Plan Review Details - Permit 13100117
Plan Review Stops For Permit 13100117
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-04 Cont ID  
Sent By lphilmor Date 2013-10-04 Time 14:01 Rev Time 0.00
Received By lphilmor Date 2013-10-04 Time 14:00 Sent To  
Notes
2013-10-04 14:01:282740 PARKER AVE
 PERMIT: 13100117
 PLAN REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY
 MATERIAL.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-04 Cont ID  
Sent By lphilmor Date 2013-10-04 Time 14:01 Rev Time 0.00
Received By lphilmor Date 2013-10-03 Time 14:46 Sent To  
Notes
2013-10-03 14:47:23ROUTED TO TEMP TENTS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved