Plan Review Details - Permit 13100414
Plan Review Stops For Permit 13100414
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-12-18 Cont ID  
Sent By shill Date 2013-12-18 Time 14:08 Rev Time 0.00
Received By shill Date 2013-12-18 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 14:33 Rev Time 0.00
Received By shill Date 2013-11-02 Time 14:33 Sent To  
Notes
2013-11-02 14:40:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 COMMENTS FROM PREVIOUS LIST:
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2ND REVIEW, NOT ADDRESSED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2ND REVIEW, NOT ADDRESSED.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 2ND REVIEW, TEST PROVIDED APPEARS COMPLIANT BUT WAS FOR
 "ACOUSTICAL SURFACES, INC." AND PRODUCT WAS "FELT
 PANELS (AKA "QUIET FLOOR ULTRA"). THIS IS NOT THE SAME
 NAME AS THE PRODUCT SUBMITTED ("ECO-ULTRA QUIET" WITH
 NO MANUFACTURER NAME). PLEASE CORRELATE.
  
 THE PHYSICAL UNDERLAYMENT SAMPLE PROVIDED DOES NOT
 APPEAR TO BE "FELT." IT IS DIFFICULT TO DETERMINE
 WHETHER THE PRODUCT TESTED IS THE PRODUCT PROPOSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-22 Cont ID  
Sent By shill Date 2013-10-22 Time 18:03 Rev Time 0.00
Received By shill Date 2013-10-22 Time 18:03 Sent To  
Notes
2013-10-22 18:04:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-18 Cont ID  
Sent By shill Date 2013-12-18 Time 14:08 Rev Time 0.00
Received By shill Date 2013-12-06 Time 17:56 Sent To  
Notes
2013-12-06 17:56:38SENT TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 14:40 Rev Time 0.00
Received By shill Date 2013-10-28 Time 09:58 Sent To  
Notes
2013-10-29 09:58:33SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-22 Cont ID  
Sent By shill Date 2013-10-22 Time 18:04 Rev Time 0.00
Received By shill Date 2013-10-11 Time 09:01 Sent To  
Notes
2013-10-12 09:02:07SENT TO BLDG UNDER $5000 BOX