Plan Review Details - Permit 13110309
Plan Review Stops For Permit 13110309
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-02-03 Cont ID  
Sent By rmcdouga Date 2014-02-03 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2014-02-03 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-13 Cont ID  
Sent By rmcdouga Date 2013-12-13 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2013-12-13 Time 16:00 Sent To  
Notes
2013-12-13 16:05:012010 FBC
  
 1) THE GEOTECHNICAL REPORT RECOMMENDS THAT THE WEST
 SIDE OF THE BOARDWALK WILL BE PARTIALLY OR FULLY
 SUPPORTED ON SHALLOW FOOTINGS. PLEASE CLARIFY THE
 LOCATIONS OF THE SHALLOW FOOTINGS. CITY AMENDMENTS
 107.2.1
  
 2) THE STRUCTURAL DRAWINGS LIST A ROOF LIVE LOAD OF 80
 PSF. THERE IS NO ROOF SHOWN ON THE DRAWING. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 3) SPECIFY THE UNIFORM LIVE LOAD OF THE WALKWAY ON THE
 DRAWINGS. FBC 1607
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-01-31 Cont ID  
Sent By Mgonzale Date 2014-01-31 Time   Rev Time 0.25
Received By   Date 2014-01-31 Time   Sent To B
Notes
2014-01-31 13:28:12NO OBJECTION.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2013-12-10 Cont ID  
Sent By Mgonzale Date 2013-12-10 Time   Rev Time 1.00
Received By mgonzale Date 2013-12-10 Time   Sent To B
Notes
2013-12-10 05:51:07ADDRESS PROPERTY LINE ENCROACHMENT AS STATED BY
 PLANNING.
  
 PLEASE REPLY AS TO WHOM WILL BE RESPONSIBLE FOR FUTURE
 MAINTENANCE AND REPAIR OF BOARDWALK.
  
 PLEASE REPLY AS TO WHOM WILL THE BOARDWALK BE CONVEYED
 TO AFTER DEVELOPER PUTS IN SERVICE.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-03 Cont ID  
Sent By rmcdouga Date 2014-02-03 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2014-01-10 Time 14:20 Sent To  
Notes
2014-01-10 14:20:48SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-13 Cont ID  
Sent By rmcdouga Date 2013-12-13 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2013-11-08 Time 13:56 Sent To  
Notes
2013-12-10 10:11:0312/10 TO RM DESK
  
2013-11-12 13:57:16SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2014-01-30 Cont ID  
Sent By eschnied Date 2014-01-30 Time 18:15 Rev Time 0.25
Received By eschneid Date 2014-01-10 Time 16:55 Sent To ENG
Notes
2014-01-10 16:56:201/10/14 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2013-11-20 Cont ID  
Sent By eschneid Date 2013-11-20 Time 18:01 Rev Time 0.50
Received By eschneid Date 2013-11-13 Time 09:17 Sent To ENG
Notes
2013-11-20 18:09:39FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE BOARDWALK IS SHOWN WITH AN OVERHANG OF THE
 PROPERTY LINE AND THUS ENCROACHING INTO CITY PROPERTY.
 THE ENTIRE BOARDWALK SHALL BE ON THE OAKTON PRESERVE
 PROPERTY.
  
 2) THE DESIGN GUIDELINES REQUIRE THAT WALKWAYS BE A
 MINIMUM OF SIX (6) FEET WIDE WITH THE ALLOWANCE THAT
 THE BOARDWALK IS REQUIRED TO HAVE A MINIMUM OF FIVE (5)
 FEET BETWEEN THE RAILINGS ON EITHER SIDE. THE PLANS
 SHOW 4' 8" BETWEEN THE INNERMOST EXTENT OF THE
 RAILINGS.
  
 3) ARE RAILINGS REQUIRED ON THE INSIDE OF THE
 BOARDWALK?
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
2013-11-13 09:17:5211/13/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL