Plan Review Details - Permit 13120185
Plan Review Stops For Permit 13120185
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-12-23 Cont ID  
Sent By jwitmer Date 2013-12-23 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2013-12-23 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-16 Cont ID  
Sent By shill Date 2014-05-16 Time 16:24 Rev Time 0.00
Received By shill Date 2014-05-16 Time 16:24 Sent To  
Notes
2014-05-16 16:24:45REVIEWED BY DAVID HAYES UNDER PERMIT #14050360
 (MASTER PERMIT INADVERTANTLY ISSUED WITHOUT AN ELECTRIC
 REVIEW)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-19 Cont ID  
Sent By wjolin Date 2013-12-19 Time 11:41 Rev Time 0.00
Received By wjolin Date 2013-12-19 Time 11:29 Sent To  
Notes
2013-12-19 11:41:423RD FLOOR: VERIFY ALL EXISTING DUCTWORK PENETRATING
 FIRE RATED CORRIDOR WALLS ARE EQUIPPED WITH FIRE
 DAMPERS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-23 Cont ID  
Sent By jwitmer Date 2013-12-23 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2013-12-05 Time 11:15 Sent To  
Notes
2013-12-05 11:18:54B22
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-23 Cont ID  
Sent By shill Date 2013-12-18 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2013-12-18 Time 16:11 Sent To  
Notes
2013-12-18 16:28:27REVIEW BY J SAEZ, PX 1328
  
 PASSED W/PROVISOS
  
 1. V1.34 LATERAL DUCT (NO TIE IN TO MAIN DUCTWORK
 ELBOW), SHEET M1
 2. NO PVC ABOVE THE RETURN AIR PLENUM
 3. PROVIDE FLOAT SWITCH ON AHU
  
  