2014-01-10 07:44:51 | 2010 FBC |
| |
| REVISION IS DENIED BY BUILDING |
| |
| 1) SHEET F.01 FOR THE THE CONCRETE BLOCK AND WOOD FENCE |
| CAN NOT BE SUBMITTED AS A REVISION. A SEPARATE PERMIT, |
| APPLICATION AND REVIEW IS REQUIRED FOR FENCE PERMITS. |
| NOTE: STRUCTURAL DETAILS SHOWING THE SIZE AND LOCATION |
| OF VERTICAL REINFORCING STEEL IN THE FILLED CELLS AND |
| THE HORIZONTAL REINFORCING STEEL IN THE TIE BEAM WILL |
| BE REQUIRED. |
| |
| 2) THE FRAMING PLAN ON SHEET T.01 IS LABELED FLOOR ROOF |
| PLAN. IT APPEARS TO BE A ROOF FRAMING PLAN. PLEASE |
| CLARIFY. CITY AMENDMENTS 107.2.1 |
| |
| 3) HETA 20 CONNECTORS ARE SPECIFIED IN THE DETAIL FOR |
| ANCHORING THE EXISTING (C) TRUSSES TO THE CBS WALL AND |
| AT THE WALL ON THE WOOD BEAM DETAIL (B). THIS IS AN |
| EMBED ANCHOR DESIGNED TO ANCHOR ROOF TRUSSES TO THE TOP |
| OF A TIE BEAM AND CAN NOT BE USED TO SUPPORT THE |
| VERTICAL GRAVITY LOADS OF THE TRUSSES. PLEASE CLARIFY. |
| FBC R801.2 |
| |
| 4) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECS., SPAN |
| AND LOAD TABLES FOR THE LAMINATED VENEER LUMBER BEAMS |
| THAT ARE SPECIFIED ON THE PLANS. FBC R801.2 |
| |
| 5) SPECIFY THE CONNECTORS FOR THE EXISTING 2 X 4 WOOD |
| FRAME CEILING THAT ARE SHOWN IN THE CONNECTOR TO |
| TRUSSES (A) DETAIL. THESE APPEAR TO BE TRUSS HANGER |
| THAT IS HANGING BELOW THE BOTTOM CORD OF THE TRUSS IN A |
| APPLICATION FOR WHICH IT WAS NOT DESIGNED. PLEASE |
| CLARIFY. CITY AMENDMENTS 107.2.1 |
| |
| 6) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR |
| THE LVL BEAMS TO THE EXISTING WALLS. FBC R801.2 |
| |
| 7) SPECIFY THE TYPE AND LOCATION OF ALL CONNECTORS, THE |
| TYPE AND NUMBER OF FASTENERS THAT WILL BE USED FOR EACH |
| APPLICATION AND THE REQUIRED UPLIFT OR GRAVITY LOAD |
| DESIGN AT EACH LOCATION. FBC R802.1.9 |
| |
| 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR EACH |
| CONNECTOR SPECIFIED OR PROVIDE AN ANCHOR SCHEDULE WITH |
| THE PRODUCT APPROVAL SPECIFIED FOR EACH CONNECTOR. DCA |
| RULE 9N-3 |
| |
| 9) THE ORIGINAL PERMIT DID NOT INCLUDE THE COSTS OF THE |
| STRUCTURAL ROOF REPAIRS SHOWN IN THE REVISED DRAWINGS. |
| PLEASE SPECIFY THE INCREASE IN VALUE OF WORK ON THE |
| REVISION FORM WHEN THIS REVISION IS RE-SUBMITTED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |