Plan Review Details - Permit 13120304
Plan Review Stops For Permit 13120304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 05:57 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 05:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-01-02 Cont ID  
Sent By jwitmer Date 2014-01-02 Time 17:34 Rev Time 0.00
Received By jwitmer Date 2014-01-02 Time 15:53 Sent To  
Notes
2014-01-02 17:34:46BUILDING PLAN REVIEW
 PERMIT: 13120304
 ADD: 2627 OKEECHOBEE BLVD STORE 102
 CONT: TO BE DETERMINED
 TEL: (954)748-7420
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JAN. 02/2014
 ACTION: DENIED
  
 1) 2010 FL EXISTING BUILDING CODE THE DESIGNER OF
 RECORD HAS NOT INDICATED AS TO WHICH METHOD COMPLIANCE
 WITH SECTION:
 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER.
  
 2) IN THE AREA WORK METHOD LEVEL 1 OR LEVEL 2 REQUIRES
 COMPLIANCE WITH THE FL ACCESSIBILITY CODE,
 LEVEL 1, 605.1 GENERAL. ACCESSIBILITY SHALL BE IN
 ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
 LEVEL 2, 706.1 GENERAL. A BUILDING, FACILITY, OR
 ELEMENT THAT IS ALTERED SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 NOTE THE RESTROOMS ARE NOT ONLY GETTING NEW FINISHES
 BUT THE STALLS ARE BEING RECONFIGURED(PERMIT #
 03120529) SHOWS A DIFFERENT CONFIGURATION THAN WHAT
 SHOWS ON THIS PERMIT. 2010 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2A) PLEASE PROVIDE ACCESSIBLE RESTROOMS THAT WIL MEET
 THE REQUIREMENTS OF 2010 FBC-ACCESSIBILITY CODE 604.3.2
 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2B) THE DOORS THAT FORM THE RESTROOM VESTIBULE DO NOT
 MEET THE 2010 FL ACCESSIBILITY CODE SEE DOORS IN
 SERIES. 404.2.6 DOORS IN SERIES AND GATES IN SERIES.
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
  
 3) THE ASSOCIATES LOUNGE IS LOCATED IN ROOM 107 WHICH
 IS LOCATED ON A MEZZININE LEVEL UNDER PERMIT (0312-529)
 THERE APPEARS TO BE A HANDICAPPED LOUNGE ON THE FLOOR
 LEVEL WHERE YOU DID NOT HAVE TO GO THROUGH THE
 STOCKROOM, NOW IN THE PROPOSED LAYOUT AN ASSOCIATE THAT
 IS DISABLED WOULD HAVE TO TRAVEL THROUGH THE STOCKROOM
 TO GET TO THE ACCESSIBLE LOUNGE. ALTERATIONS ARE NOT
 SUPPOSE TO MAKE THE ACCESSWIBLE ROUTE LESS ACCESSABLE.
  
 4) SHEET A102 DETAIL # 6 INDICATES THE USE OF A NEW
 PREFABRICATED STAIR, GAURDRAIL & HANDRAIL SYSTEM,
 PLEASE PROVIDE LIVE LOADS FOR THE STAIR DESIGN PER 2010
 FBC-B TABLE 1607.1 AND A PROFILE OF THE GAURDRAIL
 HANDRAIL SYSTEM SHOWING COMPLIANCE WITH 1013 SINCE THIS
 IS PART OF THE EXIT DISCHARGE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By albarran Date 2014-01-13 Time 15:05 Rev Time 0.00
Received By albarran Date 2014-01-13 Time 14:31 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-16 Cont ID  
Sent By scaldero Date 2013-12-16 Time 13:34 Rev Time 0.00
Received By scaldero Date 2013-12-16 Time 13:34 Sent To  
Notes
2013-12-16 13:44:10PERMIT #13120304
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***PROVISO****
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 THE FOLLOWING ITEMS MAY ALREADY BE EXISTING, HOWEVER
 THEY ARE NOT INDICATED ON PLANS:
 3) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 4) PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 5) PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS
 WITH EXIT SIGNS.
  
 6) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 05:57 Rev Time 0.00
Received By jwitmer Date 2014-01-21 Time 15:45 Sent To  
Notes
2014-01-22 15:45:50RESUBMITTAL SENT TO J. WITMER'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-13 Cont ID  
Sent By shill Date 2014-01-13 Time 17:20 Rev Time 0.00
Received By shill Date 2013-12-06 Time 08:35 Sent To  
Notes
2014-01-13 15:06:25SH DESK
  
2013-12-07 08:35:30C12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 05:54 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 05:50 Sent To  
Notes
2014-01-23 05:56:58ENGINEERS RESPONCE INDICATES THE ONLY SCOPE OF WORK IS
 THE DISCONNECTING OF THE 2 ROOFTOP UNITS THAT ARE NO
 LONGER IN THEIR LEASE AREA. LETTER PART OF THE PERMIT
 RECORDS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-01-03 Cont ID  
Sent By shill Date 2013-12-19 Time 11:24 Rev Time 0.00
Received By hmoser Date 2014-01-03 Time 11:24 Sent To  
Notes
2014-01-03 11:35:00PLAN REVIEW BY J SAIS PX 1328
  
 1. PROVIDE AC DRAWINGS
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-01-02 Cont ID  
Sent By lwagner Date 2014-01-02 Time 09:22 Rev Time 0.00
Received By lwagner Date 2014-01-02 Time 09:17 Sent To  
Notes
2014-01-02 09:22:51NO PLUMBING SHOWN AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-18 Cont ID  
Sent By ajones Date 2013-12-18 Time 10:53 Rev Time 0.00
Received By ajones Date 2013-12-18 Time 10:52 Sent To  
Notes
***NONE***