Plan Review Details - Permit 13110011
Plan Review Stops For Permit 13110011
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-02-11 Cont ID  
Sent By JWITMER Date 2014-02-11 Time 12:04 Rev Time 0.00
Received By shill Date 2014-02-08 Time 07:00 Sent To  
Notes
2014-02-11 12:04:41OK PER JW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-16 Cont ID  
Sent By jwitmer Date 2013-11-16 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2013-11-16 Time 08:45 Sent To  
Notes
2013-11-16 09:18:32BUILDING PLAN REVIEW
 PERMIT: 13110011
 ADD: 250 S AUSTRALIAN AVE/ ELEVATOR SHAFT
 PRESSURIZATION
 CONT: CHANDLER CONSTRUCTION
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 16/ 2013
 ACTION: DENIED
  
 1) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 708.14.2.2
 RATIONAL ANALYSIS. A RATIONAL ANALYSIS COMPLYING WITH
 SECTION 909.4 SHALL BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 2010 FBC-B 909.4 A RATIONAL ANALYSIS SUPPORTING THE
 TYPES OF SMOKE CONTROL SYSTEMS TO BE EMPLOYED, THEIR
 METHODS OF OPERATION, THE SYSTEMS SUPPORTING THEM AND
 THE METHODS OF CONSTRUCTION TO BE UTILIZED SHALL
 ACCOMPANY THE SUBMITTED CONSTRUCTION DOCUMENTS AND
 SHALL INCLUDE, BUT NOT BE LIMITED TO, THE ITEMS
 INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6.
  
 [F] 909.4.1 STACK EFFECT.
 THE SYSTEM SHALL BE DESIGNED SUCH THAT THE MAXIMUM
 PROBABLE NORMAL OR REVERSE STACK EFFECT WILL NOT
 ADVERSELY INTERFERE WITH THE SYSTEM?S CAPABILITIES. IN
 DETERMINING THE MAXIMUM PROBABLE STACK EFFECT,
 ALTITUDE, ELEVATION, WEATHER HISTORY AND INTERIOR
 TEMPERATURES SHALL BE USED.
  
 [F] 909.4.2 TEMPERATURE EFFECT OF FIRE.
 BUOYANCY AND EXPANSION CAUSED BY THE DESIGN FIRE IN
 ACCORDANCE WITH SECTION 909.9 SHALL BE ANALYZED. THE
 SYSTEM SHALL BE DESIGNED SUCH THAT THESE EFFECTS DO NOT
 ADVERSELY INTERFERE WITH THE SYSTEM?S CAPABILITIES.
  
 [F] 909.4.3 WIND EFFECT.
 THE DESIGN SHALL CONSIDER THE ADVERSE EFFECTS OF WIND.
 SUCH CONSIDERATION SHALL BE CONSISTENT WITH THE
 WIND-LOADING PROVISIONS OF CHAPTER 16.
  
 [F] 909.4.4 HVAC SYSTEMS.
 THE DESIGN SHALL CONSIDER THE EFFECTS OF THE HEATING,
 VENTILATING AND AIR-CONDITIONING (HVAC) SYSTEMS ON BOTH
 SMOKE AND FIRE TRANSPORT. THE ANALYSIS SHALL INCLUDE
 ALL PERMUTATIONS OF SYSTEMS STATUS. THE DESIGN SHALL
 CONSIDER THE EFFECTS OF THE FIRE ON THE HVAC SYSTEMS.
  
 [F] 909.4.5 CLIMATE.
 THE DESIGN SHALL CONSIDER THE EFFECTS OF LOW
 TEMPERATURES ON SYSTEMS, PROPERTY AND OCCUPANTS. AIR
 INLETS AND EXHAUSTS SHALL BE LOCATED SO AS TO PREVENT
 SNOW OR ICE BLOCKAGE.
  
