Plan Review Details - Permit 13110814
Plan Review Stops For Permit 13110814
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-03-26 Cont ID  
Sent By skennedy Date 2014-03-26 Time 16:16 Rev Time 0.00
Received By skennedy Date 2014-03-26 Time 16:16 Sent To  
Notes
2014-01-15 18:23:51MCDADDY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 09:24 Rev Time 0.00
Received By skennedy Date 2013-12-30 Time 09:24 Sent To  
Notes
2013-12-30 09:27:42SEE COMMENTS OF 12/12/13. NO RESPONSES WERE PROVIDED IN
 THE RESUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By skennedy Date 2013-12-12 Time 09:15 Rev Time 0.00
Received By skennedy Date 2013-12-12 Time 09:12 Sent To  
Notes
2013-12-12 09:21:54PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 PROVIDE DETAILS TO INDICATE THE METHOD INTENDED TO
 INSTALL OR SECURE THE THE GENERATOR TO THE STRUCTURE.
 PROVIDE MINMUM STRUCTURE DETAILS RELATED TO METHOD OF
 ATTACHMENT AND CAPACITY TO HANDLE CONCENTRATED LOAD OF
 EQUIPMENT. PROVIDE DETAIL FOR NECESSARY PENETRATIONS OF
 STRUCTURE TO RUN GAS PIPING AND FIRESTOPPING DETAILS
 AND MAY BE NEEDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
2013-12-10 18:56:13ELECTRIC PLACED ON SAK DESK

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-01-15 Cont ID  
Sent By skennedy Date 2014-03-14 Time 14:26 Rev Time 0.00
Received By albarran Date 2014-01-15 Time 17:02 Sent To B
Notes
2014-01-15 18:22:49BLDG. MCDUGAL DESK

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 09:29 Rev Time 0.00
Received By skennedy Date 2013-12-30 Time 09:29 Sent To  
Notes
2013-12-30 09:29:4112/30/13 - DID NOT PERFORM ELECTRICAL REVIEW, ADVISED
 CONTRACTOR TO RESUBMIT ALL COMMENTS FROM BUILDING &
 GAS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-10 Cont ID  
Sent By albarran Date 2013-12-10 Time 18:44 Rev Time 0.00
Received By albarran Date 2013-12-10 Time 17:56 Sent To B
Notes
2013-12-10 18:51:22THE FOLLOWING CORRECTIONS NEED TO BE MADE FOR THE NEXT
 PLAN REVIEW:
 1.PROVIDE COMPLETE LITERATURE PACKAGE FOR GENERATOR AND
 TRANSFER GEAR.
 2. SHOW ELEVATIONS FOR THE METER ROOM IF INTENTIONS ARE
 TOP PLACE PANEL 6G BELOW EXISTING PANEL L2C
 3. INCLUDE A COMPLETE LEGEND FOR BETTER UNDERSTANDING
 OF YOUR RISER DIAGRAM
 4. PROVIDE LOAD CALC & A PANEL SCHEDULE FOR PANEL H6
 5. CORRECT THE NOMENCLATURE FOR THE TRANSFORMER, OR
 EXPLAIN WHAT A SINGLE PHASE TRANSFORMER IS DOING THERE.
 6. COMPLETE THE RISER DIAGRAM FOR THE PENTHOUSE LEVEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-17 Cont ID  
Sent By wjolin Date 2014-01-17 Time 11:46 Rev Time 0.00
Received By wjolin Date 2014-01-17 Time 11:27 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2014-03-26 Cont ID  
Sent By skennedy Date 2014-03-26 Time 16:16 Rev Time 0.00
Received By skennedy Date 2014-03-26 Time 16:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2014-01-16 Cont ID  
Sent By skennedy Date 2014-01-16 Time 13:48 Rev Time 0.00
Received By skennedy Date 2014-01-16 Time 13:48 Sent To FIRE
Notes
2014-01-16 14:16:28PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE GENERATOR SPECS INDICATE NG CONSUMPTION AT 359
 FT3/HR. SHEET P0.1 INDICATES A 250' LONG, 1" PIPE WHICH
 ONLY SUPPLIES 119. SPOKE TO GORDON MEYERS OF KAMM. HE
 IS TO REEVALUATE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 09:27 Rev Time 0.00
Received By skennedy Date 2013-12-30 Time 09:27 Sent To  
Notes
2013-12-30 09:28:04SEE COMMENTS OF 12/12/13. NO RESPONSES WERE PROVIDED IN
 THE RESUBMITTAL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By lwagner Date 2013-12-12 Time 08:48 Rev Time 0.00
Received By lwagner Date 2013-12-12 Time 08:43 Sent To  
Notes
2013-12-12 08:45:53FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 PLEASE SUBMIT MANUFACTURE SHEETS FOR THE GAS EQUIPMENT
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58,
 AND FBC-2010 FUEL GAS SEC. 402.2
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-03-26 Cont ID  
Sent By skennedy Date 2014-03-26 Time 16:17 Rev Time 0.00
Received By skennedy Date 2014-03-20 Time 12:32 Sent To  
Notes
2014-03-20 12:32:28TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-03-14 Cont ID  
Sent By skennedy Date 2014-03-14 Time 14:27 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 14:27 Sent To  
Notes
2014-03-14 14:28:49INFORMED LEIGHANN OF CARPENTER ELECTRIC THAT THE
 RESUBMITTAL IS NOT ACCEPTABLE AS THE DOCUMENTS ARE NOT
 ORIGINALS NOR SIGNED & SEALED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-14 Cont ID  
Sent By skennedy Date 2014-01-23 Time 14:26 Rev Time 0.00
Received By skennedy Date 2014-01-11 Time 08:52 Sent To E
Notes
2014-01-15 16:06:46SENT TO MIKE ALBARRAN DESK.
2014-01-15 08:38:3201/15/14 ? SPOKE TO SHANNON, PERMIT RUNNER, JOANN IS TO
 COME TO BD AND COLLATE THE SUBMITTAL INTO THREE
 SEPARATELY BOUND UPDATED SETS. THEN FORWARD TO SAK
 PLEASE. FILED IN LARGE DENIED C.
2014-01-11 08:52:39TO PLUMBING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 09:28 Rev Time 0.00
Received By skennedy Date 2013-12-16 Time 09:19 Sent To  
Notes
2013-12-17 09:19:49RESUBMITTAL SENT TO ELECTRIC SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-12 Cont ID  
Sent By skennedy Date 2013-12-12 Time 09:22 Rev Time 0.00
Received By skennedy Date 2013-11-26 Time 13:00 Sent To  
Notes
2013-11-26 13:01:25INCOMING SENT TO ELECTRIC BOX. JW

