2013-10-18 10:38:32 | BUILDING PLAN REVIEW |
| PERMIT:13100229 |
| ADD: 7100 S DIXIE HWY |
| CONT: CILAS CONCRETE |
| TEL: (561)689-3427 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRIDAY OCT 18/ 2013 |
| ACTION: DENIED |
| |
| 1) THE PLANS ARE PREPARED BY A DRAFTING SEREVICE AND |
| ADVERTISING AS SUCH WITH THERE NAME IN THE TITLEBLOCK. |
| F. S. 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE. |
| (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN |
| $25,000.00 EXCEPT FOR A SCHOOL, AUDITORIUM OR OTHER |
| BUILDING INTENDED FOR PUBLIC USE. |
| |
| 2) PLANS FAIL TO PROVIDE THE LOCATION OF THE WORK TO BE |
| COMPLETED UNDER THIS PERMIT, NO SITE PLAN, NO FLOOR |
| PLAN WAS PROVIDED INDICATING THE LOCATION THERE ARE TWO |
| BUILDINGS ON THIS LOT, AND MORE THAN ONE TENANT SUITE. |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION |
| 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING. |
| ASSUMED INTERIOR WALL? |
| |
| 3) OCCUPANT LOAD IS NOT KNOWN OR TRAVEL DISTANCE ? WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION |
| 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING. |
| |
| 4) THE SUBMITTED PLAN SHOWS EXIT LIGHTS THAT LEAD FOR |
| EXITING THROUGH THE STOREROOM EGRESS THROUGH THE |
| STORAGE ROOM NOT SHOWN NOR COMPLIANCE WITH; |
| 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES |
| 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| EXCEPTIONS: |
| 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| FOLLOWING ARE MET: |
| |
| 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| THAT FOUND IN THE MAIN RETAIL AREA; |
| |
| 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| THROUGH THE STOCKROOM; |
| |
| 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| EGRESS SIDE; AND |
| |
| 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| TO THE EXIT WITHOUT OBSTRUCTIONS. |
| |
| 5) IS THIS A CHANGE IN OCCUPANCY? * 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, 2010 EDITION 2012 FBC 107.3.5.1.1 |
| MINIMUM PLAN REVIEW CRITERIA. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |