Plan Review Details - Permit 14010249
Plan Review Stops For Permit 14010249
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-10 Cont ID  
Sent By jwitmer Date 2014-01-10 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2014-01-09 Time 15:30 Sent To  
Notes
2014-01-10 06:31:04TO JW DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-08 Cont ID  
Sent By jwitmer Date 2014-01-08 Time 07:41 Rev Time 0.00
Received By jwitmer Date 2014-01-08 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-10 Cont ID  
Sent By jwitmer Date 2014-01-10 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2014-01-10 Time 06:30 Sent To  
Notes
2014-01-10 06:42:45PLUMBING PLAN REVIEW
 PERMIT: 14010249
 ADD: 1700 45TH ST SUITE # 1743
 CONT: DR ROOTER PLUMBING LLC
 TEL: (561)628-1953
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JAN. 10/ 2014
 ACTION: PLUMBING PROVISO APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 DESCRIPTION OF WORK: INSTALLATION OF PORTABLE GREASE
 TRAP UNDER 3 COMPARTMENT SINK.
  
 MET WITH CONTRACTOR BEFORE THE 1ST RESUBMITTAL, HE DID
 NOT PROVIDE THE SIZE OF THE 3 COMPARTMENT SINK, HE DID
 NOT PICK WHICH METHOD OF SIZING OF GREASE INTERCEPTOR
 WAS USED FOR SIZING OF UNIT. MANUFACTURERS SPEC IS FROM
 BK RESOURCES MODEL BK-GT-30. WITH A CAP FLOW RATE OF 15
 G. P.M.
  
 2010FBC-P 1003.3.4.1 GREASE INTERCEPTOR CAPACITY.
 GREASE INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE
 GREASE RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1
 FOR THE FLOW-THROUGH RATES INDICATED.
  
 NOTE IF SIZING USING THE DFU-METHOD DRAINAGE FIXTURE
 UNITS THIS GREASE INTERCEPTOR IS SIZED PROPERLY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-01-08 Cont ID  
Sent By jwitmer Date 2014-01-08 Time 07:41 Rev Time 0.00
Received By jwitmer Date 2014-01-08 Time 07:41 Sent To  
Notes
2014-01-08 07:50:22PLUMBING PLAN REVIEW
 PERMIT: 14010249
 ADD: 1700 45TH ST # 1743
 CONT: DR ROOTER PLUMBING LLC
 TEL: (561)628-0256
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN.08/ 2014
 ACTION: DENIED
  
 DESCRIPTION OF WORK: INSTALLATION OF PORTABLE GREASE
 TRAP UNDER 3 COMPARTMENT SINK.
  
 1A) 2010 FBC-PLUMBING 1003.3.4 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 1B) PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE GREASE
 INTERCEPTOR TO BE INSTALLED. * 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.3.5.1.3 PLUMBING (11)
 GREASE INTERCEPTORS MINIMUM REQUIREMENTS FOR PLUMBING
 COMMERCIAL PLAN REVIEW.
  
 2) 2010 FBC-P 1003.3.4.1 GREASE INTERCEPTOR CAPACITY.
 GREASE INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE
 GREASE RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1
 FOR THE FLOW-THROUGH RATES INDICATED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]