Plan Review Details - Permit 13110818
Plan Review Stops For Permit 13110818
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2014-01-21 Time 11:18 Rev Time 0.00
Received By jwitmer Date 2014-01-21 Time 11:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By jwitmer Date 2013-12-27 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2013-12-27 Time 10:01 Sent To  
Notes
2013-12-27 14:05:16BUILDING PLAN REVIEW
 PERMIT: 13110818
 ADD: 1016 CLARE AVE. SUITES 1 & 2
 CONT: POLO CONSTRUCTION
 TEL: (561)239-8607
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY DEC. 27/ 2013
 ACTION: DENIED
  
 1) SHEET A1.0 MISSING INFORMATION:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
  
 1A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED. PLEASE PROVIDE A NARRATIVE AS TO
 USAGE IT APPEARS THERE IS A MERCANTILE & BUSINESS
 OCCUPANCY WITH STORAGE AS A ACCESSORY OCCUPANCY AS WELL
 AS A SEPERATE STORAGE OCCUPANCY. PLEASE PROVIDE AS TO
 IF THE STORAGE OCCUPANCY IS A S1 OR S2 OCCUPANCY.
  
 1B) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503). THIS PROPERTY IS HAD UP OF 4 BUILDINGS
 WITH 4 HOUR FIRE WALLS. PLEASE PROVIDE THE MINIMUM
 BUILDING TYPE IF BUILDING AREA MODIFICATIONS, FRONTAGE
 (FBC-B 506.2) AND OR SPRINKLER INCREASES (FBC-B 506.3)
 WERE TAKEN IN DETERMINING MINIMUM BUILDING TYPE. SEE
 FBC-B 506.1 FOR BUILDING INCREASE FORMULA.
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
  
 1C) UNTIL TYPE OF CONSTRUCTION IS DETERMINED, THE WALL
 BETWEEN THE MERCANTILE PORTION AND SEPERATE STORAGE
 OCCUPANCY CAN NOT BE DETERMINED IF THIS IS A OCCUPANCY
 SEPERATION WALL OR IF IT IS A FIRE WALL CREATING
 SEPERATE BUILDINGS PER FBC-B 706.4 & TABLE 706.4 AND
 OPENING PROTECTIVES PER 715.4.
  
 1D) THE LIFE SAFETY SHEET DOES NOT DECLARE THIS TO BE A
 FIRE SPRINKLERED BUILDING ALTHOUGH THE INDEX INDICATES
 FIRE SPRINKLER PLANS ARE INCLUDED.
  
 1E) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
  
 NOTE SHEET D1.0 INDICATES 1/4 INCH SCALE WHEREAS A1.0
 INDICATES 1/8 TH SCALE, PLANS INDICATE 13,330 SQ FT IN
 THE S1 OCCUPANCY SCALING IT OFF THE PALNS BOTH SECTIONS
 OF THE BUILDING ARE APPROXIMATELY 9409 SQ FT OR AROUND
 18, 818 SQ FT.
  
 2) SHEET 01:
 2A) NEW ENTRY NORTH WALL GRADING DETAIL INDICATES THE
 EXISTING GRADE TO BE 17.69 AND THE FINISH FLOOR GRADE
 IS 18.10. PLEASE PROVIDE DETAILS HOW THE DIFFERENCE IN
 GRADE WILL BE MADE UP, THE DETAILS WILL DETERMINE IF
 THIS AREA WILL BE CONSIDERED A RAMP OR JUST GRADE. IF
 THE RUNNING SLOPE OF THE WALKING SURFACE IS NOT STEEPER
 THAN 1:20 THEN IT WILL NOT BE CONSIDERED A RAMP SEE
 2010 FBC-B 403.2.
  
 2B) THE NORTH ENTRY NEITHER THE CROSSWALK OR EXIT FROM
 THE BUILDING INDICATES THAT YOU ARE CROSSING A
 VEHICULAR LANE. SEE DETECTABLE WARNING. FL
 ACCESSIBILITY 106.5 A STANDARDIZED SURFACE FEATURE
 BUILT IN OR APPLIED TO WALKING SURFACES OR OTHER
 ELEMENTS TO WARN OF HAZARDS ON A CIRCULATION PATH.
  
