Plan Review Stops For Permit 13120109 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2014-08-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-08-28 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-08-28 |
Time |
12:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-07-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-07-24 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-07-24 |
Time |
13:23 |
Sent To |
|
|
Notes |
2014-07-24 13:25:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. A NEW CATWALK IS PROPOSED. PROVIDE ENGINEERING, FBC | | 2010 RESIDENTIAL 301. PLANS ARE TO INCLUDE WIND DESIGN | | CRITERIA. | | | | 2. ADJUST VALUE TO INCLUDE NEW WORK, FBC 109. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2013-12-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-12-27 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-12-27 |
Time |
11:57 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2014-07-18 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-07-18 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-07-18 |
Time |
15:23 |
Sent To |
|
|
Notes |
2014-07-18 15:37:30 | DATE: 7/18/2014 | | PROJECT: BOAT LIFT 7610 S. FLAGLER DR | | PERMIT#: 13120109 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 2NDELECTRICAL PLAN REVIEW | | | | NO ELECTRICAL DOCUMENTATION IS INCLUDED IN THIS OR THE | | PREVIOUS SUBMITTAL. | | | | A SEPARATE ELECTRICAL PERMIT APPLICATION ACCOMPANIED BY | | ELECTRICAL PLANS AND SPECIFICATIONS IS REQUIRED PRIOR | | TO COMMENCEMENT OF ANY ELECTRICAL WORK. PLANS TO | | INCLUDE THE BOAT LIFT MANUFACTURERS INSTALLATION | | DOCUMENTATION AND SHALL INDICATE THE SOURCE OF THE | | ELECTRICAL CIRCUITRY PROPOSED AND LOCATIONS AND | | SPECIFICATIONS OF ALL ELECTRICAL COMPONENTS INVOLVED IN | | THE INSTALLATION. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-01-02 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-01-02 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-01-02 |
Time |
16:09 |
Sent To |
I |
|
Notes |
2014-01-02 16:32:30 | THE APPLICATION DOES NOT PROVIDE AMPLE DETAIL AS TO THE | | WORK BEING PERFORMED | | YOU WILL NEED TO PROVIDE THE FOLLOWING FOR THE ISSUANCE | | OF AN ELECTRICAL PERMIT: | | 1. LOCATION OF POWER SOURCE FOR THE BOAT LIFT. | | 2. HOW WILL POWER BE TAKEN TO THE LIFT MOTORS. | | 3. SIZE AND QUANTITY OF LIFT MOTORS. | | 4. AS PER NEC 210.8 GFI PROTECTION SHALL BE PROVIDED | | FOR BOAT HOISTS | | 5. ALL TRENCHING SHALL COMPLY WITH NEC 300.5 AND BE | | INSPECTED PRIOR TO ANY BACK FILL. | | 6. THERE MUST BE A 120 VOLT 20 AMP GFCI OUTLET WITHIN | | CLOSE PROXIMITY OF THE LIFT. | | | | ALL ELECTRICAL WORK ON THIS PERMIT | | SHALL COMPLY WITH ALL THE REQUIREMENTS | | OF THE 2008 EDITION OF THE NEC. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-08-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-08-28 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-08-05 |
Time |
16:42 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-07-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-07-24 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-07-18 |
Time |
15:23 |
Sent To |
|
|
Notes |
2014-07-22 08:33:29 | TO SH DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-01-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-01-04 |
Time |
12:24 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-12-03 |
Time |
17:15 |
Sent To |
|
|
Notes |
2014-01-02 16:33:17 | SH | 2013-12-27 11:57:54 | 12/27 TO ELEC | | | 2013-12-03 17:15:51 | INCOMING SENT TO ZONING BOX. JW |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2014-08-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-08-28 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-08-07 |
Time |
14:58 |
Sent To |
B |
|
Notes |
2014-08-07 15:11:32 | 8/7/14 - SENT TO SH. DK | | | 2014-08-07 15:09:16 | 8/7/14 - NOTE: BUILDING PERMIT PLANS ARE SLIGHTLY | | DIFFERENT THAN PLAN APPROVED IN RES. 144-14, HOWEVER, | | ALL PROPOSED IMPROVEMENTS ARE STILL IN COMPLIANCE WITH | | ALL WAIVERS GRANTED. DK | 2014-08-06 15:43:04 | 8/6/14 ZONING SENT TO DK. SG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2014-07-21 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-07-21 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-07-21 |
Time |
15:44 |
Sent To |
|
|
Notes |
2014-07-22 08:40:26 | 7/22/14 - SENT TO SH. DK | | | 2014-07-21 17:06:40 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | 7/21/2014 | | | | 1. SUBMITTED PLANS INDICATE INSTALLATION OF A BOAT LIFT | | AND CATWALK. THERE WERE NO DIMENSIONS PROVIDED ON THE | | CATWALK ADDITION TO INDICATE COMPLIANCE WITH THE | | WAIVERS GRANTED IN RESOLUTION 144-14. PLEASE PROVIDE | | DIMENSIONS. | | | | 2. THE SCOPE OF WORK FOR THE CATWALK IS NOT CONSISTENT | | WITH THE SITE PLAN APPROVED AS PART OF RESOLUTION | | 144-14. PLEASE CONFIRM THERE HAS BEEN A CHANGE TO THE | | SCOPE OF WORK APPROVED IN RESOLUTION 144-14. IF YES, | | PLEASE CONTACT ME TO DISCUSS THE CHANGES TO MAKE SURE | | THEY ARE STILL GOING TO BE INCOMPLIANCE WITH THE | | WAIVERS APPROVED FOR THIS PROPERTY. | | | | 3. PLEASE REVIEW CONDITIONS OF APPROVAL FOR RESOLUTION | | 144-14 AND DEMONSTRATE COMPLIANCE WITH THESE | | CONDITIONS, WHERE APPLICABLE, SUCH AS INSTALLATION OF A | | LADDER (#3) AND INCLUSION OF STREET ADDRESS ON THE DOCK | | (#4), | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | DANIELLE J. KITTREDGE, AICP | | SENIOR PLANNER | | PLANNING & ZONING DIVISION | | PHONE: (561)-822-1443 | | EMAIL: [email protected] | | | 2014-07-21 11:57:17 | 7/21/14 ZONING SEN TO LL. SG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2013-12-09 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2013-12-09 |
Time |
16:11 |
Sent To |
B |
|
Notes |
2013-12-09 16:13:24 | | | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) THE WOOD DOCK DOES NOT MEET THE DIMENSIONAL AND | | LOCATIONAL REQUIREMENTS FOR A DOCK PER ZLDR S. 94-304 | | (E), AND THEREFORE, IS CONSIDERED AN EXISTING | | NON-CONFORMITY. | | | | 2.) A BOATLIFT CANNOT BE CONSTRUCTED TO THE EXISTING | | NON-CONFORMING DOCK. A NON-CONFORMING STRUCTURE CANNOT | | BE IMPROVED, CONSTRUCTED, ENLARGED OR ALTERED IN ANY | | MANNER TO INCREASE AN EXISTING NON-CONFORMITY. (ZLDR S. | | 94-513(A)) | | | | 3.) ANY WAIVERS FROM THE ABOVE SHALL REQUIRE APPROVAL | | BY THE CITY COMMISSION AS A CLASS "A" SPECIAL USE | | PERMIT. (ZLDR S. 94-304 (E)(1)) | | | | PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL | | COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1442 IF YOU | | HAVE QUESTIONS. | | |
|
|