Plan Review Details - Permit 14010429
Plan Review Stops For Permit 14010429
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By skennedy Date 2014-01-13 Time 17:31 Rev Time 0.00
Received By skennedy Date 2014-01-13 Time 17:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By scaldero Date 2014-01-13 Time 14:20 Rev Time 0.00
Received By scaldero Date 2014-01-13 Time 14:20 Sent To E
Notes
2014-01-13 14:27:32PERMIT #14010429
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***PROVISO***
 CEILING MOUNTED DEVICE IN STOCKROOM NEEDS TO BE LOCATED
 TOWARDS CENTER OF ROOM TO ENSURE THAT COVERAGE
 REQUIREMENTS WILL BE MET.
 RELOCATION WILL BE VERIFIED DURING FIELD INSPECTION.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-13 Cont ID  
Sent By skennedy Date 2014-01-13 Time 17:31 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2014-01-09 08:51:15ROUTED TO FIRE