Plan Review Details - Permit 13101138
Plan Review Stops For Permit 13101138
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-18 Cont ID  
Sent By rmcdouga Date 2013-12-18 Time 06:56 Rev Time 0.00
Received By rmcdouga Date 2013-12-17 Time 18:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-05 Cont ID  
Sent By rmcdouga Date 2013-12-05 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2013-12-05 Time 06:09 Sent To  
Notes
2013-12-04 18:05:492010 FBC
  
 DENIED BY BUILDING
  
 1) FOR RE-ROOFING OF THE UTILITY ROOM. SPECIFY THE
 FASTENING OPTION LISTED ON PAGE 17 OF NOA NO.
 07-1219.09 THAT WILL BE USED TO INSTALL THIS SYSTEM.
 SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AT THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #7 ON PAGE 19 OF THE PRODUCT APPROVAL.
  
 2) BASED ON THE CONTRACT THAT WAS SUBMITTED THE PERMIT
 VALUE FOR THE WORK WAS INCREASED FROM $ 25,900.00 TO $
 53,500.00. CITY AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-18 Cont ID  
Sent By rmcdouga Date 2013-12-18 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2013-12-17 Time 18:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-04 Cont ID  
Sent By rmcdouga Date 2013-12-04 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2013-12-04 Time 18:52 Sent To  
Notes
2013-12-04 18:58:302010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SUBMIT TWO SETS OF LOAD CALCULATIONS FOR THE
 DWELLING UNIT INCLUDING ALL OF THE NEW ELECTRICAL
 EQUIPMENT. CITY AMENDMENTS 107.3.5.3
  
 2) SUBMIT TWO COPIES OF A PANEL SCHEDULE FOR THE
 EXISTING SERVICE INCLUDING ALL NEW AND UPGRADED
 CIRCUITS. CITY AMENDMENTS 107.3.5.3
  
 3) SUBMIT THE SPECIFICATIONS WITH THE ELECTRICAL
 REQUIREMENTS FOR THE NEW TANKLESS ELECTRIC WATER
 HEATER. NEC 110.3(B)
  
 4) THE SMOKE ALARMS ARE TO BE LOCATED IN THE SLEEPING
 ROOMS SO THAT THEY WILL PROVIDE THE MOST EFFECTIVE
 COVERAGE IN ACCORDANCE WITH THEIR LISTING/LABELING. NEC
 110.3(B)
  
 5) THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE
 ELECTRICAL DRAWINGS. FS 471.003(2)(H)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-18 Cont ID  
Sent By rmcdouga Date 2013-12-18 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2013-12-16 Time 10:44 Sent To  
Notes
2013-12-16 10:44:44RESUBMITTAL SENT TO R. MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-05 Cont ID  
Sent By rmcdouga Date 2013-12-05 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2013-10-31 Time 10:25 Sent To  
Notes
2013-11-04 10:26:45INCOMING SENT TO BIN R-08. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-18 Cont ID  
Sent By rmcdouga Date 2013-12-18 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2013-12-17 Time 18:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-04 Cont ID  
Sent By rmcdouga Date 2013-12-04 Time 18:05 Rev Time 0.00
Received By rmcdouga Date 2013-12-04 Time 18:05 Sent To  
Notes
2013-12-04 18:29:222010 FBC
  
 DENIED BY MECHANICAL
  
 1) A MECHANICAL PERMIT IS REQUIRED TO REPLACE THE HVAC
 EQUIPMENT AS NOTED IN THE CITY'S WORK SPECIFICATIONS.
 CITY AMENDMENTS 105.1
  
 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 AS SPECIFIED IN THE SCOPE OF WORK. FBCR M1401.3
  
 3) SUBMIT TWO SETS OF MECHANICAL PLANS SHOWING THE
 LOCATION OF THE EQUIPMENT, THE SUPPLY DUCT SIZE,
 LOCATION, GRILL SIZES, CFMS AT EACH SUPPLY OUTLET AND
 THE RETURN DUCT SIZE, LOCATION, GRILL SIZES. CITY
 AMENDMENTS 107.3.5.3
  
 4) SHOW COMPLIANCE WITH BALANCED RETURN AIR AS REQUIRED
 BY FBCR M1602.4.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT IS
 CONSISTENT WITH THE SIZING CALCULATIONS. THE NAME AN
 LICENSE NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN
 IS REQUIRED ON THE MECHANICAL PLANS. CITY AMENDMENTS
 107.2.1.3 AND FS 471.003 (2) (H)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-12-04 Cont ID  
Sent By rmcdouga Date 2013-12-04 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2013-12-04 Time 16:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-12-04 Cont ID  
Sent By rmcdouga Date 2013-12-04 Time 17:11 Rev Time 0.00
Received By rmcdouga Date 2013-12-04 Time 16:44 Sent To  
Notes
2013-12-04 17:11:02RE-ROOF - FLAT ROOF AT REAR UTILITY ROOM 49 SQFT, 9 FT
 MRH
  
 GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA NO.
 07-1219.09
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-14 Cont ID  
Sent By dkittred Date 2013-11-14 Time 11:44 Rev Time 0.00
Received By dkittred Date 2013-11-14 Time 11:41 Sent To  
Notes
2013-11-14 11:40:42PLANNING & ZONING COMMENTS:
  
 11/14/13
 PREVIOUS COMMENTS REGARDING LANDSCAPING ARE *VOID*. PER
 ANGELLA, CITY HOUSING PROJECT AND NOT REQUIRED. DK
  
2013-11-06 09:23:53PLANNING AND ZONING COMMENTS: ***FAILED***
  
 11/6/13
 THE VALUE OF THE CONSTRUCTION ($35,500) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($56,431) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
 (NOTE: ZLDR SEC. 94-442(B)(2)A. ? FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING, OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-11-05 18:10:4111/5/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved