Plan Review Details - Permit 13120357
Plan Review Stops For Permit 13120357
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-23 Cont ID  
Sent By jwitmer Date 2013-12-23 Time 11:02 Rev Time 0.00
Received By jwitmer Date 2013-12-23 Time 11:02 Sent To  
Notes
2013-12-23 14:16:40BUILDING PLAN REVIEW
 PERMIT: 13120357
 ADD: 800 N TAMARIND AVE
 CONT: FASTRACK MCI
 TEL: (561)304-7881
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 23/ 2013
 ACTION: DENIED
  
 1A) THE PALM BEACH COUNTY PROPERTY APPRAISERS LIST THIS
 PROPERTY AS A SINGLE FAMILY DWELLING. THE CONTRACTOR
 WILL NEED TO NOTE ON THE PERMIT APPLICATION THIS IS A
 CHANGE OF OCCUPANCY FROM A RESIDENTIAL USE TO A SHELL
 PERMIT (WHITE BOX) , OCCUPANCY BUSINESS. A CERTIFICATE
 OF COMPLETION WILL BE ISSUED ONCE ALL REQUIRED
 INSPECTIONS ARE PASSED. A CERTIFICATE OF OCCUPANCY WILL
 BE ISSUED FOR THE TENANT BUILD-OUT.
  
 1B) THE DESIGNER OF RECORD LIST THE WORK TO BE
 COMPLETED UNDER THIS PERMIT AS A LEVELL II ALTERATION,
 PLEASE UPDATE PLANS TO A:
 CHANGE OF OCCUPANCY, EXISTING BUILDING CODE 901.3
 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 2) 903.1 GENERAL. BUILDING ELEMENTS AND MATERIALS IN
 PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912. THE
 INTERIOR DEMOLITION PLAN LIST THE REMOVAL OF WOOD
 FLOORING DOWN TO THE FLOOR JOIST. THE CODES ALLOWED FOR
 THE LIVE LOADS TO BE DESIGNED TO 30 LBS/ SQ FT LIVE
 LOADS FOR SLEEPING ROOMS AND 40 LBS/ SQ FT FOR LIVING
 AREAS OF THE DWELLING. THE CHANGE OF OCCUPANCY TO
 BUSINESS THE LIVE LOADS ARE TO BE INCREASED TO 50 LBS/
 SQ FT. IF MERCANTILE 100 LBS/ SQ FT.
 PLEASE PROVIDE ANALYSIS FOR COMPLIANCE WITH: 907.1
 GRAVITY LOADS.
 BUILDINGS OR PORTIONS THEREOF SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER UNIFORM OR CONCENTRATED LOADS BASED
 ON THE FLORIDA BUILDING CODE, BUILDING TABLES 1607.1
 SHALL COMPLY WITH THE GRAVITY LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3)SHEET A-2. 906.1 GENERAL. ACCESSIBILITY IN PORTIONS
 OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
 3A) RAMPS:2010 FBC ACCESSIBILITY CODE 405.8 HANDRAILS.
 RAMP RUNS WITH A RISE GREATER THAN 6 INCHES (150 MM)
 SHALL HAVE HANDRAILS COMPLYING WITH 505.
 2010 FBC ACCESSIBILITY CODE. 505.2 WHERE REQUIRED.
 HANDRAILS SHALL BE PROVIDED ON BOTH SIDES OF STAIRS AND
 RAMPS.
  
 3B) UPPER LANDING TO DOORWAY, MUST HAVE A MINIMUM OF 24
 INCHES. 2010 FBC ACCESSIBILITY CODE 404.2.4 MANEUVERING
 CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE. ALSO SEE FIGURE
 404.2.4(J) LATCH APPROACH, PULL SIDE REQUIRES 24"
 BEFORE THE START OF THE RAMP, LEVEL APPROACH.
  
 3C) 2010 FBC-ACCESSIBILITY CODE 405.9 EDGE PROTECTION.
 EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL
 BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE
 OF RAMP LANDINGS.
  
 4) SHEET A-4 :
 4A) INDICATES A 1/2" ELEVATION CHANGE FROM THE INTERIOR
 FINISH FLOOR AND ACCESSIBLE FRONT ENTRY STOOP. PLEASE
 UPDATE PLANS TO COMPLY WITH 2010 FBC- ACCESSIBILITY
 CODE 303. 3 BEVELED. 303.3 BEVELED. CHANGES IN LEVEL
 BETWEEN 1/4 INCH (6.4 MM) HIGH MINIMUM AND 1/2 INCH (13
 MM) HIGH MAXIMUM SHALL BE BEVELED WITH A SLOPE NOT
 STEEPER THAN 1:2.
  
