Plan Review Details - Permit 14010226
Plan Review Stops For Permit 14010226
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-26 Cont ID  
Sent By jwitmer Date 2014-03-26 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2014-03-26 Time 16:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-01 Cont ID  
Sent By jwitmer Date 2014-02-01 Time 08:34 Rev Time 0.00
Received By jwitmer Date 2014-02-01 Time 07:06 Sent To  
Notes
2014-02-01 08:34:36BUILDING PLAN REVIEW
 PERMIT: 14010226
 ADD: 319 CLEMATIS ST SUITE # 112
 CONT: CLAY KOHLMEYER
 TEL: (561) 627-3190
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FEB. 01/2014
 ACTION: DENIED
  
 1) THE ADDRESS ON THE PERMIT APPLICATION THE ADDRESS &
 SHEET LS-1 INDICATES 317 AND OR 319 CLEMATIS ST. OR
 BOTH. THE CITY SITE ADDRESS ASWELL AS THE PROPERETY
 APPRAISERS SITE HAVE THE SITE ADDRESS AS 319 CLEMATIS
 ST. THERE CAN ONLY BE ONE SITE ADDRESS FOR EACH
 PROPERTY CONTROL NUMBER. THERE CAN BE SEVERAL TENANT
 ADDRESS, ONE FOR EACH UNIT, THE SUITE NUMBERS WILL
 FLUXUATE DEPENDING ON THE MOVEMENT OF NEW TENNATCYS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF THE PROJECT.
  
 2) THE LIFE SAFETY PLAN INDICATES AN OCCUPANT LOAD OF
 34 OCCUPANTS BUT DOES NOT SHOW THE TABLES AND CHAIRS
 FOR THE OCCUPANTS AND COMPLIANCE WITH 2010 FBC-B 1017.4
 AISLE ACCESSWAYS SEATING AT TABLES, AND COMPLIANCE WITH
 2010 FL ACCESSIBILITY CODE 902.1 GENERAL. DINING
 SURFACES AND WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3.
 ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS.
 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) NOTE THIS IS A CHANGE IN OCCUPANCY AND WILL NEED TO
 BE INDICATED AS SUCH ON THE PERMIT APPLICATION, AND THE
 PLANS WILL NEEDTO BE ASSESSED BY PALM BEACH COUNTY
 IMPACT FEE OFFICE BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-31 Cont ID  
Sent By albarran Date 2014-03-31 Time 19:07 Rev Time 0.00
Received By albarran Date 2014-03-31 Time 17:28 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-06 Cont ID  
Sent By dharvey Date 2014-02-06 Time 14:48 Rev Time 0.00
Received By dharvey Date 2014-02-06 Time 14:48 Sent To  
Notes
2014-02-06 13:21:40BY RL
  
 14010226
 317 CLEMATIS STREET
 INTERIOR CHANGE OF USE TO CAFE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE
 ROOF TOP AIR CONDITIONING EQUIPMENT. NEC 210.63
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND
 WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED.
 NEC 210.8
  
 PROVIDE SHOW WINDOW LIGHTING OUTLETS ABOVE THE WINDOWS.
 NEC 210.62
  
 CLARIFY THE PLANS FOR PHASE AND VOLTAGE. THE PANELS ARE
 SHOWN AS 208 VOLTS AND AS 240 VOLTS. VERIFY THE
 EXISTING SERVICE AND FEEDERS ARE AVAILABLE AS SHOWN.
 NEC 215.5
  
 PROVIDE A SUMMARY LOAD CALCULATION. INCLUDE A CIRCUIT
 AND LOAD FOR THE WATER HEATER. VERIFY THE EXISTING
 SERVICE IS ADEQUATE TO SUPPLY THE NEW RESTAURANT. NEC
 230.31; 220.14; 220.40
  
 VERIFY THE REQUIRED SAFETY LABELING FOR FLASH
 PROTECTION FOR THE ELECTRIC SERVICE, PANEL BOARD AND
 MAIN DISCONNECTING MEANS IS IN PLACE. NEC 110.22,
 110.16, 110.22
  
 VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ADD THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP TO THE LIGHTING SCHEDULE. FBC, ENERGY CONSERVATION
 502.3.8; FBC 1011
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-20 Cont ID  
Sent By lphilmor Date 2014-01-20 Time 15:01 Rev Time 0.00
Received By lphilmor Date 2014-01-14 Time 14:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-02-01 Cont ID  
Sent By jwitmer Date 2014-02-01 Time 10:08 Rev Time 0.00
Received By jwitmer Date 2014-02-01 Time 10:08 Sent To  
Notes
2014-02-01 10:09:21NO GAS IS SHOWN ON THE PLANS. NO RESPONCE NECCESSARY.
 JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-31 Cont ID  
Sent By albarran Date 2014-03-31 Time 19:08 Rev Time 0.00
Received By albarran Date 2014-03-12 Time 14:48 Sent To CRA
Notes
2014-03-31 19:09:16SAK BOX
  
2014-03-12 14:48:34RESUBMITTAL SENT TO C13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-07 Cont ID  
Sent By skennedy Date 2014-02-07 Time 13:39 Rev Time 0.00
Received By skennedy Date 2014-01-07 Time 10:32 Sent To  
Notes
2014-01-08 10:32:47SENT TO C-10. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-04-03 Cont ID  
Sent By skennedy Date 2014-04-03 Time 16:34 Rev Time 0.00
Received By skennedy Date 2014-04-03 Time 16:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-03-26 Cont ID  
Sent By jwitmer Date 2014-03-26 Time 17:56 Rev Time 0.00
Received By jwitmer Date 2014-03-26 Time 17:56 Sent To  
Notes
2014-03-26 17:58:52I'VE SPOKEN WITH PB COUNTY IMPACT FEE OFFICE TO SEE IF
 IT WAS NECESSARY TO TAKE THE PLANS FOR ASSESSMENT SINCE
 THERE IS NO CHANGE IN OCCUPANCY OR SQUARE FOOTAGE, THEY
 SAID YES SINCE IT IS A DIFFERENT USAGE- RESTARANT/
 DELI.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-02-01 Cont ID  
Sent By jwitmer Date 2014-02-01 Time 10:09 Rev Time 0.00
Received By jwitmer Date 2014-02-01 Time 10:09 Sent To  
Notes
2014-02-01 10:10:13BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-03-26 Cont ID  
Sent By jwitmer Date 2014-03-26 Time 17:28 Rev Time 0.00
Received By jwitmer Date 2014-03-26 Time 17:28 Sent To  
Notes
2014-03-26 17:41:51MECHANICAL PLAN REVIEW
 PERMIT: 14010226
 ADD: 319 CLEMATIS ST SUITE # 112
 CONT: CLAY KOHLMEYER
 TEL: (561) 627-3190
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 26/2014
  
 MECHANICAL PROVISO:
  
 1) HOOD TO BE REVIEWED UNDER A SEPARATE PERMIT WITH
 PLANS.
  
 2)MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 2A) PROVIDE PRODUCT APPROVALS FOR THE A/C CONDENSATE
 STAND PER RULE 9N-3 FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G PRE-ENGINEERED A/C STANDS.
  
 2B) FANSKSF-1 & KEF-1 PROVIDE CURB DETAILS, ATTACHMENT
 DETAILS AND ASSOCIATED PRESSURES.
  
 PLUMBING PROVISO:
  
 1) A SEPARATE PERMIT IS REQUIRED FOR A GREASE
 INTERCEPTOR. PROVIDE A CURRENT SIZING METHOD 2010 FBC-P
 1003.3.4 FOR THE GREASE INTERCEPTOR. PDI G101
 TABLE A1.7 IS NO LONGER CURRENT, NOT SINCE THEY DID
 UPDATES IN 2006.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By hmoser Date 2014-02-04 Time 16:13 Rev Time 0.00
Received By hmoser Date 2014-02-04 Time 15:37 Sent To  
Notes
2014-02-04 16:13:21PLAN DENIED
 1) FRESH AIR CALCULATION REQUIRED ON THE PLAN
 PER TABLE 403.3 FBC (M) 2010
 2) HOOD AND COOLERS REQUIRE SEPARATE APPLICATION
 PLAN AND PERMIT.
 3) EQUIPMENT SCHEDULE REQUIRED ON THE PLAN.
 4) ENERGY CALCULATION REQUIRED PER SECTION
 301.2 ENERGY UTILIZATION 2010 FBC (M)
 5) PROVIDE A DETAIL ON THE PLAN FROM THE ENGINEER
 FOR THE CONDENSER STAND TO ROOF TIE DOWN AND
 CONDENSER TO STAND TIE DOWN PER SECTION
 301.12 WIND RESISTANCE. 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-03-26 Cont ID  
Sent By jwitmer Date 2014-03-26 Time 17:55 Rev Time 0.00
Received By jwitmer Date 2014-03-26 Time 17:55 Sent To  
Notes
2014-03-26 17:56:03PLUMBING PLAN REVIEW
 PERMIT: 14010226
 ADD: 319 CLEMATIS ST SUITE # 112
 CONT: CLAY KOHLMEYER
 TEL: (561) 627-3190
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 26/2014
  
 PLUMBING PROVISO:
  
 1) A SEPARATE PERMIT IS REQUIRED FOR A GREASE
 INTERCEPTOR. PROVIDE A CURRENT SIZING METHOD 2010 FBC-P
 1003.3.4 FOR THE GREASE INTERCEPTOR. PDI G101
 TABLE A1.7 IS NO LONGER CURRENT, NOT SINCE THEY DID
 UPDATES IN 2006.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-01 Cont ID  
Sent By jwitmer Date 2014-02-01 Time 10:08 Rev Time 0.00
Received By jwitmer Date 2014-02-01 Time 07:06 Sent To  
Notes
2014-02-01 10:08:29PLUMBING PLAN REVIEW
 PERMIT: 14010226
 ADD: 319 CLEMATIS ST SUITE # 112
 CONT: CLAY KOHLMEYER
 TEL: (561) 627-3190
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW PLUMBING
 DATE: FEB. 01/2014
 ACTION: DENIED
  
 1) SHEET P-2:
  
 1A) WITHIN THE SERVICE WORK AREA THERE IS A FLOOR SINK
 LOCATED ADJACENT TO A ICE MAKER, WILL THE COOLER AND
 FREEZER ALSO DRAIN INTO THE SAME FLOOR SINK? WOULD
 THERE BE ANY OTHER APPLIANCES DRAINING INTO THIS FLOOR
 SINK? 2010 FBC-P 709.4.1 CLEAR-WATER WASTE RECEPTORS.
 WHERE WASTE RECEPTORS SUCH AS FLOOR DRAINS, FLOOR SINKS
 AND HUB DRAINS RECEIVE ONLY CLEAR-WATER WASTE FROM
 DISPLAY CASES, REFRIGERATED DISPLAY CASES, ICE BINS,
 COOLERS AND FREEZERS, SUCH RECEPTORS SHALL HAVE A
 DRAINAGE FIXTURE UNIT VALUE OF ONE-HALF.
 709.3 VALUES FOR CONTINUOUS AND SEMICONTINUOUS FLOW.
 DRAINAGE FIXTURE UNIT VALUES FOR CONTINUOUS AND
 SEMICONTINUOUS FLOW INTO A DRAINAGE SYSTEM SHALL BE
 COMPUTED ON THE BASIS THAT 1 GPM (0.06 L/S) OF FLOW IS
 EQUIVALENT TO TWO FIXTURE UNITS.
  
 1B) PLEASE SEE THE PREP SINK BY THE MIXER, THIS ISNK IS
 NOT IDENTIFIED IN THE PLUMBING FIXTURE SCHEDULE NOR IS
 IT SHOWN ON THE FLAT OR ISOMETRIC WASTE DIAGRAM.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) DIRECTLY EAST OF THE MAIN DOUBLE DOOR ENTRY THE
 PLANS INDICATE A ICE BEN AND REFRIGARATOR, THE PLANS
 ARE MISSING A FLOOR SINK OR HUB DRAIN FOR THE ICE BEN,
 DEPENDING ON THE REFRIGARATOR THERE MAY BE A EVAPORATOR
 NOT NEEDING A FLOOR DRAIN. 2010 FBC-P 709.4.1
 CLEAR-WATER WASTE RECEPTORS. WHERE WASTE RECEPTORS SUCH
 AS FLOOR DRAINS, FLOOR SINKS AND HUB DRAINS RECEIVE
 ONLY CLEAR-WATER WASTE FROM DISPLAY CASES, REFRIGERATED
 DISPLAY CASES, ICE BINS, COOLERS AND FREEZERS, SUCH
 RECEPTORS SHALL HAVE A DRAINAGE FIXTURE UNIT VALUE OF
 ONE-HALF.
  
