Plan Review Details - Permit 13110168
Plan Review Stops For Permit 13110168
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-12 Cont ID  
Sent By jgomez Date 2013-11-12 Time 15:51 Rev Time 0.00
Received By jgomez Date 2013-11-12 Time 15:51 Sent To  
Notes
2013-11-12 15:54:55BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- CONTRACTOR WILL FASTEN ROOF ZONE #1 AS PER PRODUCT
 APPROVAL AND AS REQUIRED BY SEC. 8.1 OF RAS 117.
 ENGINEER TO REVISE RAS 117 CALCULATIONS ACCORDINGLY.
  
 ***NOTE: ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-08 Cont ID  
Sent By jgomez Date 2013-11-08 Time 18:10 Rev Time 0.00
Received By jgomez Date 2013-11-08 Time 17:58 Sent To  
Notes
2013-11-08 18:34:37REROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS. PAGE 15
 OF NOA 13-0129.15 SUBMITTED SHOWS BASE SHEET FASTENING
 TO BE 8"O.C. IN THE LAP AND "THREE" ADDITIONAL ROWS IN
 THE FIELD AT 8"O.C. THIS IS THE FASTENING THAT NEEDS TO
 BE USED FOR ROOF ZONE ONE AS REQUIRED BY SEC. 8.1 OF
 RAS 117. ENGINEER SPECIFIED TWO ROWS IN MID-SHEET
 INSTEAD OF THREE. THIS NEED TO BE REVISED.
  
 ***NOTE: ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-12 Cont ID  
Sent By jgomez Date 2013-11-12 Time 15:51 Rev Time 0.00
Received By jgomez Date 2013-11-12 Time 15:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-08 Cont ID  
Sent By jgomez Date 2013-11-08 Time 17:59 Rev Time 0.00
Received By jgomez Date 2013-11-08 Time 17:59 Sent To  
Notes
***NONE***