 4B) PLEASE NOTE THE THRESHOLD WILL NEED TO COMPLY WITH
 2010 FBC-ACCESSIBILITY CODE 404.2.5 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. PLEASE
 BE AWARE INSWING DOOR, THE ONLY THING THAT IS KEEPING
 WATER OUT OF THIS STRUCTURE IS A AWNING UNDER SEPERATE
 PERMIT.
  
 4C) PLANS INDICATE A IN-SWING DOOR WHEREAS THE PRODUCT
 APPROVAL SUBMITTED IS FOR A OUTSWING DOOR. PLEASE
 PROVIDE THE PRODUCT APPROVAL FOR A IN-SWING DOOR AS
 INDICATED BY THE PLANS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4D) THE PLANS INDICATE NEW EXTERIOR WALL INFILL
 SECTIONS OF WALL, NO WALL SECTIONS WERE PROVIDED FOR
 CONTINIOUS LOAD PATH (MWFRS) FROM FOUNDATION TO TOP
 PLATE, SUB-SHEATHING, OR EXTERIOR FINISH, WALL
 INSULATION OR INTERIOR WALL TYPE OR THICKNESS. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.3.5.1
 MINIMUM PLAN REVIEW CRITERIA.
  
 4E) THIS PLAN SHOWS NEW WINDOWS AND OR NEW WINDOWS
 PARTIALLY IN THE SAME OPENING. THE PLANS DO NOT PROVIDE
 THE HEADER SIZE REQUIRED, HOW MANY JACK STUDS
 (CRIPPLERS) AND HOW MANY FULL LENGTH STUDS ARE TO BE
 REQUIRED ON EACH SIDE OF THE OPENINGS, NOR STAPPING
 REQUIREMENTS, AGAIN PART OF THE (MWFRS).
  
 4F) THIS PLAN INDICATES R-30 INSULATION IS TO BE
 APPLIED TO ROOF SHEATHING IS THIS ABOVE OR BENEATH THE
 ROOF SHEATING? WHAT TYPE OF INSULATION? IS THIS
 ICYNENE, IF SO PROVIDE PRODUCT TESTING REPORT, AND THE
 TYPE OF SUB-SYSTEM TO BE USED, WILL A IGNITION BARRIER
 BE REQUIRED PER 2010 FBC-B 2603.4.1.6.
  
 4G) PLANS ARE MISSING COMPLIANCE WITH 2010 FBC-B 1209.2
 ACCESS HATCH.
  
 4H) WINDOWS 103, 104 & 105 ARE CONSIDEREDA HAZARDOUS
 LOCATION, PLEASE PROVIDE COMPLIANCE WITH, 2010 FBC-B
 2406.4 HAZARDOUS LOCATIONS. THE FOLLOWING SHALL BE
 CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING
 SAFETY GLAZING MATERIALS:
 10. GLAZING ADJACENT TO STAIRWAYS, LANDINGS AND RAMPS
 WITHIN 36 INCHES (914 MM) HORIZONTALLY OF A WALKING
 SURFACE; WHEN THE EXPOSED SURFACE OF THE GLASS IS LESS
 THAN 60 INCHES (1524 MM) ABOVE THE PLANE OF THE
 ADJACENT WALKING SURFACE.
 EXCEPTION: SAFETY GLAZING FOR ITEM 10 OR 11 IS NOT
 REQUIRED FOR THE FOLLOWING INSTALLATIONS WHERE:
 1. THE SIDE OF A STAIRWAY, LANDING OR RAMP WHICH HAS A
 GUARD OR HANDRAIL, INCLUDING BALUSTERS OR IN-FILL
 PANELS, COMPLYING WITH THE PROVISIONS OF SECTIONS 1013
 AND 1607.7; AND
 2. THE PLANE OF THE GLASS IS GREATER THAN 18 INCHES
 (457 MM) FROM THE RAILING.
  
 5) 2010 FBC EXISITNG BUILDING CODE SECTION 913 ENERGY
 CONSERVATION SEE THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION. SEE THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION.
 502.1.1.1 SHELL BUILDINGS, RENOVATIONS AND ALTERATIONS.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE 502.1.1.1(1) OR TABLE
 502.1.1.1(2). SEE SECTION 101.4.3.
  
 502.2.1 ROOF ASSEMBLY.
 502.2.1.1 SHELL BUILDINGS, RENOVATIONS AND ALTERATIONS.
 THE SUM OF THE INSTALLED INSULATING MATERIAL INSTALLED
 R-VALUES SHALL MEET THE MINIMUM THERMAL RESISTANCE
 REQUIREMENTS AS SPECIFIED IN TABLE 502.1.1.1(1) OR
 TABLE 502.1.1.1.(2).
  