Review Stop Z ZONING
Rev No 2 Status P Date 2014-03-26 Cont ID  
Sent By Jroach Date 2014-03-26 Time 14:46 Rev Time 0.00
Received By jroach Date 2014-03-20 Time 13:07 Sent To  
Notes
2014-03-26 14:46:19PROVISO
  
 1. ALL EQUIPMENT LOCATED ABOVE THE HEIGHT OF THE
 PARAPET WALL SHALL BE PAINTED TO MATCH THE COLOR OF
 THAT PORTION OF THE BUILDING IMMEDIATELY ADJACENT TO
 THE GENERATOR (I.E. WHITE).
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  
2014-03-20 13:07:353/20/14 ZONING RECEIVED, SENT TO JR. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-01-23 Cont ID  
Sent By jroach Date 2014-01-23 Time 11:45 Rev Time 0.00
Received By jroach Date 2014-01-17 Time 15:41 Sent To B
Notes
2014-01-23 11:46:24ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.23.2014
 PERMIT NO.: 13110814
 ADDRESS: 1700 PALM BEACH LAKE BOULEVARD
 CONTRACTOR/CONTACT: NICK
 TELEPHONE NO.: 561.848.7881
 SCOPE OF REVIEW: NEW GENERATOR
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE LOCATION OF THE PROPOSED (AS WELL AS EXISTING)
 GENERATOR APPEARS TO BE INCORRECT. THE LOCATION
 INDICATED ON THE PLANS IS THE RAMP LEADING TO THE TOP
 LEVEL OF THE PARKING GARAGE. THIS SHOULD NOT BE BLOCKED
 AS IT RESULTS IN A LOSS OF PARKING SPACES FOR THE
 BUILDING. I BELIEVE THE EXISTING GENERATOR IS LOCATED
 OUT FROM UNDERNEATH THE TOWER IN THE DEAD-END (NO
 PARKING) SECTION OF THE TOP LEVEL OF THE GARAGE.
  
 2. IF THE PROPOSED GENERATOR IS LOCATED OUTSIDE,
 ADJACENT TO THE PARAPET WALL, PLEASE PROVIDE A DETAIL
 SHOWING THE OVERALL HEIGHT OF THE GENERATOR RELATIVE TO
 THE PARAPET WALL, ETC. THE GENERATOR SHALL NOT BE
 VISIBLE FROM THE PUBLIC RIGHT-OF-WAY OR ADJACENT
 PROPERTIES.
  
 3. AS WAS REQUIRED OF THE EXISTING GENERATOR, IF THE
 PROPOSED GENERATOR IS BEING LOCATED OUTSIDE, THEN IT
 SHALL BE PAINTED TO MATCH THE COLOR OF THE EXISTING
 STRUCTURE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-01-17 15:42:021/17/14 - ZONING RECEIVED. ROUTED TO JR PER SKENNEDY.
 LL