Plan Review Details - Permit 13100085
Plan Review Stops For Permit 13100085 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-10-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-10-08 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-10-08 |
Time |
16:14 |
Sent To |
|
|
Notes |
2013-10-08 15:32:03 | NOTES: | | | | (A) MR. WARREN SCHAEFER (ENGINEER) EXPLAINED TO ROBERT | | BROWN THAT HORIZONTAL CROSS SECTION "L" ON SHEET 9 OF | | 18 OF NOA 12-0130.08 SHOWS A REINFORCED INTERLOCK. THE | | ASSEMBLY IS ACTING AS A SINGLE UNIT AND THAT'S WHY HE | | USED A TRIBUTARY AREA OF 50SF FOR THE CALCULATIONS. | | | | (B) JAMES GORDON (CONTRACTOR) SAID THAT THEY ARE USING | | THE SLIDING GLASS DOOR NOA 12-0130.08 FOR THE SLIDING | | WINDOWS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-10-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-10-07 |
Time |
19:00 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-10-07 |
Time |
18:53 |
Sent To |
|
|
Notes |
2013-10-08 09:55:22 | DOORS/WINDOWS REPLACEMENT, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED | | IN EXPOSURE "D" NOT "C". ENGINEER TO REVISE HIGHLIGHTED | | CALCULATIONS AS REQUIRED. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR THE SLIDING WINDOWS. | | | | 3- CLARIFY WHY THERE ARE TWO DIFFERENT SLIDING GLASS | | DOORS PRODUCT APPROVALS SUBMITTED. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | | | 4- CLARIFY WHY USING 50SF AS THE TRIBUTARY AREA ON THE | | COMPONENTS AND CLADDING CALCULATIONS. SEC. 107.2.1.3 | | CITY AMENDMENTS TO FBC. | | | | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-10-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-10-07 |
Time |
19:00 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-10-02 |
Time |
15:15 |
Sent To |
|
|
Notes |
2013-10-02 15:16:00 | ROUTED TO MISC 1 |
|
|
|