Plan Review Details - Permit 14010016
Plan Review Stops For Permit 14010016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-02 Cont ID  
Sent By skennedy Date 2014-01-02 Time 13:38 Rev Time 0.00
Received By skennedy Date 2014-01-02 Time 13:38 Sent To  
Notes
2014-01-02 13:39:20OTHER PORTIONS OF ROOF WERE APPROVED IN 2008.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-02 Cont ID  
Sent By skennedy Date 2014-01-02 Time 13:19 Rev Time 0.00
Received By skennedy Date 2014-01-02 Time 13:19 Sent To  
Notes
2014-01-02 13:23:13IT APPEARS FROM THE SUBMITTED DRAWING THAT THE ENTIRE
 ROOF CONSTITUTES ONE ROOF SECTION AND THIS APPLICATION
 IS TO REPLACE MORE THAN 25% OF THE ROOF COVERING. THIS
 IS NOT ALLOWABLE BASED UPON THE SECTION BELOW.
 FBC EXISTING BUILDINGS - 611.1.1 - NOT MORE THAN 25
 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION OF ANY
 EXISTING BUILDING OR STRUCTURE SHALL BE REPAIRED,
 REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD UNLESS THE
 ENTIRE ROOFING SYSTEM OR ROOF SECTION CONFORMS TO
 REQUIREMENTS OF THIS CODE.
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  