 [F] 909.4.6 DURATION OF OPERATION.
 ALL PORTIONS OF ACTIVE OR PASSIVE SMOKE CONTROL SYSTEMS
 SHALL BE CAPABLE OF CONTINUED OPERATION AFTER DETECTION
 OF THE FIRE EVENT FOR A PERIOD OF NOT LESS THAN EITHER
 20 MINUTES OR 1.5 TIMES THE CALCULATED EGRESS TIME,
 WHICHEVER IS LESS.
  
 2) SHEET M5.1 INDICATES THE ELEVATOR LEAKAGE CALULATION
 TO BE 300 300 CFM PER DOOR. 707.14.2.3.4 FAN CAPACITY
 INDICATES THE ADJUSTABLE FAN BE ABLE TO MEET 1,000 CFM
 OR THE DESIGN PROFESSIONAL CAN DESIGN THE SYSTEM TO
 OPERATE IN THE RANGE OF 0.04 TO 0.06 INCHES OF WATER
 COLUMN SPECIFIED IN THE PRESSURE REQUIREMENTS OF
 SECTION 708.14.2.1. PLEASE PROVIDE THE CALCULATION
 PORTION FOR THE REQUIRED 0.04 TO 0.06 WATER COLUMN.
  
  
 3) 708.14.2.8 MARKING AND IDENTIFICATION. DETECTION AND
 CONTROL SYSTEMS SHALL BE MARKED IN ACCORDANCE WITH
 SECTION 909.14.
 [F] 909.14 MARKING AND IDENTIFICATION.
 THE DETECTION AND CONTROL SYSTEMS SHALL BE CLEARLY
 MARKED AT ALL JUNCTIONS, ACCESSES AND TERMINATIONS.
  
 4) 708.14.2.9 CONTROL DIAGRAMS. CONTROL DIAGRAMS SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 909.15.
 [F] 909.15 CONTROL DIAGRAMS.
 IDENTICAL CONTROL DIAGRAMS SHOWING ALL DEVICES IN THE
 SYSTEM AND IDENTIFYING THEIR LOCATION AND FUNCTION
 SHALL BE MAINTAINED CURRENT AND KEPT ON FILE WITH THE
 BUILDING OFFICIAL, THE FIRE DEPARTMENT AND IN THE FIRE
 COMMAND CENTER IN A FORMAT AND MANNER APPROVED BY THE
 FIRE CHIEF.
  
 5) 708.14.2.10 CONTROL PANEL. A CONTROL PANEL COMPLYING
 WITH SECTION 909.16 SHALL BE PROVIDED.
 [F] 909.16 FIRE-FIGHTER?S SMOKE CONTROL PANEL.
 A FIRE-FIGHTER?S SMOKE CONTROL PANEL FOR FIRE
 DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE
 PROVIDED AND SHALL INCLUDE MANUAL CONTROL OR OVERRIDE
 OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE CONTROL
 SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE COMMAND
 CENTER COMPLYING WITH SECTION 911 IN HIGHRISE BUILDINGS
 OR BUILDINGS WITH SMOKE-PROTECTED ASSEMBLY SEATING. IN
 ALL OTHER BUILDINGS, THE FIRE-FIGHTER?S SMOKE CONTROL
 PANEL SHALL BE INSTALLED IN AN APPROVED LOCATION
 ADJACENT TO THE FIRE ALARM CONTROL PANEL. THE
 FIRE-FIGHTER?S SMOKE CONTROL PANEL SHALL COMPLY WITH
 SECTIONS 909.16.1 THROUGH 909.16.3.
  
 [F] 909.16.1 SMOKE CONTROL SYSTEMS.
 FANS WITHIN THE BUILDING SHALL BE SHOWN ON THE
 FIRE-FIGHTER?S CONTROL PANEL. A CLEAR INDICATION OF THE
 DIRECTION OF AIRFLOW AND THE RELATIONSHIP OF COMPONENTS
 SHALL BE DISPLAYED. STATUS INDICATORS SHALL BE PROVIDED
 FOR ALL SMOKE CONTROL EQUIPMENT, ANNUNCIATED BY FAN AND
 ZONE, AND BY PILOT-LAMP-TYPE INDICATORS AS FOLLOWS:
 1. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN THEIR
 NORMAL STATUS?WHITE.
 2. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN THEIR
 OFF OR CLOSED STATUS?RED.
 3. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN THEIR
 ON OR OPEN STATUS?GREEN.
 4. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN A
 FAULT STATUS?YELLOW/AMBER.
  
 [F] 909.16.2 SMOKE CONTROL PANEL.
 THE FIRE-FIGHTER?S CONTROL PANEL SHALL PROVIDE CONTROL
 CAPABILITY OVER THE COMPLETE SMOKE-CONTROL SYSTEM
 EQUIPMENT WITHIN THE BUILDING AS FOLLOWS:
 1. ON-AUTO-OFF CONTROL OVER EACH INDIVIDUAL PIECE OF
 OPERATING SMOKE CONTROL EQUIPMENT THAT CAN ALSO BE
 CONTROLLED FROM OTHER SOURCES WITHIN THE BUILDING. THIS
 INCLUDES STAIRWAY PRESSURIZATION FANS; SMOKE EXHAUST
 FANS; SUPPLY, RETURN AND EXHAUST FANS; ELEVATOR SHAFT
 FANS AND OTHER OPERATING EQUIPMENT USED OR INTENDED FOR
 SMOKE CONTROL PURPOSES.
 2. OPEN-AUTO-CLOSE CONTROL OVER INDIVIDUAL DAMPERS
 RELATING TO SMOKE CONTROL AND THAT ARE ALSO CONTROLLED
 FROM OTHER SOURCES WITHIN THE BUILDING.
 3. ON-OFF OR OPEN-CLOSE CONTROL OVER SMOKE CONTROL AND
 OTHER CRITICAL EQUIPMENT ASSOCIATED WITH A FIRE OR
 SMOKE EMERGENCY AND THAT CAN ONLY BE CONTROLLED FROM
 THE FIRE-FIGHTER?S CONTROL PANEL.
 EXCEPTIONS:
 1. COMPLEX SYSTEMS, WHERE APPROVED, WHERE THE CONTROLS
 AND INDICATORS ARE COMBINED TO CONTROL AND INDICATE ALL
 ELEMENTS OF A SINGLE SMOKE ZONE AS A UNIT.
 2. COMPLEX SYSTEMS, WHERE APPROVED, WHERE THE CONTROL
 IS ACCOMPLISHED BY COMPUTER INTERFACE USING APPROVED,
 PLAIN ENGLISH COMMANDS.
  
