Plan Review Details - Permit 14010549
Plan Review Stops For Permit 14010549
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-14 Cont ID  
Sent By jwitmer Date 2014-01-14 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2014-01-14 Time 07:49 Sent To  
Notes
2014-01-13 08:50:34ROUTED TO PLUMBING $5000 & UNDER

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-27 Cont ID  
Sent By jwitmer Date 2014-01-27 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2014-01-27 Time 15:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-01-14 Cont ID  
Sent By jwitmer Date 2014-01-14 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2014-01-14 Time 07:49 Sent To  
Notes
2014-01-14 08:06:01 
 PLUMBING PLAN REVIEW
 PERMIT: 14010549
 ADD: 701 NEW JERSEY ST
 CONT:DON LIPSCOMS PLUMBING
 TEL: (561)310-9245
  
 2010 FLORIDA PLUMBING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 14/2014
 ACTION: DENIED
  
 1) PROVIDE THE MANUFACTURERS SPEC SHEETS, IF MORE THAN
 ONE MODEL NUMBER IS LISTED, CIRCLE WHICH UNIT IS TO BE
 INSTALLED. 2010 FBC- R G2413.2.
 NOTE THIS IS AN ELECTRIC WATER HEATER CHANGE OUT,
 TANKLESS WATER HEATER REQUIRE A HIGHER DEMAND ELECTRIC
 SO THE WIRE SIZING FOR THE NEW UNIT WILL ALSO NEED TO
 BE SIZED.
  
 2) A ELECTRICAL SUB-PERMIT MAY ALSO BE REQUIRED BECAUSE
 OF THE ADDITIONAL DEMAND BEING PUT ON THE EXISSTING
 CIRCUIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]