Plan Review Stops For Permit 13100177 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-11-07 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-07 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-11-07 |
Time |
16:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-11 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-11 |
Time |
11:37 |
Sent To |
|
|
Notes |
2013-10-11 11:38:59 | NEED TO COMPLY WITH FBC 1603.1.4 FOR WIND DDSIGN DATA | | ON CONSTRUCTION DOCUMENTS. | | | | 1) PROVIDE ULTIMATE DESIGN WIND SPEED AND NORMAL DESIGN | | WIND SPEED AS DETERMINED IN ACCORDANCE WITH FBC SECTION | | 1609.3.1. | | 2) PROVIDE RISK CATEGORY FROM TABLE 1604.5 OR TABLE | | 1.5-1 OF ASCE 7. | | 3) WIND EXPOSURE. | | 4) APPLICABLE ENCLOSURE CLASSIFICATION. | | 5) COMPONETS AND CLADDING DESIGN PRESSURES. | | | | REVIEWED BY WDS. | | | | DENIED SENT TO (F). | | CALL CONTRACTOR. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2013-11-04 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2013-11-04 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2013-11-04 |
Time |
15:49 |
Sent To |
I |
|
Notes |
2013-11-04 15:50:35 | THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO THE | | ELECTRICAL COMPLIANCE WITH NEC ARTICLE 600 FOR THE | | ACTUAL SIGN. THE ELECTRICAL CONNECTIONS TO SAME ARE | | UNDER A DIFFERENT PERMIT. SEE 13100178 FOR ELECTRICAL | | CONNECTIONS PERMIT | | SENT TO SH DESK |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
albarran |
Date |
2013-11-04 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-11 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-11 |
Time |
11:39 |
Sent To |
|
|
Notes |
2013-10-11 11:40:07 | PROVIDE ALL ELECTRICAL DATA FOR A COMPLETE SIGN | | ELECTRIC. INCLUDE-- CIRCUITRY WITH CONDUIT AND | | CONDUCTOR SIZING, VOLTAGE DROP CALCS, WIND LOAD PER SE | | FLORIDA ENGINEERING, DISCONNECT LOCATIONS, UL LISTINGS, | | ETC....... | | REVIEWED BY WDS | | LEFT MESSAGE WITH CONTRACTOR. | | DENIED IN (F). |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-11-07 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-07 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2013-11-06 16:53:27 | 11/6 TO MISC 2 | | | 2013-10-16 14:38:59 | ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-11-07 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-07 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-10-07 |
Time |
10:15 |
Sent To |
|
|
Notes |
2013-10-07 10:15:21 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2013-10-29 |
|
|
Cont ID |
|
Sent By |
avann |
Date |
2013-10-29 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2013-10-22 |
Time |
14:22 |
Sent To |
E |
|
Notes |
2013-10-22 14:22:48 | 10/22/13 - ZONING RECEIVED. SENT TO AV FOR REVIEW. LL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2013-10-10 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2013-10-10 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2013-10-10 |
Time |
11:22 |
Sent To |
|
|
Notes |
2013-10-10 11:23:05 | 10/10/13- DENIED- PLANS NEED TO BE STAMPED BY THE PALM | | BEACH OUTLETS AND A SITE PLAN INDICATING THE LOCATION | | OF THE BAY NEEDS TO BE INCLUDED. | | | | ANGELLA VANN | | 561-822-1441 | | [email protected] |
|
|