Plan Review Details - Permit 13120739
Plan Review Stops For Permit 13120739
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-13 Cont ID  
Sent By albarran Date 2014-01-13 Time 09:05 Rev Time 0.00
Received By albarran Date 2014-01-13 Time 08:55 Sent To I
Notes
2014-01-13 09:07:37A REVIEW OF MY PREVIOUS MOTES WILL SHOW THAT THIS WAS
 APPROVED BY ME ON THE FIRST GO AROUND AND THE NOTES
 WERE MERELY COMMENTS TO AVOID ISSUES LATER. PREVENTIVE
 MEDICINE

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-17 Cont ID  
Sent By albarran Date 2013-12-17 Time 17:35 Rev Time 0.00
Received By albarran Date 2013-12-17 Time 17:08 Sent To I
Notes
2013-12-17 17:39:39THE FOLLOWING ARE AMONG THE NEC REQUIREMENTS NOT
 ADDRESSED BUT COMMONLY MISSED. PLEASE ADDRESS THESE AS
 NECESSARY:
 1. AS PER NEC 550.16 DRYERS REQUIRE A 4 WIRE
 CONNECTION.
 2. AS PER NEC 406.8 ALL 15 & 20 AMP RECEPTACLES IN WET
 OR DAMP LOCATIONS SHALL BE LISTED "WR", WEATHER
 RESISTANT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-13 Cont ID  
Sent By shill Date 2014-01-13 Time 17:26 Rev Time 0.00
Received By shill Date 2014-01-10 Time 06:49 Sent To  
Notes
2014-01-13 09:08:28SH DESK
  
2014-01-11 06:50:12SENT TO M ALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-19 Cont ID  
Sent By jlmitch Date 2013-12-19 Time 09:13 Rev Time 0.00
Received By jlmitch Date 2013-12-17 Time 16:30 Sent To  
Notes
2013-12-17 17:41:46SENT TO SH DESK
  
2013-12-17 16:30:17ROUTED TO ELEC $5000 & UNDER