Plan Review Details - Permit 13121128
Plan Review Stops For Permit 13121128
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By albarran Date 2014-01-13 Time 17:58 Rev Time 0.00
Received By albarran Date 2014-01-13 Time 17:58 Sent To I
Notes
2014-01-13 17:59:54AS NOTED ON THE APPROVED PLANS,
 A SEPARATE GAS PERMIT IS REQUIRED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-01-16 Cont ID  
Sent By rmcdouga Date 2014-01-16 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2014-01-16 Time 15:53 Sent To  
Notes
2014-01-16 17:51:172010 FBC
  
 GAS REVIEW IS DENIED
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER FBC
 2010 FUEL GAS.
  
 2) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED AND ALL
 PIPE SIZES.
  
 3) SPECIFY TYPE OF GAS (LP OR NATURAL)
  
 4) SPECIFY THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2010 FBC FUEL GAS
 SPECS. 401.8 THRU 402.6.1 / G2412.8 THRU G2413.6.1 AND
 TABLES 402.4(1) THRU 402.4 (35) / G2413.4 (1) THRU
 G2413.4(8).
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY (METER)
 TO THE MOST REMOTE OUTLET IN THE SYSTEM PER 2010 FBC
 FUEL GAS APPENDIX A - USE OF CAPACITY SECTION A.3.1(4)
  
 6) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC 2010
 FUEL GAS SEC. 402.2 & G2413.2. IF NATURAL GAS SPECIFY
 .5 PSI OR 2 PSI.
  
 7) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58 AND FUEL GAS SEC. 402.2 & G2413.2.
  
 8) THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-16 Cont ID  
Sent By shill Date 2014-01-16 Time 18:20 Rev Time 0.00
Received By rmcdouga Date 2013-12-30 Time 13:54 Sent To  
Notes
2014-01-16 12:41:171/16 ROUTED TO RM DESK FOR GAS REVIEW
  
  
  
2014-01-14 08:35:29CONTRACTOR REQUIRED - DISCUSSED WITH OWNER
  
  
2014-01-13 18:01:03DO NOT ISSUE UNTIL A GAS PERMIT IS SECURED.
 SH DESK
2013-12-30 13:54:29ROUTED TO ELEC $5000 & UNDER

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-01-16 Cont ID  
Sent By rmcdouga Date 2014-01-16 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2014-01-16 Time 17:52 Sent To  
Notes
2014-01-16 18:19:352010 FBC
  
 DENIED BY PLUMBING
  
 1) A PLUMBING SUB PERMIT IS REQUIRED.
  
 2) SUBMIT 2 COPIES OF A POOL PIPING DRAWING SHOWING THE
 PIPE SIZES AND THE PIPE ROUTING TO THE NEW HEATER AND
 THE EXISTING POOL EQUIPMENT. CITY AMENDMENTS 107.1
  
 3) PROVIDE AN ANCHORING DETAIL FOR THE POOL HEATER.
 SPECIFY THE PAD AND HOW THE HEATER WILL BE ANCHORED TO
 IT TO RESIST THE 170 MPH WINDSPEED. FBCR 301.1
  
 4) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SEC.
 403.9.2 FOR THE REQUIRED TIME SWITCH TO CONTROL THE
 POOL HEATER.
  
 5) A POOL COVER IS REQUIRED BY FBC ENERGY CONSERVATION
 SEC. 403.9.3 FOR HEATED POOLS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]