Plan Review Details - Permit 13110732
Plan Review Stops For Permit 13110732
Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By albarran Date 2014-02-03 Time 10:37 Sent To  
Notes
2014-02-03 10:49:47I CALLED PANEL ELECTRIC FOR MORE INFORMATION AND
 COMMENTS. THE SUBMITTED DRAWING DOES NOT MEET THE NEC
 250.66 REQUIREMENTS FOR THE GEC.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 10:53 Rev Time 0.00
Received By skennedy Date 2013-12-30 Time 10:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-03 Cont ID  
Sent By albarran Date 2013-12-03 Time 08:48 Rev Time 0.00
Received By albarran Date 2013-12-03 Time 08:48 Sent To I
Notes
2013-12-03 08:52:36THERE IS NOT SUFFICIENT DETAIL ON THE SUBMITTED PLANS
 FOR APPROVAL. PROVIDE A BETTER DESCRIPTION OF THE SCOPE
 OF WORK. EXPLAIN HOW MUCH OF THIS/THESE SERVICE/S ARE
 EXISTING AND WHAT WILL BE REPLACED. ARE ALL 5 SERVICES
 TYPICAL AND WHAT IS THE WIRE INSULATION OF BOTH THE
 EXISTING IF TO REMAIN AND THE NEW. BEAR IN MIND THE
 2008 NEC REQUIREMENTS FOR UNDERGROUND WIRING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-30 Cont ID  
Sent By skennedy Date 2013-12-30 Time 10:53 Rev Time 0.00
Received By skennedy Date 2013-12-14 Time 10:38 Sent To  
Notes
2013-12-14 10:38:16TO ELECTRICAL
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-03 Cont ID  
Sent By shill Date 2013-12-03 Time 17:42 Rev Time 0.00
Received By shill Date 2013-11-22 Time 09:59 Sent To  
Notes
2013-12-03 08:53:03SENT TO SK FOR PROCESSING
2013-11-22 10:00:09ROUTED TO ELECTRICAL LESS THAN 5000