Plan Review Details - Permit 13100890
Plan Review Stops For Permit 13100890
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-12-13 Cont ID  
Sent By jgomez Date 2013-12-13 Time 15:27 Rev Time 0.00
Received By jgomez Date 2013-12-13 Time 15:27 Sent To  
Notes
2013-12-13 15:27:36LEGIBLE DRAWINGS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-09 Cont ID  
Sent By jgomez Date 2013-12-09 Time 09:01 Rev Time 0.00
Received By jgomez Date 2013-12-09 Time 09:01 Sent To  
Notes
2013-12-09 09:46:18TALKED TO CLAY THOMAS. DRAWINGS ARE TOO LIGHT AND ARE
 NOT LEGIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-31 Cont ID  
Sent By jgomez Date 2013-10-30 Time 16:13 Rev Time 0.00
Received By jgomez Date 2013-10-30 Time 16:13 Sent To  
Notes
2013-10-28 10:51:03BUILDING REVIEW COMMENTS TO SUBMITTAL ADDRESSING
 PROVISO:
  
 ***NOTE: THERE WERE NOT REVISED DRAWINGS SUBMITTED AT
 THIS TIME. ONLY PRODUCT APPROVALS AND ENERGY
 CALCULATIONS***
  
  
 1- ENERGY CALCULATIONS SUBMITTED MAIN HOUSE AND CABANA:
 A) ENERGY CALCULATIONS AND PLANS NEED TO BE
 COORDINATED. PLANS TO SHOW THE R-VALUE FOR WALLS,
 CEILINGS AND FLOOR OVER OTHER SPACE.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) CALCULATIONS WERE SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER. NEED ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE (NO COPY) AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 C) REVISE DOOR TYPE TO MATCH PRODUCT APPROVALS. THERE
 ARE NOT WOOD DOORS.
  
 2- PROVIDE MANUFACTURER SPECS FOR THE ICYNENE
 INSULATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS
 CREDIT. NEED PLANS TO SHOW FAN SIZES AS REQUIRED BY SEE
 SEC. 405.6.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 *A)ENTRY DOOR THAT MEETS THE ENGINEER CALCULATED
 PRESSURES. INFORMATION SUBMITTED IS NOT A FLORIDA
 PRODUCT APPROVAL AND DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 ***NOTE; MANUFACTURER MAY APPLY FOR A LOCAL OR SITE
 SPECIFIC PRODUCT APPROVAL IF THERE IS NOT A CURRENT
 FLORIDA PRODUCT APPROVAL. COMPLETE ORIGINAL ENGINEERED
 PACKAGE WILL BE REQUIRED FOR APPROVAL.
  
 B) SHUTTERS AS SHOWN ON PLANS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
  
 C) STORAGE STEEL DOOR. NEED COMPLETE PRODUCT APPROVAL
 INCLUDING THE DRAWINGS.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-12-02 Cont ID  
Sent By fmittner Date 2013-12-02 Time 11:46 Rev Time 0.00
Received By fmittner Date 2013-12-02 Time 11:46 Sent To B
Notes
2013-11-22 07:51:0711/22/13 - ZONING RECEIVED. SENT TO FM FOR HIST REVIEW.
 LL

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By fmittner Date 2013-10-31 Time 10:05 Rev Time 0.00
Received By fmittner Date 2013-10-31 Time 10:05 Sent To  
Notes
2013-10-31 10:08:33NO TINITING PERMITTED ON FRONT ELEVATION WINDOWS.
 FRIEDERIKE CONFIRMED WITH CHRISTIAN THOMAS 10/31/13.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-09 Cont ID  
Sent By jgomez Date 2013-12-09 Time 09:46 Rev Time 0.00
Received By jgomez Date 2013-11-21 Time 13:48 Sent To  
Notes
2013-11-21 13:48:56SENT TO ZONING SHELF FOR HISTORIC REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-31 Cont ID  
Sent By jgomez Date 2013-10-31 Time 10:20 Rev Time 0.00
Received By jgomez Date 2013-10-24 Time 10:54 Sent To  
Notes
2013-10-28 10:54:52SENT TO JULIO'S DESK FOR REVIEW. JG.