|
 |
 |
 |
 |
 |
Plan Review Details - Permit 13100179
Plan Review Stops For Permit 13100179 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-11-07 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-07 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-11-07 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-11 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-11 |
Time |
11:32 |
Sent To |
|
|
Notes |
2013-10-11 11:35:18 | NEED TO COMPLY WITH FBC 1603.1.4 FOR WIND DDSIGN DATA | | ON CONSTRUCTION DOCUMENTS. | | | | 1) PROVIDE ULTIMATE DESIGN WIND SPEED AND NORMAL DESIGN | | WIND SPEED AS DETERMINED IN ACCORDANCE WITH FBC SECTION | | 1609.3.1. | | 2) PROVIDE RISK CATEGORY FROM TABLE 1604.5 OR TABLE | | 1.5-1 OF ASCE 7. | | 3) WIND EXPOSURE. | | 4) APPLICABLE ENCLOSURE CLASSIFICATION. | | 5) COMPONETS AND CLADDING DESIGN PRESSURES. | | | | REVIEWED BY WDS. | | | | DENIED SENT TO (F) | | CALL CONTRACTOR. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-11-01 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2013-11-01 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2013-11-01 |
Time |
15:46 |
Sent To |
B |
|
Notes |
2013-11-01 15:52:48 | THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO THE | | ELECTRICAL COMPLIANCE WITH NEC ARTICLE 600 FOR THE | | ACTUAL SIGN. THE ELECTRICAL CONNECTIONS TO SAME ARE | | UNDER A DIFFERENT PERMIT. | | SENT TO MISC. 2 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-11 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-11 |
Time |
11:35 |
Sent To |
|
|
Notes |
2013-10-11 11:36:26 | PROVIDE ALL ELECTRICAL DATA FOR A COMPLETE SIGN | | ELECTRIC. INCLUDE-- CIRCUITRY WITH CONDUIT AND | | CONDUCTOR SIZING, VOLTAGE DROP CALCS, WIND LOAD PER SE | | FLORIDA ENGINEERING, DISCONNECT LOCATIONS, UL LISTINGS, | | ETC....... | | REVIEWED BY WDS | | DENIED IN (F) | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-11-07 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-07 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-10-16 |
Time |
|
Sent To |
|
|
Notes |
2013-10-16 14:41:45 | ZONING BOX | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-11-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-11-02 |
Time |
12:24 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-10-07 |
Time |
10:14 |
Sent To |
|
|
Notes |
2013-11-02 12:26:26 | 11/2 FIRST SUBMITTAL HAS NOT COMPLETED ALL REVIEWS. | | CUSTOMER RESUBMITTED PRIOR TO COMPLETION OF ALL | | REVIEWS. ROUTING PLAN TO DENIED DRAWER TO MATCH WITH | | RESUBMITTAL AT FUTURE DATE. SH | | | 2013-10-07 10:14:49 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2013-10-29 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2013-10-29 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2013-10-29 |
Time |
10:41 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2013-10-10 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2013-10-10 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2013-10-10 |
Time |
10:50 |
Sent To |
|
|
Notes |
2013-10-10 11:22:32 | 10/10/13- DENIED- PLANS NEED TO BE STAMPED BY THE PALM | | BEACH OUTLETS AND A SITE PLAN INDICATING THE LOCATION | | OF THE BAY NEEDS TO BE INCLUDED. | | | | ANGELLA VANN | | 561-822-1441 | | [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |