Plan Review Details - Permit 13100950
Plan Review Stops For Permit 13100950
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By scaldero Date 2013-10-28 Time 14:40 Rev Time 0.00
Received By scaldero Date 2013-10-28 Time 14:15 Sent To M
Notes
2013-10-28 14:40:17PERMIT #13100950
 MASTER # 13070818
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLANS DO NOT SHOW LOCATION(S) OF EMERGENCY PULL
 STATION(S). PER FBC 904.11.1, A MANUAL ACTIVATION
 DEVICE SHALL BE LOCATED ALONG THE EGRESS PATH AND BE A
 MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM THE
 KITCHEN EXHAUST SYSTEM. THE DEVICE SHALL BE MOUNTED
 42-48 INCHES ABOVE THE FLOOR AND SHALL CLEARLY IDENTIFY
 THE HAZARD PROTECTED.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-01 Cont ID  
Sent By shill Date 2013-11-01 Time 12:56 Rev Time 0.00
Received By shill Date 2013-10-25 Time 14:30 Sent To  
Notes
2013-10-25 14:30:51INCOMING SENT TO FIEW BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By mricard Date 2013-10-31 Time 14:31 Rev Time 0.00
Received By mricard Date 2013-10-31 Time 14:22 Sent To  
Notes
***NONE***