Plan Review Details - Permit 13120556
Plan Review Stops For Permit 13120556
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2013-12-16 Cont ID  
Sent By skennedy Date 2013-12-16 Time 09:14 Rev Time 0.00
Received By skennedy Date 2013-12-16 Time 09:14 Sent To Z
Notes
2013-12-16 09:15:01EXEMPT

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-02-04 Cont ID  
Sent By wjolin Date 2014-02-04 Time 09:45 Rev Time 0.00
Received By wjolin Date 2014-02-04 Time 09:42 Sent To  
Notes
2014-02-04 09:45:238100 IBIS BOULEVARD
 PERMIT #13120556
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **CONTRACTOR TO SCHEDULE A #131 FIRE FINAL INSPECTION
 PRIOR TO OCCUPANCY**
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-01-02 Cont ID  
Sent By wjolin Date 2014-01-02 Time 12:44 Rev Time 0.00
Received By wjolin Date 2014-01-02 Time 12:37 Sent To  
Notes
2014-01-02 12:44:138100 IBIS BOULEVARD
 PERMIT #13120556
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **CONTRACTOR TO SCHEDULE A #131 FIRE FINAL INSPECTION
 PRIOR TO OCCUPANCY**
  
 NO FLOOR PLANS SUBMITTED.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO STAIR, HANDRAIL OR GUARDRAIL DETAILS SUBMITTED.
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE. HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF THE STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN
 34 INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS
 SHALL BE RETURNED TO THE WALL OR FLOOR OR SHALL
 TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION SHALL
 HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT
 MORE THAN 2 INCHES. STAIR RISERS SHALL BE BETWEEN 4
 INCHES AND 7 INCHES IN HEIGHT. STAIRS SHALL BE SLIP
 RESISTANT AND HAVE A MINIMUM TREAD DEPTH OF 11 INCHES
 AND PREVENT THE ACCUMULATION OF WATER.
  
 NOT ENOUGH INFORMATION SUBMITTED TO CONDUCT A THOROUGH
 AND COMPLETE PLAN REVIEW AT THIS TIME.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-04 Cont ID  
Sent By wjolin Date 2014-02-04 Time 09:45 Rev Time 0.00
Received By wjolin Date 2014-01-31 Time 10:55 Sent To  
Notes
2014-01-31 10:56:14INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-02 Cont ID  
Sent By wjolin Date 2014-01-02 Time 12:45 Rev Time 0.00
Received By wjolin Date 2013-12-13 Time 09:13 Sent To  
Notes
2014-01-02 11:48:29TO FIRE
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-31 Cont ID  
Sent By avann Date 2013-12-31 Time 10:47 Rev Time 0.00
Received By ajones Date 2013-12-17 Time 10:06 Sent To  
Notes
2013-12-17 10:06:3312/17/13 - ZONING RECEIVED. SENT TO AV FOR REVIEW. LL