Plan Review Details - Permit 13120526
Plan Review Stops For Permit 13120526
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-23 Cont ID  
Sent By rmcdouga Date 2014-01-23 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-01-22 Time 18:39 Sent To  
Notes
2014-01-23 08:54:50APPROVED WITH EXCEPTION. SEE NOTES ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By rmcdouga Date 2013-12-12 Time 19:09 Rev Time 0.00
Received By rmcdouga Date 2013-12-12 Time 17:45 Sent To  
Notes
2013-12-12 19:09:552010 FBC / 2008 NEC
  
 THE SCOPE OF WORK FOR THIS PROJECT IS TO WIRE AN
 EXISTING 1434 SQFT RESIDENTIAL STRUCTURE THAT WAS
 COMPLETELY GUTTED (ALL INTERIOR WALLS WERE REMOVED)
 THAT WILL HAVE AN ADDITIONAL 112 SQFT ADDED TO IT FOR A
 TOTAL OF 2546 SQFT.
  
 DENIED BY ELECTRICAL
  
 1) PROVIDE TWO SETS OF PLANS WITH A SERVICE RISER
 DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING
 DETAIL. NEC 230, 250
  
 2) PROVIDE COMPLETE LOAD CALCULATIONS. NEC 220.40
  
 3) PROVIDE COMPLETE PANEL SCHEDULES. NEC 240
  
 4) SPECIFY THE METER AND PANEL LOCATIONS ON THE FLOOR
 PLANS. NEC 230, 408
  
 5) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT.
 NEC 110.9
  
 6) LABEL THE ROOMS ON THE ELECTRICAL FLOOR PLANS,
 SPECIFY THE LOCATIONS OF THE AIR HANDLERS, CONDENSING
 UNITS, WATER HEATER, WASHER, DRYER, KITCHEN COUNTER
 TOPS, BATHROOM BASINS, TUBS AND SHOWERS ON THE FLOOR
 PLAN TO SHOW COMPLIANCE WITH NEC 210.52, 210.63,
 406.8(B)
  
 7) SHOW COMPLIANCE WITH NEC 210.8 GFCI, 210.12 AFCI,
 406.11 TAMPER-RESISTANT RECEPTACLES WHERE REQUIRED.
  
 8) THESE PLANS SHOW A FIREPLACE THAT IS NOT SHOWN ON
 THE MASTER PLANS. IF THERE IS A FIREPLACE CARBON
 MONOXIDE DETECTORS ARE REQUIRED. FBCR 315
  
 9) IN ADDITION TO THE SIGNATURE, PLEASE PROVIDE THE
 PRINTED NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN ON THE DRAWINGS. CITY
 AMENDMENTS 107.2.1
  
 THIS REVIEW IS NOT INTENDED AS A PUNCH LIST TO LIST ALL
 OF THE DEFICIENCIES WITH THE ELECTRICAL PLANS. DUE TO
 THE AMOUNT OF MISSING INFORMATION IT IS SUGGESTED THAT
 THESE PLANS BE REVIEWED BY A LICENSED DESIGN
 PROFESSIONAL BEFORE THEY ARE RESUBMITTED FOR REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-23 Cont ID  
Sent By rmcdouga Date 2014-01-23 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-01-21 Time 14:22 Sent To  
Notes
2014-01-22 14:23:19RESUBMITTAL SENT TO R. MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-12 Cont ID  
Sent By rmcdouga Date 2013-12-12 Time 19:10 Rev Time 0.00
Received By rmcdouga Date 2013-12-12 Time 17:27 Sent To  
Notes
2013-12-12 17:29:16APPLICATION AND ELECTRICAL PLANS PUT WITH MASTER.
2013-12-12 14:38:26ROUTED TO ELECTRICAL