To  
Notes
2014-03-03 12:55:03THE SCOPE OF THIS PERMIT IS TO DO SOME EXPLORATORY
 DEMOLISION TO DETERMINE THE EXISTING STRUCTURAL
 CONNECTIONS. THERE IS AN IMPACT FEE REVIEW STAMP ON TWO
 OF THE PLANS THAT WERE SUBMITTED. BE SURE TO SUBMIT
 THESE STAMPED PLANS WHEN YOU APPLY FOR THE PERMIT TO
 CONVERT THE GARAGE TO HABITABLE SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 12:44 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 12:44 Sent To  
Notes
2014-03-03 13:59:37NO MECHANICAL WORK IS SPECIFIED AS PART OF THIS PERMIT.
 A SEPARATE APPLICATION, PERMIT AND REVIEW IS REQUIRED
 FOR MECHANICAL WORK.
  
 2010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR
 THE HEATING/COOLING EQUIPMENT. FBCR M1401.3
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS THAT MATCHES THE SIZING CALCULATIONS. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE DUCT LOCATION AND SIZES, THE GRILL SIZES
 AND CFMS AT EACH SUPPLY OUTLET, SHOW LOCATION AND SIZE
 OF RETURN DUCTS AND GRILLS. CITY AMENDMENTS 107.3.5.3
  
 4) SHOW THE LOCATION OF THE HVAC EQUIPMENT ON THE
 PLANS. CITY AMENDMENTS 107.3.5.3
  
 5) SHOW THE A/C DISCONNECTS AND EQUIPMENT SERVICING
 RECEPTACLE OUTLET ON THE PLANS. NEC 422.31 AND 210.63
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 09:50 Sent To  
Notes
2014-03-03 11:06:24NO PLUMBING WORK IS SPECIFIED AS PART OF THIS PERMIT. A
 SEPARATE APPLICATION, PERMIT AND REVIEW IS REQUIRED FOR
 PLUMBING WORK.2010 FBC
  
 DENIED BY PLUMBING
  
 1) THE BATHROOM FIXTURES ARE NOT PROPERLY VENTED. THERE
 ARE TWO WET-VENTED FIXTURE DRAINS DISCHARGING UPSTREAM
 OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. THIS IS NOT
 ALLOWED BY CODE. SEE FBCR P3108.2.1
  
 2) THE PLUMBING RISER DIAGRAM DOES NOT MATCH THE FLOOR
 PLAN. THE DRAINS FOR THE CLOTHES WASHER AND THE KITCHEN
 SINK ARE NOT SHOWN. CITY AMENDMENTS 107.2.1 AND
 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 15:18 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 15:18 Sent To  
Notes
2014-03-03 15:22:53THE ZONING COMMENTS FROM THE FIRST REVIEW WILL NEED TO
 BE ADDRESSED WHEN APPLICATIONS ARE MADE FOR SEPARATE
 PERMITS TO CONVERT THE GARAGE TO LIVING SPACE.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-01-28 Cont ID  
Sent By dkittred Date 2014-01-27 Time 17:10 Rev Time 0.00
Received By dkittred Date 2014-01-27 Time 15:26 Sent To  
Notes
2014-01-27 17:10:171/27/14 - SENT BACK TO R06
  
2014-01-27 17:09:38PLANNING AND ZONING COMMENTS: ***FAILED***
 1/27/14
  
 PERMIT IS UNCLEAR IF AS-BUILTS ARE DEPICTING A
 RECREATION ROOM OR ACCESSORY APARTMENT (SEE OPTIONS
 BELOW). PROPERTY IS APPROX. 5,000 SQ. FT. WITH A WIDTH
 OF 50 FT. IN THE MF20 ZONING DISTRICT. AN ACCESSORY
 APARTMENT IS NOT PERMITTED. PLEASE CLARIFY THE REQUEST.
  
 OPTION 1 - STRUCTURE CAN BE UTILIZED AS A DETACHED
 BEDROOM FROM THE MAIN HOUSE WITH BATHROOM, BUT NO
 KITCHEN. THIS SPACE CAN NOT BE RENTED SEPARATELY FROM
 THE MAIN HOUSE. A MICROWAVE, UNDERCOUNTER REFRIGERATOR,
 AND/OR SMALL SINK WOULD ALL BE PERMITTED AND NOT
 CLASSIFIED AS A KITCHEN.
  
 OPTION 2 - THE STRUCTURE CAN BE USED AS A RECREATION
 ROOM, BUT PLANS SHOULD MORE CLEARLY INDICATE AS SUCH AS
 THE PLANS SHOW A BEDROOM, BATHROOM, AND KITCHEN AREA.
  
 PLEASE FEEL FREE TO CALL AND DISCUSS BEFORE RESUBMITTAL
 TO MAKE SURE THE REVISION WILL PASS ZONING REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  