Plan Review Details - Permit 13100551
Plan Review Stops For Permit 13100551
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-06 Cont ID  
Sent By shill Date 2013-12-06 Time 12:19 Rev Time 0.00
Received By shill Date 2013-12-06 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 08:08 Rev Time 0.00
Received By shill Date 2013-11-02 Time 08:08 Sent To  
Notes
2013-11-02 08:12:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, THE FASTENER DIAMETER AND LENGTH (OR
 MINIMUM EMBEDMENT) AS WELL AS FASTENER SPACING WAS NOT
 INCLUDED ON THE PLAN.
  
 2. COVER SHEET OF PLAN STATES THAT ENGINEERING IS
 INCLUDED. PLEASE PROVIDE FBC 107.
  
 3. STRUCTURAL PLAN TO INCLUDE WIND DESIGN CRITERIA
 FBC1603.1.4. IF PLANS ARE NOT SIGNED AND SEALED BY AN
 ARCHITECT OR ENGINEER, INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN, AND CALCULATIONS MAY BE REQUIRED.
  
 4. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS
 JOB, FBC 109. VALUE IS TO BE INCLUDE LABOR, MATERIALS,
 AND ENGINEERING. IF SIGNS ARE PROVIDED BY OTHERS,
 PLEASE HAVE THEM PROVIDE THE CONTRACT OR WORK ORDER FOR
 THE MATERIALS FBC 109.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By albarran Date 2013-10-31 Time 17:41 Rev Time 0.00
Received By albarran Date 2013-10-31 Time 16:56 Sent To I
Notes
2013-10-31 18:11:45THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE NEC
 COMPLIANCE OF THE SIGN ITSELF, BUT EXCLUDES ANY
 ELECTRICAL INSTALLATION FOR SUCH
  
 THIS WAS SUBMITTED IN CONJUNCTION W/PERMIT 13130552

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-06 Cont ID  
Sent By shill Date 2013-12-06 Time 12:19 Rev Time 0.00
Received By shill Date 2013-12-05 Time 17:43 Sent To  
Notes
2013-12-05 17:46:06TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 08:13 Rev Time  
Received By shill Date 2013-10-16 Time   Sent To  
Notes
2013-10-16 14:57:49ZONING BOX
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-29 Cont ID  
Sent By eschneid Date 2013-10-29 Time 10:31 Rev Time 0.00
Received By ajones Date 2013-10-21 Time 08:15 Sent To E
Notes
2013-10-21 08:15:4210/21/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL