Plan Review Stops For Permit 13110774 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2013-12-03 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-12-03 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-12-03 |
Time |
09:52 |
Sent To |
|
|
Notes |
2013-12-03 11:04:30 | 6751 NORTH JOG ROAD - VISITOR'S CENTER | | TRACKING #13110774 | | PERMIT #12080615 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE HYDRAULIC CALCULATIONS SUBMITTED ARE FOR THE 3RD | | FLOOR AREA (207 GPM @60 PSI); HOWEVER, THE 2ND FLOOR | | AREA INDICATES A GREATER HYDRAULICA DEMAND (360 GPM @72 | | PSI). SUBMIT THE HYDRAULIC CALCULATIONS FOR THE SECOND | | FLOOR REMOTE AREA. | | | | SUBMIT AN ADDITIONAL SET OF HYDRAULIC CALCULATIONS | | UTILIZING ONLY CITY FLOW/PRESSURE AS THE VISITOR'S | | CENTER BUILDING HAS BEEN REQUESTED TO RECEIVE TEMPORARY | | OCCUPANCY BEFORE THE NEW FIRE PUMPS ARE TO BE | | INSTALLED, INPSECTED, TESTED, AND APPROVED. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE INSPECTOR & FIRE INVESTIGATOR | | T: 561-804-4752 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-12-13 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-12-13 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-11-05 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2013-11-23 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2013-11-23 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2013-11-23 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
|