2013-12-03 10:48:02ROUTED TO MECHANICAL $5000 & UNDER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-16 Cont ID  
Sent By hmoser Date 2013-12-16 Time 09:20 Rev Time 0.00
Received By hmoser Date 2013-12-14 Time 10:23 Sent To  
Notes
2013-12-16 09:18:46PASS PROVISO
 ENGINEER DETAIL IS REQUIRED AT FIRST INSPECTION FOR
 CONDENSER
 WALL HANGERS. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-10 Cont ID  
Sent By hmoser Date 2013-12-10 Time 10:00 Rev Time 0.00
Received By hmoser Date 2013-12-10 Time 09:47 Sent To  
Notes
2013-12-10 10:00:291) PROVIDE A ENGINEER DETAIL ON HOW THE OUTDOOR
 WALL BRACKETS ARE MOUNTED TO THE WALL.
 PER SECTION 301.12 WIND RESISTANCE.
 2) THE COOLERS MUST BE PART OF THE VALUE
 OF THE JOB.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676