 1D) JUST TO THE LEFT OF THE RESTROOM THERE IS A NOTE
 FOR THE CONTRACTOR TO VERIFY THE INVERT AND TO CONFIRM
 THERE IS SUFFICIENT FALL FOR THE NEW FIXTURES, THE
 SHEET A-1.0 INDICATES THIS TO BE A CONCRETE COLUMN, ARE
 THE WASTE AND VENT ENCASED IN CONCRETE OR IS THERE A
 CHASE? 107.2.1.3 ADDITIONA LINFORMATION REQUIRED.
  
 1E) NOTES FROM THE BUILDING REVIEW REQUEST A SEATING
 PLAN FOR LIFE SAFETY, THE PLUMBING REVIEW WILL ALSO USE
 THIS PLAN FOR DETERMINING COMPLIANCE WITH 403.2
 SEPERATE FACILITIES
 EXCEPTION # 3 STATES SEPARATE FACILITIES SHALL NOT BE
 REQUIRED IN BUSINESS AND MERCANTILE OCCUPANCIES WITH A
 TOTAL FLOOR AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 IF THE NEW LIFE SAFETY PLAN SHOWS MORE THAN 10 SEATS
 THEY WILL NEED TO COMPLY WITH EXCEPTION # 2 SEPARATE
 FACILITIES SHALL NOT BE REQUIRED FOR FOOD SERVICE
 ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
  
 1F) THE PLUMBING TABLES SET UP UNDER THE HEADING TABLE
 403.1FOR A A2 OCCUPANCY (RESTARAUNT) REQUIRE A SERVICE
 SINK, THE SAME TABLE UNDER A M (MERCANTILE) OCCUPANCY
 DO NOT
 REQUIRE A SERVICE SINK, UNDER THE DEFINITION OF
 ASSEMBLY OCCUPANCY IT INCLUDES FOR THE CONSUMPTION OF
 FOOD OR DRINK, THE BUILDING OFFICIAL SHALL DETERMINE
 FOR THIS USAGE IF A SERVICE SINK IS REQUIRED OR NOT.
  
 1G) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION ON
 THE UNDER COUNTER GREASE INTERCEPTOR AND FLOW RATE
 DEVICE, PLEASE NOTE THE FLOW RATE DEVICE SHALL BE
 VENTED.
 2010 FBC-1003.3.4.2 RATE OF FLOW CONTROLS.
 GREASE INTERCEPTORS AND GREASE TRAPS SHALL BE EQUIPPED
 WITH DEVICES TO CONTROL THE RATE OF WATER FLOW SO THAT
 THE WATER FLOW DOES NOT EXCEED THE RATED FLOW. THE
 FLOW-CONTROL DEVICE SHALL BE VENTED AND TERMINATE NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD RIM LEVEL
 OR BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 1003.2 APPROVAL.
 THE SIZE, TYPE AND LOCATION OF EACH INTERCEPTOR AND OF
 EACH SEPARATOR SHALL BE APPROVED BY THE PLUMBING
 OFFICIAL. WHERE THE INTERCEPTOR OR SEPARATOR IS LOCATED
 WITHIN AN ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM,
 SUCH INTERCEPTOR OR SEPARATOR SHALL BE APPROVED BY THE
 HEALTH OFFICIAL. THE INTERCEPTOR OR SEPARATOR SHALL BE
 DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND THE REQUIREMENTS OF
 THIS SECTION. WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR
 OR SEPARATOR.
  
 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By aaponte Date 2014-01-13 Time 10:35 Rev Time 0.00
Received By aaponte Date 2014-01-13 Time 10:35 Sent To  
Notes
2014-01-13 10:39:14INTERIOR BUILD-OUT FOR A CAFE.
2014-01-09 11:04:071/9/14