Plan Review Details - Permit 13120870
Plan Review Stops For Permit 13120870
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-03 Cont ID  
Sent By rmcdouga Date 2014-01-03 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2014-01-03 Time 14:30 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-03 Cont ID  
Sent By rmcdouga Date 2014-01-03 Time 14:31 Rev Time  
Received By rmcdouga Date   Time   Sent To  
Notes
2014-01-02 19:41:57THIS PERMIT IS BEING CONDITIONALLY APPROVED AS
 MENTIONED BELOW:
 1.THE SUBMITTED DRAWING DOES NOT INDICATE WHO WILL BE
 RESPONSIBLE FOR THE SERVICE LATERAL, UNLESS IT IS
 SUPPLIED BY THE LOCAL UTILITY, IT SHALL COMPLY WITH NEC
 300.5(B)
 2. ANY OTHER CONDUCTORS RUNNING UNDERGROUND SHALL BE
 COMPLIANT WITH 300.0(B) AS WELL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By Mgonzale Date 2014-01-13 Time   Rev Time 1.00
Received By mgonzale Date 2014-01-13 Time   Sent To I
Notes
2014-01-13 07:52:31OBTAIN ROW PERMIT
  
 [email protected]
 (561) 494-1085

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jlmitch Date 2013-12-19 Time 14:47 Sent To  
Notes
2013-12-19 14:47:55ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 1 Status N Date 2014-01-08 Cont ID  
Sent By llouie Date 2014-01-08 Time 15:42 Rev Time 0.00
Received By llouie Date 2014-01-08 Time 15:42 Sent To  
Notes
2014-01-08 15:43:19ZONING AND LAND DEVELOPMENT REGULATIONS DOES NOT
 REGULATE STRUCTURES WITHIN RIGHT-OF-WAY. ADDED
 ENGINEERING STOP FOR REVIEW. LL