 3) SHEET S-2 PLEASE REVIEW THE DESIGN CRITERIA FOR THIS
 PROJECT TYPE VB AND GROUP R-3 OCCUPANCY.
  
 4) PLEASE PROVIDE THE WIND DESIGN CRITEIA: 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 5) THE PLANS INDICATE A MERCANTILE PORTION OF THE
 TENANT SPACE PLEASE PROVIDE COMPLIANCE WITH THE 2010
 FBC ACCESSIBILITY CODE:
 904.3 CHECK-OUT AISLES.
 CHECK-OUT AISLES SHALL COMPLY WITH 904.3.
 904.3.1 AISLE.
 AISLES SHALL COMPLY WITH 403.
 904.3.2 COUNTER.
 THE COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF
 THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM)
 MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE
 AISLE SIDE OF THE CHECK-OUT COUNTER.
 FIGURE 904.3.2
 CHECK-OUT AISLE COUNTERS
 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-01-13 Cont ID  
Sent By albarran Date 2014-01-13 Time 13:52 Rev Time 0.00
Received By albarran Date 2014-01-13 Time 12:03 Sent To I
Notes
2014-01-13 13:52:56APPROVED WITH A NOTE OF REFERENCE TO NEC 600.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-12 Cont ID  
Sent By wjolin Date 2013-12-12 Time 13:45 Rev Time 0.00
Received By wjolin Date 2013-12-12 Time 11:00 Sent To  
Notes
2013-12-12 13:19:561016 CLARE AVENUE - SUITE #1 
 PERMIT #13110818
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO
  
 SHEET D1.0: PLAN INCORRECTLY INDICATES THIS BUILDING TO
 BE A TYPE VB BUILDING.
  
 SHEET A1.0: PROVIDE A STORAGE LAYOUT PLAN FOR THE LARGE
 STORAGE ROOM.
  
 SHEET A1.0: PLEASE INDICATE THE FOLLOWING FOR THE
 STORAGE INTENDED FOR THE LARGE STORAGE ROOM:
 1) COMMODITY CLASS
 2) STORAGE ARRANGEMENT (PALLETS, RACKS, SHELVING, ETC.)
 3) HEIGHT OF STORAGE
 4) WILL STORAGE WILL BE IN BINS, BOXES OR ENCAPSULATED
 (PLASTIC WRAP)
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2014-01-21 Time 11:18 Rev Time 0.00
Received By jwitmer Date 2014-01-15 Time 19:23 Sent To  
Notes
2014-01-16 19:24:33TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-13 Cont ID  
Sent By shill Date 2014-01-13 Time 17:21 Rev Time 0.00
Received By shill Date 2013-11-25 Time 13:11 Sent To  
Notes
2014-01-13 13:53:21SH DESK
  
2013-11-26 13:11:38INCOMING SENT TO C-02 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 11:57 Sent To  
Notes
2014-01-23 11:58:512004-2006 RETAIL STORE SILK STAR DECOR
 BUSINESS TAX 0000014234

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2014-01-21 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2014-01-21 Time 11:17 Sent To  
Notes
2014-01-21 11:18:09BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-12-27 Cont ID  
Sent By jwitmer Date 2013-12-27 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2013-12-27 Time 14:06 Sent To  
Notes
2013-12-27 14:06:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-19 Cont ID  
Sent By shill Date 2013-12-19 Time 15:11 Rev Time 0.00
Received By hmoser Date 2013-12-19 Time 15:11 Sent To  
Notes
2013-12-19 17:31:00REVIEW BY J SAEZ
 PX 1328
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-12-27 Cont ID  
Sent By lwagner Date 2013-12-27 Time 09:06 Rev Time 0.00
Received By lwagner Date 2013-12-27 Time 08:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-12-17 Cont ID  
Sent By lwagner Date 2013-12-17 Time 15:48 Rev Time 0.00
Received By lwagner Date 2013-12-10 Time 15:37 Sent To  
Notes
2013-12-17 15:49:14OPENED IN ERROR

Review Stop Z ZONING
Rev No 1 Status P Date 2013-12-09 Cont ID  
Sent By avann Date 2013-12-09 Time 14:13 Rev Time 0.00
Received By ajones Date 2013-12-09 Time 14:13 Sent To  
Notes
2013-12-02 11:35:2812/2/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved