Plan Review Details - Permit 13120456
Plan Review Stops For Permit 13120456
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2014-04-25 Time 08:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-09 Cont ID  
Sent By jwitmer Date 2014-04-09 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2014-04-09 Time 11:38 Sent To  
Notes
2014-04-09 12:03:55BUILDING PLAN REVIEW
 PERMIT: 13120456
 ADD: 424 PALM ST
 CONT: COMET & ELECTRIC
 TEL: (561) 689-4400
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 09/ 2014
 ACTION: DENIED
  
 1-2) COMPLIED.
 2) THE SURVEY DOES NOT INDICATE WHERE THE LOCATION OF
 THE NEW GENERATOR WILL BE LOCATED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) 2ND REVIEW, TYPICAL GENERATOR PAD DETAILS ARE BY
 DAVID CARMO P. E.. PLANS ARE COPIED NOT SIGNED NOR
 SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 THE PLANS DO NOT SHOW HOW THE GENERATOR WILL BE
 ANCHORED TO RESIST, SLIDDING AND THE MOMENT OF
 OVERTURNING, NOR IS THERE PLANS INCLUDED SHOWING A
 FOUNDATION/ SLAB AND REINFORCEMENT NOR WIND DESIGN
 CRITERIA. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED,
 MWFRS (MAIN WIND FORCE RESISTING SYSTEM FOR MOMENT OF
 OVERTURNING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-26 Cont ID  
Sent By jwitmer Date 2013-12-26 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2013-12-26 Time 09:44 Sent To  
Notes
2013-12-26 09:58:13BUILDING PLAN REVIEW
 PERMIT: 13120456
 ADD: 424 PALM ST
 CONT: COMET & ELECTRIC
 TEL: (561) 689-4400
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY DEC. 26/2013
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE GENERATOR
 PROVIDED BY OTHERS, THE COST OF THE GENERATOR IS TO BE
 APPLIED TO THE JOB VALUE EVEN WHEN IT IS BOUGHT BY THE
 OWNERS, IT IS PART OF THE SCOPE OF WORK TO BE
 COMPLETED. VALUE IS LOW.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE SURVEY DOES NOT INDICATE WHERE THE LOCATION OF
 THE NEW GENERATOR WILL BE LOCATED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE PLANS DO NOT SHOW HOW THE GENERATOR WILL BE
 ANCHORED TO RESIST, SLIDDING AND THE MOMENT OF
 OVERTURNING, NOR IS THERE PLANS INCLUDED SHOWING A
 FOUNDATION/ SLAB AND REINFORCEMENT NOR WIND DESIGN
 CRITERIA. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED,
 MWFRS (MAIN WIND FORCE RESISTING SYSTEM FOR MOMENT OF
 OVERTURNING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-02-06 Cont ID  
Sent By dharvey Date 2014-02-06 Time 12:08 Rev Time 0.00
Received By dharvey Date 2014-02-06 Time 11:27 Sent To  
Notes
2014-02-06 11:27:51BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-21 Cont ID  
Sent By wjolin Date 2013-12-21 Time 11:47 Rev Time 0.00
Received By wjolin Date 2013-12-21 Time 11:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-02-06 Cont ID  
Sent By skennedy Date 2014-02-06 Time 16:56 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2014-04-04 Time 09:07 Sent To  
Notes
2014-04-08 09:10:20TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-06 Cont ID  
Sent By skennedy Date 2014-02-06 Time 16:56 Rev Time 0.00
Received By skennedy Date 2013-12-11 Time 11:18 Sent To  
Notes
2013-12-14 11:19:51B02

Review Stop Z ZONING
Rev No 2 Status P Date 2014-01-09 Cont ID  
Sent By eschneid Date 2014-01-09 Time 10:43 Rev Time 0.75
Received By eschneid Date 2014-01-09 Time 10:43 Sent To  
Notes
2014-01-09 10:47:53GENERATOR ENCLOSURE WAS APPROVED BY PERMIT 13110298.

Review Stop Z ZONING
Rev No 1 Status F Date 2013-12-23 Cont ID  
Sent By jroach Date 2013-12-23 Time 11:48 Rev Time 0.00
Received By jroach Date 2013-12-23 Time 11:47 Sent To  
Notes
2013-12-23 11:48:09ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.23.2013
 PERMIT NO.: 13120456
 ADDRESS: 424 PALM STREET
 CONTRACTOR/CONTACT: MEL DESTIO
 TELEPHONE NO.: 561.689.4400
 SCOPE OF REVIEW: GENERATOR
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A SITE PHOTOMETRIC PLAN IS PROVIDED?PLEASE CLARIFY.
 IS SITE LIGHTING A PART OF THE SCOPE OF THE WORK?
  
 2. GENERATORS SHALL BE SCREENED. SCREENING SHALL
 CONSIST OF A SOLID, OPAQUE MATERIAL THAT IS EITHER
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY DURABLE WOOD AND STEEL. THE SCREEN SHALL
 ALSO BE LANDSCAPED WITH SHRUBS/HEDGES PLANTED AT 2-FOOT
 INTERVALS, WHICH SHALL BE IRRIGATED WITH A PERMANENT
 IRRIGATION SYSTEM. DETAILS OF THE FENCE/WALL WILL NEED
 TO BE INCLUDED IN THE PLANS. ALL LANDSCAPING SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT AND SHALL INCLUDE 2
 SETS OF LANDSCAPE PLANS AND A CERTIFIED COST ESTIMATE.
  
 3. PLEASE PROVIDE A SITE PLAN THAT INDICATES THE
 LOCATION OF THE GENERATOR, AS WELL AS THE DIMENSION
 FROM THE GENERATOR TO ALL SURROUNDING PROPERTY LINES.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2013-12-18 11:04:4712/18/13