Plan Review Details - Permit 13110378
Plan Review Stops For Permit 13110378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-14 Cont ID  
Sent By rmcdouga Date 2013-11-14 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2013-11-14 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-13 Cont ID  
Sent By rmcdouga Date 2013-11-13 Time 06:52 Rev Time 0.00
Received By rmcdouga Date 2013-11-13 Time 06:52 Sent To  
Notes
2013-11-13 08:13:162010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT SPECIFICATIONS AND TESTING INFORMATION FOR
 THE PROFLEX 90 SOUND PROOFING. SHOW THAT IT COMPLIES
 WITH THE SOUND TRANSMISSION REQUIREMENTS OF FBC 1207.2
 AIR-BOURNE SOUND AND FBC 1207.3 STRUCTURE-BORNE SOUND,
 AS WELL AS, THE FLAME SPREAD INDEX AND SMOKE-DEVELOPED
 INDEX TO SHOW COMPLIANCE WITH FBC 603.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2013-11-13 Cont ID  
Sent By rmcdouga Date 2013-11-13 Time 06:53 Rev Time 0.00
Received By rmcdouga Date 2013-11-13 Time 06:53 Sent To  
Notes
2013-11-13 06:54:02NO ELECTRICAL WORK SHOWN ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-11-13 Cont ID  
Sent By rmcdouga Date 2013-11-13 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2013-11-13 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-14 Cont ID  
Sent By rmcdouga Date 2013-11-14 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2013-11-13 Time 15:29 Sent To  
Notes
2013-11-13 15:37:21INCOMING SENT TO R. MCDOUGAL. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-13 Cont ID  
Sent By rmcdouga Date 2013-11-13 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2013-11-08 Time 06:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-13 Cont ID  
Sent By rmcdouga Date 2013-11-13 Time 06:50 Rev Time 0.00
Received By rmcdouga Date 2013-11-13 Time 06:50 Sent To  
Notes
2013-11-13 06:51:27REMOVE AND REPLACE FIXTURES IN THE SAME LOCATIONS.
 PLUMBING SUB-PERMIT REQUIRED.