Plan Review Details - Permit 14010493
Plan Review Stops For Permit 14010493
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2014-01-13 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2014-01-13 Time 06:32 Sent To  
Notes
2014-01-13 06:54:131/21/2014
 TODAY DESIGNER ALAN BURST CALLED DISCUSSED PROJECT
 EXISTING OVERHEAD DOORS ARE TO STAY, OKED RED LINING
 REQUIRED EXIT LIGHT. PASSED. JW
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 14010493
 ADD: 219 CLEMATIS ST.
 CONT: SKYE BLU CONSTRUCTION
 TEL: (561)935-7584
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 13/2014
 ACTION: DENIED
  
 1) SHEET A2 PLEASE CLARIFY WITHIN THE AREA OF WORK IN
 THE CREATION OF THE PATIO BAR THE PLANS ARE NOT CLEAR
 AS TO THE INTENT, IS THIS AREA TO BE USED AS EXTERIOR
 SEATING, THE TERM PATIO LEADS ONE TO BELIEVE THIS AREA
 IS EXTERIOR SEATING OR IS THE EXTERIOR GLAZED OVERHEAD
 DOORS NOT TO BE REMOVED. PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3.
  
 IF THE EXTERIOR OVERHEAD DOORS ARE TO BE REMOVED THEN
 THIS MAKES THE NEW WALL & OPENINGS PART OF THE EXTERIOR
 ENVELOPE AS WELL AS THE EXISITNG CEILINGS AND WOULD
 NEED TO BE DESIGNED TO RESIST WIND PRESSURES ANAD ALSO
 DEAL WITH COMPONENTS AND CLADDING AS WELL AS INSULATION
 IN THE NEWLY CONSTRUCTED EXTERIOR WALL.
  
 2) ON NEITHER SHEET A2 NOR THE E SHEETS DOES THERE SHOW
 EXIT LIGHTS, SINCE THE OCCUPANT LOAD IS OVER 50 (2)
 EXITS ARE REQUIRED. TABLE 1015.1/ 1006.3.1.
  
 3) IF IN THE ANSWERING OF COMMENT # 1 THIS IS GOING TO
 NEWLY FORMED EXTERIOR SEATING THEN:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-21 Cont ID  
Sent By skennedy Date 2014-01-21 Time 12:13 Rev Time 0.00
Received By skennedy Date 2014-01-21 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-14 Cont ID  
Sent By lphilmor Date 2014-01-14 Time 14:36 Rev Time 0.00
Received By lphilmor Date 2014-01-14 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-21 Cont ID  
Sent By skennedy Date 2014-01-21 Time 16:48 Rev Time 0.00
Received By skennedy Date 2014-01-09 Time 06:37 Sent To  
Notes
2014-01-10 06:37:37INCOMING SENT TO C11. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-01-18 Cont ID  
Sent By hmoser Date 2014-01-18 Time 13:01 Rev Time 0.00
Received By hmoser Date 2014-01-18 Time 12:52 Sent To  
Notes
2014-01-18 13:00:58MECHANICAL PERMIT NOT REQUIRED
 TO CLEAN GRILLES.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By jwitmer Date 2014-01-13 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2014-01-13 Time 07:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-21 Cont ID  
Sent By aaponte Date 2014-01-21 Time 15:21 Rev Time 0.00
Received By aaponte Date 2014-01-21 Time 15:21 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved