Plan Review Details - Permit 13100403
Plan Review Stops For Permit 13100403
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 12:54 Rev Time 0.00
Received By shill Date 2014-04-09 Time 12:54 Sent To FIRE
Notes
2014-04-09 12:56:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 4. ILLUMINATION NOT SHOWN BUT IS REQUIRED, FBC 1006.
  
 IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. THE PLANS
 ARE TO BE STAMPED AND RECEIPT PROVIDED (IF FEES WERE
 DUE AND PAID). 233-5025 FOR MORE INFORMATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-21 Cont ID  
Sent By shill Date 2013-11-21 Time 13:02 Rev Time 0.00
Received By shill Date 2013-11-21 Time 11:27 Sent To Z
Notes
2013-11-21 13:02:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGNER TO ELECT A METHOD OF COMPLIANCE, FBC 2010
 EXISTING BUILDING 101.5. AS DESIGNER HAS NOT ELECTED A
 METHOD, COMMENTS WILL REFER TO THE APPLICABLE FBC 2010
 BUILDING REQUIREMENTS (RATHER THAN FBC 2010 EXISTING
 BUILDING). NOTE THAT NOT ENOUGH INFORMATION WAS
 PROVIDED TO GIVE A COMPLETE COMMENT LIST.
  
 2. PROVIDE A BUILDING SUMMARY ? SIZE, BUILDING TYPE,
 OCCUPANCY CLASSIFICATION (FBC CHAPTER 5, 6, 3).
  
 3. INCLUDE OCCUPANCY CLASSIFICATION (FBC CHAPTER 3) AND
 OCCUPANT LOAD OF PROPOSED SPACE, (FBC CHAPTER 10, FBC
 2010 ACCESSIBILITY 201.1.1. IF THIS IS TO BE DESIGNED
 TO BE EXEMPT FROM VERTICAL ACCESSIBILITY REQUIREMENTS,
 CLEARLY INDICATE ON THE PLAN WHICH EXEMPTION THIS FALLS
 UNDER.
  
 4. ILLUMINATION NOT SHOWN BUT IS REQUIRED, FBC 1006.
  
 5. CEILING HEIGHT TO COMPLY WITH FBC 1003.2.
  
 6. BARRIER REQUIRED, FBC 1003.3.1.
  
 7. PROPOSED IMPROVEMENT IS A MEZZANINE, PROVIDE
 INFORMATION SHOWING COMPLIANCE WITH FBC 505.
  
 8. STAIR INFORMATION FBC 1009 NOT SHOWN.
  
 9. HANDRAILS NOT SHOWN FBC 1009.12.
  
 10. PROVIDE A DETAIL WHICH SHOWS COMPLIANCE WITH FBC
 1013.3.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-04-18 Cont ID  
Sent By pleduc Date 2014-04-18 Time 14:54 Rev Time 0.00
Received By pleduc Date 2014-04-18 Time 14:47 Sent To PC
Notes
2014-04-18 14:55:43THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENT.
  
 THE PREVIOUS COMMENTS OF FIRE PREVENTION WERE NOT
 ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-02 Cont ID  
Sent By wjolin Date 2013-11-02 Time 12:54 Rev Time 0.00
Received By wjolin Date 2013-11-02 Time 12:35 Sent To B
Notes
2013-11-02 12:54:311717 EDGAR STREET
 PERMIT #13100403
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 HEADROOM: THE BAR JOISTS ABOVE THE MEZZANINE ARE
 LOCATED WITHIN 7'-6" OF THE FLOOR DECK.
  
 STAIR HANDRAILS& GUARDRAILS: GUARDS, AT LEAST 42-INCHES
 TALL, SHALL BE PROVIDED AT THE OPEN SIDES OF MEANS OF
 EGRESS (STAIRS, MEZZANINE, ETC.) THAT EXCEED 30-INCHES
 ABOVE THE FLOOR. OPEN GUARDS SHALL PROHIBIT THE PASSAGE
 OF A 4-INCH DIAMETER SPHERE UP TO A HEIGHT OF
 34-INCHES. THE TRIANGULAR OPENINGS FORMED BY THE RISER,
 TREAD AND BOTTOM ELEMENT OF THE GUARDRAIL SHALL
 PROHIBIT THE PASSAGE OF A 6-INCH DIAMETER SPHERE.
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 STAIR RISERS: INDICATE THE HEIGHT OF THE STAIR RISERS.
  
 INDICATE THE LOCATIONS OF MEZZANINE LIGHTING. IS
 LIGHTING TO BE PROVIDED TO ILLUMINATE THE AREA BELOW
 THE MEZZANINE?
  
 STRUCTURES WITH LIGHT FRAME FLOOR CONSTRUCTION SHALL BE
 IDENTIFIED WITH A SIGN AFFIXED TO THE BUILDING. THE
 SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE AND
 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE COLOR
 AND BEAR THE LETTER F DESIGNATION PER FLORIDA STATUTE
 633.027 AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-18 Cont ID  
Sent By pleduc Date 2014-04-18 Time 15:00 Rev Time 0.00
Received By pleduc Date 2014-03-28 Time 07:17 Sent To PC
Notes
2014-04-09 12:58:234/9 TO FIRE
  
2014-03-31 07:17:29SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-26 Cont ID  
Sent By llouie Date 2013-11-26 Time 13:51 Rev Time 0.00
Received By llouie Date 2013-10-11 Time 10:12 Sent To  
Notes
2013-11-22 13:29:5511/22 TO ZONING
  
2013-10-30 11:08:5910/30 TO FIRE
  
2013-10-12 10:13:14SENT TO BUILDING UNDER $5000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 12:57 Rev Time 0.00
Received By shill Date 2014-04-09 Time 12:57 Sent To  
Notes
2014-04-09 12:58:10IMPACT FEE ASSESSMENT REQUIRED - CONTACT 561-233-5025
 FOR MORE INFORMATION
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-11-21 Cont ID  
Sent By shill Date 2013-11-21 Time 11:58 Rev Time 0.00
Received By shill Date 2013-11-21 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-11-26 Cont ID  
Sent By llouie Date 2013-11-26 Time 13:51 Rev Time 0.00
Received By llouie Date 2013-11-26 Time 13:51 Sent To I
Notes
2013-11-26 13:51:08ZONING REVIEW NOT REQUIRED. PROPOSED MEZZANINE IS LESS
 THAN 1,000 SQ. FT.