Plan Review Details - Permit 13101127
Plan Review Stops For Permit 13101127
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By wjolin Date 2013-12-10 Time 12:44 Rev Time 0.00
Received By wjolin Date 2013-12-10 Time 12:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-19 Cont ID  
Sent By wjolin Date 2013-11-19 Time 11:13 Rev Time 0.00
Received By wjolin Date 2013-11-15 Time 12:39 Sent To M
Notes
2013-11-19 11:13:36777 SOUTH FLAGLER DRIVE - PARKING GARAGE
 PERMIT #13101127
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 COVER SHEET INDICATES A HYDROSTATIC PRESSURE TEST OF
 200 PSI. PER NFPA 13 (2007 EDITION) SECTION 24.2.1.2,
 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO SYSTEM
 WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE TESTED
 AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING PRESSURE
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR
 2-HOURS. INDICATE THE NEW HYDROSTATIC TEST PRESSURE
 ACCOUNTING FOR THE FIRE PUMP CHURN PRESSURE AND
 AVAILABLE CITY PRESSURE.
  
 THE SPRINKLER DETAIL ON THE COVER SHEET INDICATES A
 K-FACTOR OF 2.8.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR THE
 SPRINKLER DISTANCE BELOW THE CONCRETE TEES.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 NO SPRINKLER CUT-SHEETS SUBMITTED.
  
 NO NORTH ARROW OR COLUMN LINES PROVIDED ON PLANS.
  
 PLANS INDICATE A DESIGN OF ORDINARY HAZARD GROUP 1;
 HOWEVER, 8 SPRINKLERS IN DESIGN AREA 1 ARE COVERING 144
 SQ.FT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-10 Cont ID  
Sent By wjolin Date 2013-12-10 Time 12:44 Rev Time 0.00
Received By wjolin Date 2013-12-10 Time 12:44 Sent To  
Notes
2013-11-21 15:39:31ROUTED TO BLDG

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-10 Cont ID  
Sent By wjolin Date 2013-12-10 Time 12:44 Rev Time 0.00
Received By wjolin Date 2013-10-31 Time 12:16 Sent To  
Notes
2013-10-31 12:16:41FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By skennedy Date 2013-12-03 Time 14:48 Rev Time 0.00
Received By skennedy Date 2013-12-03 Time 14:48 Sent To FIRE
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved