Plan Review Details - Permit 13120954
Plan Review Stops For Permit 13120954
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 17:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-28 Cont ID  
Sent By rmcdouga Date 2014-04-28 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2014-04-28 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 17:56 Sent To  
Notes
2014-03-03 18:41:132010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS.
 NEC 408.30
  
 2) SUBMIT TWO COPIES OF A PANEL SCHEDULE AND SPECIFY
 THE AIC RATING OF THE NEW EQUIPMENT. NEC 408.4 AND
 110.9
  
 3) SPECIFY THE LOCATION OF THE METER AND THE PANEL ON
 THE PLANS. CITY AMENDMENTS 107.2.1 AND NEC 240.24
  
 4) SHOW THE LOCATIONS OF THE DISCONNECTS FOR THE NEW
 A/C EQUIPMENT AND THE EQUIPMENT SERVICING RECEPTACLE
 OUTLET. NEC 440.14 AND 210.63
  
 5) PROVIDE THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN ON THE ELECTRICAL PLANS.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-01-07 Cont ID  
Sent By fmittner Date 2014-01-07 Time 10:42 Rev Time 0.00
Received By fmittner Date 2014-01-07 Time 10:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-28 Cont ID  
Sent By rmcdouga Date 2014-04-28 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2014-04-15 Time 07:15 Sent To  
Notes
2014-04-15 07:16:15INCOMING SENT TO ROBERT MCDOUGAL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2013-12-23 Time 09:43 Sent To  
Notes
2013-12-26 09:44:33R13
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-28 Cont ID  
Sent By rmcdouga Date 2014-04-28 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2014-04-28 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 17:23 Sent To  
Notes
2014-03-03 17:44:572010 FBC
  
 MECHANICAL IS DENIED
  
 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 AS REQUIRED BY FBCR M1401.3.
  
 2) SPECIFY THE CFMS AT EACH SUPPLY OUTLET. CITY
 AMENDMENTS 107.3.5.3
  
 3) THE RETURN AIR TRANSFER DUCTS ARE UNDER SIZED. FBCR
 M1602.4 BALANCED RETURN AIR REQUIRES THE TRANSFER DUCTS
 TO BE 1.5 TIMES THE CROSS-SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM AND THE DOOR HAVING AT LEAST A
 ONE INCH UNDERCUT.
  
 4) THE ADDRESS OF THE PROJECT, THE NAME AND LICENSE
 NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED ON THE MECHANICAL PLANS. CITY AMENDMENTS
 107.2.1
  
 5) THE AIR-HANDLER APPEARS TO BE LOCATED IN A CLOSET.
 SPECIFY THE RETURN GRILL SIZE AND LOCATION OR IF THE
 CLOSET HAS A LOUVERED DOOR. CITY AMENDMENTS 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-03 Cont ID  
Sent By rmcdouga Date 2014-03-03 Time 17:56 Rev Time 0.00
Received By rmcdouga Date 2014-03-03 Time 17:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-07 Cont ID  
Sent By dkittred Date 2014-01-07 Time 10:40 Rev Time 0.00
Received By fmittner Date 2014-01-02 Time 15:01 Sent To  
Notes
2014-01-02 15:22:30HISTORIC - SENT TO FM 1/2/14. DK