 02.2.2.1 SHELL BUILDINGS, RENOVATIONS AND ALTERATIONS.
 502.2.2.1.1 ABOVE-GRADE WALLS.
 THE MINIMUM THERMAL RESISTANCE (R-VALUE) OF THE
 INSULATING MATERIAL(S) INSTALLED IN THE WALL CAVITY
 BETWEEN THE FRAMING MEMBERS AND CONTINUOUSLY ON THE
 WALLS SHALL BE AS SPECIFIED IN TABLE 502.1.1.1(1) OR
 TABLE 502.1.1.1(2), BASED ON FRAMING TYPE AND
 CONSTRUCTION MATERIALS USED IN THE WALL ASSEMBLY. THE
 R-VALUE OF INTEGRAL INSULATION INSTALLED IN CONCRETE
 MASONRY UNITS (CMU) SHALL NOT BE USED IN DETERMINING
 COMPLIANCE WITH TABLE 502.1.1.1(1) OR TABLE
 502.1.1.1(2).
  
 502.2.3 FLOORS. 502.2.3.1 SHELL BUILDINGS, RENOVATIONS
 AND ALTERATIONS.
 502.2.3.1.1 FLOORS OVER OUTDOOR AIR OR UNCONDITIONED
 SPACE.
 THE MINIMUM THERMAL RESISTANCE (R-VALUE) OF THE
 INSULATING MATERIAL INSTALLED EITHER BETWEEN THE FLOOR
 FRAMING OR CONTINUOUSLY ON THE FLOOR ASSEMBLY SHALL BE
 AS SPECIFIED IN TABLE 502.1.1.1(1) OR TABLE
 502.1.1.1(2), BASED ON CONSTRUCTION MATERIALS USED IN
 THE FLOOR ASSEMBLY.
  
 502.2.4.1 SHELL BUILDINGS, RENOVATIONS AND ALTERATIONS.
 502.2.4.1.1 OPAQUE DOORS. OPAQUE DOORS (DOORS HAVING
 LESS THAN 50 PERCENT GLASS AREA) SHALL MEET THE
 APPLICABLE REQUIREMENTS FOR DOORS AS SPECIFIED IN TABLE
 502.1.1.1(1) OR TABLE 502.1.1.1(2).
  
 502.2.5 FENESTRATION (PRESCRIPTIVE). 502.2.5.1 SHELL
 BUILDINGS, RENOVATIONS AND ALTERATIONS. FENESTRATION
 SHALL COMPLY WITH TABLE 502.1.1.1(1) OR TABLE
 502.1.1.1(2).
  
 502.2.5.1.2 MAXIMUM U-FACTOR AND SHGC.
 FOR VERTICAL FENESTRATION, THE MAXIMUM U-FACTOR AND
 SOLAR HEAT GAIN COEFFICIENT (SHGC) SHALL BE AS
 SPECIFIED IN TABLE 502.1.1.1(1) OR TABLE 502.1.1.1(2),
 BASED ON THE WINDOW PROJECTION FACTOR. FOR SKYLIGHTS,
 THE MAXIMUM U-FACTOR AND SOLAR HEAT GAIN COEFFICIENT
 (SHGC) SHALL BE AS SPECIFIED IN TABLE 502.1.1.1(1) OR
 TABLE 502.1.1.1(2).
  
 502.3.5.4 AIR DISTRIBUTION SYSTEM COMPONENTS.
 BUILDING CAVITIES DESIGNED TO BE AIR DISTRIBUTION
 SYSTEM COMPONENTS SHALL BE SEALED ACCORDING TO THE
 CRITERIA FOR AIR DUCTS, PLENUMS, ETC. IN SECTION
 503.2.7.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By albarran Date 2014-02-04 Time 18:54 Rev Time 0.00
Received By albarran Date 2014-02-04 Time 18:24 Sent To I
Notes
2014-02-04 19:10:16THIS APPLICATION FAILED THE ELECTRICAL REVIEW AND THE
 FOLLOWING CORRECTIONS SHALL BE MADE.
 1.TABLE 310.15(B) OF THE NEC NO LONGER APPLIES TO THE
 SERVICE AS THE NEW OCCUPANCY IS A BUSINESS.
 2. EMERGENCY LIGHTING AS PER FBC, LIFE SAFETY & NFPA
 SHALL BE PROVIDED.
 3. EXIT LIGHTING COMP[LYING WITH THE ABOVE CODES SHALL
 ALSO BE PROVIDED.
 4. THE SIGN OUTLET REQUIRED BY NEC 600.5 SHALL BE
 PROVIDED, AS WELL AS SHOW WINDOW LIGHTING IF
 APPLICABLE.
 5. INCLUDE IN THE RISER DIAGRAM THE INTER-SYSTEM
 BONDING TERMINAL REQUIRED BY NEC 250.94
 6. AS PER NEC 422.52, THE WATER COOLER SHALL BE ON A
 GFI PROTECTED CIRCUIT.
 7. SHOW WITH MORE DETAIL THE PROPOSED ELECTRIC FOR THE
 HVAC SYSTEM, INCLUDING THE REQUIRED DISCONNECTS.
 8. YOUR LIGHTING SHALL COMPLY WITH ALL THE REQUIREMENTS
 OF THE FBC-ENERGY CONSERVATION CODE.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH BLDG. DEPARTMENT
 PH: (561) 805-6718
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-12-13 Cont ID  
Sent By fmittner Date 2013-12-13 Time 16:00 Rev Time 0.00
Received By fmittner Date 2013-12-13 Time 16:00 Sent To  
Notes
2013-12-13 16:01:30WITH CONDITION OF ADDING PLANTS IN FRONT OF RAILING AND
 STAIRS TO FRONT DOOR. QUESTIONS CONTACT FRIEDERIKE
 MITTNER 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-05 Cont ID  
Sent By skennedy Date 2014-02-05 Time 08:04 Rev Time 0.00
Received By skennedy Date 2013-12-09 Time 18:53 Sent To  
Notes
2014-02-04 19:10:46SAK FOR PROCESSING

