Plan Review Details - Permit 13110774
Plan Review Stops For Permit 13110774
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By wjolin Date 2013-12-03 Time 11:04 Rev Time 0.00
Received By wjolin Date 2013-12-03 Time 09:52 Sent To  
Notes
2013-12-03 11:04:306751 NORTH JOG ROAD - VISITOR'S CENTER
 TRACKING #13110774
 PERMIT #12080615
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE HYDRAULIC CALCULATIONS SUBMITTED ARE FOR THE 3RD
 FLOOR AREA (207 GPM @60 PSI); HOWEVER, THE 2ND FLOOR
 AREA INDICATES A GREATER HYDRAULICA DEMAND (360 GPM @72
 PSI). SUBMIT THE HYDRAULIC CALCULATIONS FOR THE SECOND
 FLOOR REMOTE AREA.
  
 SUBMIT AN ADDITIONAL SET OF HYDRAULIC CALCULATIONS
 UTILIZING ONLY CITY FLOW/PRESSURE AS THE VISITOR'S
 CENTER BUILDING HAS BEEN REQUESTED TO RECEIVE TEMPORARY
 OCCUPANCY BEFORE THE NEW FIRE PUMPS ARE TO BE
 INSTALLED, INPSECTED, TESTED, AND APPROVED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE INSPECTOR & FIRE INVESTIGATOR
 T: 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-13 Cont ID  
Sent By skennedy Date 2013-12-13 Time 09:46 Rev Time 0.00
Received By skennedy Date 2013-11-05 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-23 Cont ID  
Sent By rregueir Date 2013-11-23 Time 13:57 Rev Time 0.00
Received By rregueir Date 2013-11-23 Time 13:57 Sent To  
Notes
***NONE***