Plan Review Stops For Permit 13120464 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
Sent By |
lphilmor |
Date |
2013-12-12 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
lphilmor |
Date |
2013-12-12 |
Time |
13:42 |
Sent To |
|
|
Notes |
2013-12-12 13:43:05 | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES | | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET | | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | ENCLOSURE. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
jlmitch |
Date |
2013-12-11 |
Time |
14:26 |
Sent To |
|
|
Notes |
2013-12-11 14:26:58 | ROUTED TO TEMP TENTS |
|
|
|