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-12-23 Cont ID  
Sent By jwitmer Date 2013-12-23 Time 11:02 Rev Time 0.00
Received By jwitmer Date 2013-12-23 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-19 Cont ID  
Sent By shill Date 2013-12-19 Time 15:10 Rev Time 0.00
Received By hmoser Date 2013-12-19 Time 15:10 Sent To  
Notes
2013-12-19 17:29:15REVIEW BY J SAEZ PX 1328
  
 561-805-6710
  
 1. PROVIDE FLOAT SWITCH
  
 2. PROVIDE OUTSIDE AIR CALC
  
 3. PROVIDE ENERGY CALC
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-12-19 Cont ID  
Sent By lwagner Date 2013-12-19 Time 15:07 Rev Time 0.00
Received By lwagner Date 2013-12-19 Time 14:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-12-13 Cont ID  
Sent By aaponte Date 2013-12-13 Time 09:57 Rev Time 0.00
Received By aaponte Date 2013-12-13 Time 09:57 Sent To  
Notes
2013-12-13 10:55:391. ALL PARKING SPACES WITHIN PARKING AREA SHALL BE
 STRIPED AND DIMENSIONED IN COMPLIANCE WITH CITY CODE
 (SEC 94-485). COMPACT SPACES ARE ALLOWED.
 2. THE HC SPACE SHOWS DIFFERENT DIMENSIONS ON SHEET A-1
 AND A-2. IT SHALL BE 18' LONG BY 12' WIDE, WITH A 5'
 ACCESSIBLE AISLE.
 3. IS THE PROPOSED CURB CUT IN THE SAME LOCATION THAN
 THE EXISTING?
 4. ONCE THE PARKING SPACES HAVE BEEN ACCOMODATED, THE
 LEFT OVER SPACE SHALL BE ADDED AS A LANDSCAPE ON THE
 EAST PROPERTY LINE, EXCEPT ALONG THE AISLE TO PROVIDE
 FOR SOME TURN AROUND SPACE.
 5. LIVE OAKS ALONG TAMARIND SHALL BE MOVED AWAY FROM
 THE DRIVEWAY, AND SHALL BE LOCATED IN FRONT OF THE
 HEDGE TO PROVIDE ADDITIONAL ROOM FOR ROOTS.
 6. SHADE TREES ARE REQUIRED ALONG THE EAST PROPERTY
 LINE.
 7. IS THERE A REASON WHY THE FENCE ON THE NORTH SIDE IS
 NOT LOCATED ON THE PROPERTY LINE? IS IT THE EXISTING
 FENCE?
 8. A DIRECT ACCESS FROM THE SIDEWALK SHALL BE PROVIDED.
 9. A TREE REMOVAL PERMIT WILL BE REQUIRED FOR THE
 PROJECT.
 10. FENCE ALONG TAMARIND AVE AND 7TH STREET CAN NOT
 EXCEED 4 FEET IN HEIGHT.
 11. PLANT MATERIAL WITHIN THE VISIBILITY TRIANGLE SHALL
 BE MAINTAINED BELOW 18". COCOPLUM WILL VERY RAPIDLY
 GROW ABOVE THAT HEIGHT, ANOTHER SPECIE IS RECOMMENDED.
 12. SIGNED AND SEALED LANDSCAPE DRAWINGS WILL BE
 REQUIRED FOR THIS PROJECT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-8221439.