Plan Review Details - Permit 13100669
Plan Review Stops For Permit 13100669
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By albarran Date 2013-10-28 Time 11:33 Rev Time 0.00
Received By albarran Date 2013-10-28 Time 11:25 Sent To I
Notes
2013-10-28 11:40:45THOUGH INCLUDED IN YOUR LOAD CALCS, THE HVAC EQUIPMENT
 IS NOT REFLECTED ON THE SUBMITTED PLANS. IF FOR ANY
 REASON, THIS IS BECAUSE THE UNIT WILL BE IN THE ATTIC,
 THE REQUIREMENTS OF NEC 110.33(B) WILL APPLY.
 BECAUSE THE ROOM REFLECTED AS A STUDY ON THE PLANS, HAS
 A CLOSET, IT WILL BE CONSIDERED A BEDROOM; THEREFORE
 THE REQUIREMENTS FOR SMOKE DETECTORS WILL APPLY.
 SENT TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-28 Cont ID  
Sent By jlmitch Date 2013-10-28 Time 17:47 Rev Time 0.00
Received By jlmitch Date 2013-10-21 Time 11:52 Sent To  
Notes
2013-10-21 11:52:38TO ELECTRIC BOX. JW