Plan Review Details - Permit 13121128
Plan Review Stops For Permit 13121128 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-01-13 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-01-13 |
Time |
17:58 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-01-13 |
Time |
17:58 |
Sent To |
I |
|
Notes |
2014-01-13 17:59:54 | AS NOTED ON THE APPROVED PLANS, | | A SEPARATE GAS PERMIT IS REQUIRED |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2014-01-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-01-16 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-01-16 |
Time |
15:53 |
Sent To |
|
|
Notes |
2014-01-16 17:51:17 | 2010 FBC | | | | GAS REVIEW IS DENIED | | | | 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER FBC | | 2010 FUEL GAS. | | | | 2) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED AND ALL | | PIPE SIZES. | | | | 3) SPECIFY TYPE OF GAS (LP OR NATURAL) | | | | 4) SPECIFY THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | BTU LOAD ON THE SYSTEM. REFER TO THE 2010 FBC FUEL GAS | | SPECS. 401.8 THRU 402.6.1 / G2412.8 THRU G2413.6.1 AND | | TABLES 402.4(1) THRU 402.4 (35) / G2413.4 (1) THRU | | G2413.4(8). | | | | 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY (METER) | | TO THE MOST REMOTE OUTLET IN THE SYSTEM PER 2010 FBC | | FUEL GAS APPENDIX A - USE OF CAPACITY SECTION A.3.1(4) | | | | 6) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC 2010 | | FUEL GAS SEC. 402.2 & G2413.2. IF NATURAL GAS SPECIFY | | .5 PSI OR 2 PSI. | | | | 7) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | NFPA 58 AND FUEL GAS SEC. 402.2 & G2413.2. | | | | 8) THE NAME AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-01-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-01-16 |
Time |
18:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-12-30 |
Time |
13:54 |
Sent To |
|
|
Notes |
2014-01-16 12:41:17 | 1/16 ROUTED TO RM DESK FOR GAS REVIEW | | | | | | | 2014-01-14 08:35:29 | CONTRACTOR REQUIRED - DISCUSSED WITH OWNER | | | | | 2014-01-13 18:01:03 | DO NOT ISSUE UNTIL A GAS PERMIT IS SECURED. | | SH DESK | 2013-12-30 13:54:29 | ROUTED TO ELEC $5000 & UNDER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-01-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-01-16 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-01-16 |
Time |
17:52 |
Sent To |
|
|
Notes |
2014-01-16 18:19:35 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) A PLUMBING SUB PERMIT IS REQUIRED. | | | | 2) SUBMIT 2 COPIES OF A POOL PIPING DRAWING SHOWING THE | | PIPE SIZES AND THE PIPE ROUTING TO THE NEW HEATER AND | | THE EXISTING POOL EQUIPMENT. CITY AMENDMENTS 107.1 | | | | 3) PROVIDE AN ANCHORING DETAIL FOR THE POOL HEATER. | | SPECIFY THE PAD AND HOW THE HEATER WILL BE ANCHORED TO | | IT TO RESIST THE 170 MPH WINDSPEED. FBCR 301.1 | | | | 4) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SEC. | | 403.9.2 FOR THE REQUIRED TIME SWITCH TO CONTROL THE | | POOL HEATER. | | | | 5) A POOL COVER IS REQUIRED BY FBC ENERGY CONSERVATION | | SEC. 403.9.3 FOR HEATED POOLS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
|