 6) 708.14.2.11 SYSTEM RESPONSE TIME. HOISTWAY
 PRESSURIZATION SYSTEMS SHALL COMPLY WITH THE
 REQUIREMENTS FOR SMOKE CONTROL SYSTEM RESPONSE TIME IN
 SECTION 909.17.
 [F] 909.17 SYSTEM RESPONSE TIME.
 SMOKE-CONTROL SYSTEM ACTIVATION SHALL BE INITIATED
 IMMEDIATELY AFTER RECEIPT OF AN APPROPRIATE AUTOMATIC
 OR MANUAL ACTIVATION COMMAND. SMOKE CONTROL SYSTEMS
 SHALL ACTIVATE INDIVIDUAL COMPONENTS (SUCH AS DAMPERS
 AND FANS) IN THE SEQUENCE NECESSARY TO PREVENT PHYSICAL
 DAMAGE TO THE FANS, DAMPERS, DUCTS AND OTHER EQUIPMENT.
 FOR PURPOSES OF SMOKE CONTROL, THE FIRE-FIGHTER?S
 CONTROL PANEL RESPONSE TIME SHALL BE THE SAME FOR
 AUTOMATIC OR MANUAL SMOKE CONTROL ACTION INITIATED FROM
 ANY OTHER BUILDING CONTROL POINT. THE TOTAL RESPONSE
 TIME, INCLUDING THAT NECESSARY FOR DETECTION, SHUTDOWN
 OF OPERATING EQUIPMENT AND SMOKE CONTROL SYSTEM
 STARTUP, SHALL ALLOW FOR FULL OPERATIONAL MODE TO BE
 ACHIEVED BEFORE THE CONDITIONS IN THE SPACE EXCEED THE
 DESIGN SMOKE CONDITION. THE SYSTEM RESPONSE TIME FOR
 EACH COMPONENT AND THEIR SEQUENTIAL RELATIONSHIPS SHALL
 BE DETAILED IN THE REQUIRED RATIONAL ANALYSIS AND
 VERIFICATION OF THEIR INSTALLED CONDITION REPORTED IN
 THE REQUIRED FINAL REPORT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-02-19 Cont ID  
Sent By albarran Date 2014-02-19 Time 13:14 Rev Time 0.00
Received By albarran Date 2014-02-19 Time 13:13 Sent To M
Notes
2014-02-19 13:15:34RETURNED TO BIN B27 FOR MECHANICAL REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-02 Cont ID  
Sent By albarran Date 2014-01-02 Time 10:49 Rev Time 0.00
Received By albarran Date 2014-01-02 Time 10:04 Sent To I
Notes
2014-01-02 11:03:50THE FOLLOWING ITEMS NEED TO BE ADDRESSED:
 1. CONTROL WIRE INSULATION AS PER NEC 620.11(B)
 2. INDICATE CONDUCTOR INSULATION AS INDICATED IN NEC
 620.36 AS WELL AS RACEWAY TYPE FROM PANEL "1XA" TO
 PANEL "PBX"
 3. SHOW THE PROPOSED FANS ON THE RISER DIAGRAM.
 4. INDICATE PROPER GROUNDING AS PER NEC 620.82 OR 83
 5. PROVIDE ELECTRICAL DETAILS FOR "ESF1" & "ESF2"
 6. INDICATE ALL RACEWAY TYPES AND CONDUCTOR INSULATION
 ON DRAWINGS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-02-14 Cont ID  
Sent By wjolin Date 2014-02-14 Time 11:04 Rev Time 0.00
Received By wjolin Date 2014-02-14 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-22 Cont ID  
Sent By wjolin Date 2013-11-22 Time 12:43 Rev Time 0.00
Received By wjolin Date 2013-11-22 Time 11:24 Sent To  
Notes
2013-11-22 12:41:44250 SOUTH AUSTRALIAN AVENUE
 PERMIT #13110011
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 MEANS FOR MANUAL OPERATION OF SMOKE CONTROL SYSTEMS
 SHALL BE PROVIDED AT A LOCATION APPROVED BY THE AHJ.
  
 PROVIDE A GRAPHIC FIREFIGHTER'S SMOKE CONTROL STATION
 (FSCS) SHOWING THE FAN CONTROLS AND HVAC SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-13 Cont ID  
Sent By hmoser Date 2014-03-13 Time 14:13 Rev Time 0.00
Received By hmoser Date 2014-01-29 Time 09:21 Sent To  
Notes
2014-01-30 09:15:39B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-02 Cont ID  
Sent By shill Date 2014-01-02 Time 18:17 Rev Time 0.00
Received By shill Date 2013-11-01 Time 08:35 Sent To  
Notes
2014-01-02 11:04:10SH
2013-11-04 11:35:25SENT TO B27 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-03-13 Cont ID  
Sent By hmoser Date 2014-03-13 Time 14:13 Rev Time 0.00
Received By hmoser Date 2014-03-13 Time 14:13 Sent To  
Notes
2014-02-19 13:14:58BACK TO BIN B27

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-18 Cont ID  
Sent By hmoser Date 2013-12-18 Time 15:40 Rev Time 0.00
Received By hmoser Date 2013-12-18 Time 13:57 Sent To  
Notes
2013-12-18 15:40:32PLAN DENIED
 1) PROVIDE A DETAIL SHOWING WHAT THE ELEVATOR PRESSURE
 ARE IN ALARM AT EACH FLOOR
 2) PROVIDE THE SEQUENCE OF OPERATION OF THE ELEVATORS
 IN BUILDING ALARM.
 3) PROVIDE ANCHOR SIZE WHERE FAN MOUNTS TO WALL.WALL
 FAN DETAIL PAGE M5.1
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676