Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-14 Cont ID  
Sent By shill Date 2013-12-14 Time 13:38 Rev Time 0.00
Received By shill Date 2013-12-14 Time 13:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-06 Cont ID  
Sent By shill Date 2013-12-06 Time 06:42 Rev Time 0.00
Received By shill Date 2013-12-06 Time 06:42 Sent To  
Notes
2013-12-06 06:43:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ASSEMBLY SELECTED REFERS TO GENERAL LIMITATION
 #9. SEE LAST PAGE OF NOA, ENHANCED FASTENING NOT
 PERMITTED; ASSEMBLY IS TO EITHER MEET REQUIRED DESIGN
 PRESSURES OR REFER TO GENERAL LIMITATION #7.
  
 2. CALCULATIONS ARE TO BE IN ACCORDANCE WITH
 FAC61G15-23. EITHER AN INDEX SHEET TO BE INCLUDED OR
 EACH SHEET SIGNED AND SEALED. TITLE BLOCK TO INCLUDE
 CERTIFICATE OF AUTHORIZATION NUMBER.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-14 Cont ID  
Sent By shill Date 2013-12-14 Time 13:38 Rev Time 0.00
Received By shill Date 2013-12-14 Time 13:38 Sent To  
Notes
2013-12-11 16:12:58RESUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-06 Cont ID  
Sent By shill Date 2013-12-06 Time 06:44 Rev Time 0.00
Received By shill Date 2013-12-06 Time 06:43 Sent To  
Notes
***NONE***