Plan Review Details - Permit 13120868
Plan Review Stops For Permit 13120868 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-01-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-01-03 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-01-03 |
Time |
14:27 |
Sent To |
Z |
|
Notes |
2014-01-03 14:27:47 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE ENGINEER (LARRY M. SMITH FL PE 45997) THAT | | IS LISTED IN THE TITLE BLOCK. FS 471 AND FAC | | 61G15-23.002 | | | | 2) SPECIFY THE WIND LOAD DESIGN CRITERIA FOR THE | | EQUIPMENT SUPPORT STANDS ON THE PLANS. FBC 1609.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-01-02 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-01-02 |
Time |
19:22 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-01-02 |
Time |
19:17 |
Sent To |
B |
|
Notes |
2014-01-02 19:22:58 | THIS PERMIT IS BEING CONDITIONALLY APPROVED AS | | MENTIONED BELOW: | | 1.THE SUBMITTED DRAWING DOES NOT INDICATE WHO WILL BE | | RESPONSIBLE FOR THE SERVICE LATERAL, UNLESS IT IS | | SUPPLIED BY THE LOCAL UTILITY, IT SHALL COMPLY WITH NEC | | 300.5(B) | | 2. ANY OTHER CONDUCTORS RUNNING UNDERGROUND SHALL BE | | COMPLIANT WITH 300.0(B) AS WELL. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2014-01-10 |
|
|
Cont ID |
|
Sent By |
Mgonzale |
Date |
2014-01-10 |
Time |
|
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2014-01-10 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
jlmitch |
Date |
2013-12-19 |
Time |
14:47 |
Sent To |
|
|
Notes |
2013-12-19 14:47:14 | ROUTED TO ELECTRICAL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2014-01-09 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2014-01-09 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2014-01-09 |
Time |
17:39 |
Sent To |
ENG |
|
Notes |
2014-01-09 17:40:13 | ZONING REVIEW NOT REQURIED. ZLDR DOES NOT REGULATE | | STRUCTURES WITHIN ROW. FORWARDED TO ENGINEERING FOR | | REVIEW. |
|
|
|