Plan Review Details - Permit 14010565
Plan Review Stops For Permit 14010565
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-16 Cont ID  
Sent By rmcdouga Date 2014-01-16 Time 20:06 Rev Time 0.00
Received By rmcdouga Date 2014-01-16 Time 20:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-10 Cont ID  
Sent By rmcdouga Date 2014-01-10 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2014-01-10 Time 16:11 Sent To  
Notes
2014-01-10 17:14:552010 FBC
  
 DENIED BY BUILDING
  
 1) THIS STRUCTURE IS LOCATED IN 170 MPH VULT WIND SPEED
 EXPOSURE C THE UPLIFT FOR THE FLAT ROOF EXCEEDS THE
 MAXIMUM DESIGN PRESSURE OF THE -60 PSF SPECIFIED ON
 PAGE 22 OF NOA NO.13-0514.10 . SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS117 CALCULATIONS FOR ENHANCED
 FASTENING AT THE PERIMETER AND CORNER ROOF AREAS AS
 REQUIRED BY LIMITATION NUMBER 7 ON PAGE 26 OF THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-01-10 Cont ID  
Sent By fmittner Date 2014-01-10 Time 14:58 Rev Time 0.00
Received By fmittner Date 2014-01-10 Time 14:58 Sent To  
Notes
***NONE***