Plan Review Details - Permit 13120872
Plan Review Stops For Permit 13120872 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-01-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-01-03 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-01-03 |
Time |
14:33 |
Sent To |
Z |
|
Notes |
2014-01-03 14:33:44 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE ENGINEER (LARRY M. SMITH FL PE 45997) THAT | | IS LISTED IN THE TITLE BLOCK. FS 471 AND FAC | | 61G15-23.002 | | | | 2) SPECIFY THE WIND LOAD DESIGN CRITERIA FOR THE | | EQUIPMENT SUPPORT STANDS ON THE PLANS. FBC 1609.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-01-02 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-01-02 |
Time |
19:37 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-01-02 |
Time |
19:33 |
Sent To |
B |
|
Notes |
2014-01-02 19:37:40 | THIS PERMIT IS BEING CONDITIONALLY APPROVED AS | | MENTIONED BELOW: | | 1.THE SUBMITTED DRAWING DOES NOT INDICATE WHO WILL BE | | RESPONSIBLE FOR THE SERVICE LATERAL, UNLESS IT IS | | SUPPLIED BY THE LOCAL UTILITY, IT SHALL COMPLY WITH NEC | | 300.5(B) | | 2. ANY OTHER CONDUCTORS RUNNING UNDERGROUND SHALL BE | | COMPLIANT WITH 300.0(B) AS WELL. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-01-09 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-01-09 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2013-12-19 |
Time |
14:48 |
Sent To |
|
|
Notes |
2013-12-19 14:48:16 | ROUTED TO ELECTRICAL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-01-09 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-01-09 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-01-09 |
Time |
17:35 |
Sent To |
I |
|
Notes |
2014-01-09 17:36:35 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) APPROPRIATE SCREENING MUST BE PROVIDED FOR ALL | | MECHANICAL EQUIPMENT. THE WALLS OF THE FENCING SHALL BE | | LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT | | INTERVALS. (ZLDR S.94-444(B)) | | | | 2.) A SEPARATE LANDSCAPE PERMIT IS REQUIRED FOR | | LANDSCAPE SCREENING IMPROVEMENTS. | | | | PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL | | COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1442 IF YOU | | HAVE QUESTIONS. | | |
|
|
|