Plan Review Details - Permit 13110815
Plan Review Stops For Permit 13110815
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-26 Cont ID  
Sent By shill Date 2013-12-26 Time 14:23 Rev Time 0.00
Received By shill Date 2013-12-26 Time 14:23 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By shill Date 2013-12-11 Time 18:46 Rev Time 0.00
Received By shill Date 2013-12-11 Time 18:46 Sent To  
Notes
2013-12-11 18:48:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN, FBC 107. INCLUDE PROJECTION
 OVER PROPERTY LINE, SIDEWALK, AND WIDTH OF SIDEWALK FBC
 3105.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-01-02 Cont ID  
Sent By fmittner Date 2014-01-02 Time 10:48 Rev Time 0.00
Received By fmittner Date 2014-01-02 Time 10:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-02 Cont ID  
Sent By shill Date 2014-01-02 Time 14:34 Rev Time 0.00
Received By shill Date 2013-12-18 Time 18:04 Sent To  
Notes
2013-12-26 14:24:0712/26 TO ZONING
  
2013-12-18 18:04:45SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-16 Cont ID  
Sent By shill Date 2013-12-16 Time 17:57 Rev Time 0.00
Received By shill Date 2013-11-25 Time 15:21 Sent To  
Notes
2013-12-16 17:57:21 
  
2013-12-02 10:22:41TO MSC 2 BOX.
2013-11-25 15:21:19ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-31 Cont ID  
Sent By aaponte Date 2013-12-31 Time 10:16 Rev Time 0.00
Received By aaponte Date 2013-12-31 Time 10:16 Sent To  
Notes
2013-12-26 14:52:3912/26/13 - ZONING RECEIVED. SENT TO AA FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2013-12-02 Cont ID  
Sent By aaponte Date 2013-12-02 Time 10:15 Rev Time 0.00
Received By aaponte Date 2013-11-26 Time 08:12 Sent To  
Notes
2013-12-02 10:22:231. PLEASE SUBMIT A SURVEY OF THE PROPERTY TO CONFIRM
 AWNING PROJECTION. AWNING SHALL BE SET BACK A MINIMUM
 OF 4 FEET FROM THE FACE OF CURB.
 2. BASED ON THE PICTURE OF THE PROPERTY IT DOES NOT
 SEEM THERE IS ANY SPACE FOR SEPARATION BETWEEN THE
 AWNING ABOVE THE MAIN DOOR,AND THE RETAIL AWNINGS.
 3. HAVING ONLY THE TWO AWNINGS ABOVE THE RETAIL SPACE
 WOULD BE THE MOST APPROPRIATE FOR THE BUILDING DESIGN.
 4. STAFF SUGGESTS ADDING A STRAIGHT VALANCE TO THE
 PROPOSED AWNINGS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2013-11-26 08:12:2811/26/13 - ZONING RECEIVED. SENT TO AA FOR REVIEW. LL