Plan Review Stops For Permit 13090935 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2013-12-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-12-16 |
Time |
17:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-12-16 |
Time |
17:11 |
Sent To |
|
|
Notes |
2013-12-16 17:16:35 | THE VALUE OF THE WORK WAS INCREASED FROM $24,150.00 TO | | $45,685.00 BASED ON THE CONTRACT THAT WAS SUBMITTED AND | | THE REDUCED SCOPE OF WORK. ONLY TWO BLADE SIGNS AND ONE | | "R" LETTER SIGN WILL BE INSTALLED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2013-12-13 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2013-12-12 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-12-13 |
Time |
17:21 |
Sent To |
|
|
Notes |
2013-12-13 17:52:18 | NEED COPY OF CONTRACT TO VERIFY THE VALUE OF THE | | PROJECT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2013-12-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-12-06 |
Time |
06:30 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-12-06 |
Time |
17:53 |
Sent To |
E |
|
Notes |
2013-12-06 06:31:56 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE VALUE OF $24,150.00 LISTED ON THE APPLICATION | | FOR THE "REVISED" SCOPE OF WORK INDICATED BY THE | | RE-SUBMITTED PLANS TO FABRICATE AND INSTALL (1) NON - | | ILLUMINATED REVERSE CHANNEL LETTER SIGN AND (2) | | ILLUMINATED 20' TALL BLADE SIGNS IS LOW. FOR PERMITTING | | PURPOSES THE VALUATION IS TO INCLUDE ALL DESIGN, | | FABRICATION, INSTALLATION COSTS, OVERHEAD AND PROFIT. | | PLEASE SUBMIT TWO COPIES OF THE SIGNED CONTRACT FOR | | THIS WORK. CITY AMENDMENTS 109.3 | | | | 2) THE SCOPE OF WORK ON THE APPLICATION WILL NEED TO BE | | CHANGED TO CORRESPOND WITH THE PLANS. | | | | 3) THE PLANS INDICATE THAT ONE OF THE BLADE SIGNS IS | | ATTACHED TO THE CORNER OF THE BUILDING. THE ENGINEERING | | ONLY SHOWS A FLAT BRACKET AND AN ANGLE BRACKET WILL BE | | NEEDED TO ATTACH THE SIGN AT THE CORNER. PROVIDE | | ENGINEERING FOR THE BLADE SIGN THAT WILL BE MOUNTED TO | | THE CORNER OF THE BUILDING. FBC 1604.2 | | | | NOTE: IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE | | PROVIDE A RESPONSE LETTER INDICATING HOW EACH REVIEW | | COMMENT WAS ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-10-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-10-07 |
Time |
19:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-10-07 |
Time |
19:04 |
Sent To |
E |
|
Notes |
2013-10-08 09:06:06 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE VALUE OF $24,150.00 LISTED ON THE APPLICATION | | FOR THE SCOPE OF WORK INDICATED, FABRICATE AND INSTALL | | (4) LED ILLUMINATED REVERSE CHANNEL LETTER SIGNS AND | | (2) + 23' TALL BLADE SIGNS IS LOW. FOR PERMITTING | | PURPOSES THE VALUATION IS TO INCLUDE ALL DESIGN, | | FABRICATION, INSTALLATION COSTS, OVERHEAD AND PROFIT. | | PLEASE SUBMIT TWO COPIES OF THE SIGNED CONTRACT FOR | | THIS WORK. CITY AMENDMENTS 109.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-12-12 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-12-12 |
Time |
16:39 |
Sent To |
B |
|
Notes |
2013-12-12 16:39:36 | TO RM DESK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-12-06 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-12-06 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-12-06 |
Time |
08:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2013-10-08 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-08 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-08 |
Time |
15:39 |
Sent To |
|
|
Notes |
2013-10-08 15:46:36 | VALUE OF PROJECT MUST COMPLY WITH NOTES FRM BUILDING | | REVIEW. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2013-12-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-12-13 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-12-09 |
Time |
17:54 |
Sent To |
Z |
|
Notes |
2013-12-09 17:58:00 | SENT TO ZONING BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-12-06 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-12-06 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-12-03 |
Time |
|
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-12-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-10-11 |
Time |
07:48 |
Rev Time |
|
Received By |
rmcdouga |
Date |
2013-09-27 |
Time |
|
Sent To |
|
|
Notes |
2013-09-27 14:59:31 | TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2014-01-24 |
Time |
|
Sent To |
|
|
Notes |
2014-01-24 10:30:38 | 1/24/14 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-12-13 |
Time |
17:52 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2013-12-10 |
Time |
15:46 |
Sent To |
B |
|
Notes |
2013-12-12 14:51:57 | PASSED | | | | 1) CITYPLACE AUTHORIZED THE 10% TRANSFER FROM EAST TO | | NORTH FACADE = 320.75 LINEAR FEET X 10% = 32.075 LINEAR | | FEET. NORTH FACADE 107 LINEAR FEET + 32.075 LINEAR FEET | | = 139.075 LINEAR FEET = 139.075 SQ. FT. | | | | PERMITTED EAST EXTERIOR ARCADE FACADE: 288.675 SQ. FT. | | (320.75 SQ. FT. - 32.075 SQ. FT.) | | PROPOSED EAST VERTICAL BUILDING SIGN: 136.66 SQ. FT. | | | | PERMITTED EAST INTERIOR ARCADE FACADE: 320.75 SQ. FT. | | PROPOSED R SIGN: 31.41 SQ. FT. | | | | PERMITTED NORTH EXTERIOR FACADE: 139.075 SQ. FT. ( 107 | | SQ. FT. + 32.075 SQ. FT) | | PROPOSED NORTH VERTICAL BUILDING SIGN: 136.66 SQ. FT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2013-12-10 15:46:56 | 12/10/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2013-12-04 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-12-06 |
Time |
08:54 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2013-12-04 |
Time |
11:37 |
Sent To |
E |
|
Notes |
2013-12-04 13:17:36 | FAILED | | | | GENERAL COMMENTS | | | | 1) PLEASE PROVIDE CLARITY AS TO THE SPECIFIC WAY THE | | VERTICAL BUILDING SIGNS WILL BE MOUNTED TO THE WALLS. | | SOME OF THE DRAWINGS FOR SIGN 1 APPEAR TO HAVE IT | | MOUNTED ON THE SOUTH FACADE OF THE BUILDING INSTEAD OF | | THE EAST FACADE. SIGN 2 APPEARS TO BE MOUNTED OUT FROM | | THE CORNER OF THE BUILDING IN SOME DRAWINGS, BUT | | MOUNTED PERPENDICULAR TO THE WALLS IN OTHERS. PLEASE | | PROVIDE A PLAN VIEW OF BOTH SIGNS TO SHOW THEIR EXACT | | ORIENTATION. PLEASE INCLUDE THE ADJACENT FEATURES, SUCH | | AS THE BALCONY FOR SIGN 1. | | | | 2) THE FLOOR PLAN AND ELEVATION DRAWINGS INCORRECTLY | | SHOW 339 FEET OF FRONTAGE. THE RECESSED SOUTHERN AREA | | MAY NOT BE COUNTED AS FRONTAGE SINCE THE KITCHEN AREA | | DOES NOT DIRECTLY FRONT ON THE EAST FACADE. IT IS | | BLOCKED BY THE ELEVATOR AND STAIRWAY FOR THE UPPER | | FLOORS TO 477 S. ROSEMARY AVENUE. PLEASE PROVIDE | | REVISED CALCULATIONS TO THE EDGE OF THE COVERED PATIO. | | WHILE IT APPEARS THAT THE FRONTAGE WILL STILL BE IN | | EXCESS OF 273.32 LINEAR FEET (SIZE OF BOTH VERTICAL | | BUILDING SIGNS) STAFF REQUIRES THE CORRECT DIMENSION TO | | APPROVE THE PERMIT. | | | | PERMITTED EAST EXTERIOR ARCADE FACADE ? | | PROPOSED VERTICAL BUILDING SIGNS (136.66 SQ. FT. X 2): | | 273.32 SQ. FT. | | | | PERMITTED EAST INTERIOR ARCADE FACADE ? | | PROPOSED R SIGN: 31.41 SQ. FT. | | | | 3) VERTICAL BUILDING SIGNS | | | | A. THE CITYPLACE MASTER SIGN PLAN PROHIBITS VISIBLE | | EXPOSED BULBS. THE SIGNED AND SEALED ENGINEER DRAWINGS | | SHOW A CLEAR PLEXIGLAS COVER ON THE SIDE AND BOTTOM | | BULBS, BUT NOT THE TOP. THE SIGN DRAWINGS SHOW NO COVER | | ON THE BULBS. | | | | B. THE RENDERING FOR SIGN 1 IS INCORRECT. IT ACUTALLY | | APPEARS TO BE A RENDERING OF SIGN 2, YET THE WINDOWS | | ARE NOT SHOWN CORRECTLY SO IT IS DIFFICULT FOR STAFF TO | | DETERMINE. IT IS DEFINATELY NOT SIGN 1 LOCATION. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | 2013-12-04 10:40:53 | 12/4/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2013-10-11 |
Time |
14:16 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2013-09-30 |
Time |
08:34 |
Sent To |
B |
|
Notes |
2013-10-11 15:32:05 | FAILED | | | | GENERAL COMMENTS | | | | 1) PROVIDE AN OVERALL SITE PLAN SHOWING WHERE ALL THE | | SIGNS ARE TO BE LOCATED. | | | | 2) THE CITYPLACE MASTER SIGN PLAN MEASURES SIGNAGE | | ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR | | EACH ONE LINEAR FOOT OF STORE FRONTAGE. PLEASE PROVIDE | | THE LINEAR FEET OF STORE FRONTAGE FOR EACH FACADE. A | | FULL ANALYSIS OF THE PERMIT CAN NOT BE COMPLETED | | WITHOUT THIS DIMENSION. | | | | PERMITTED NORTH FACADE ? | | PROPOSED R (15.46 SQ. FT. X 2): 30.92 SQ. FT. | | PROPOSED WORDS: ? SQ. FT. | | | | PERMITTED WEST FACADE ? | | PROPOSED RED BRICK GRILL SIGN: ? | | PROPOSED VERTICAL BUILDING SIGNS (X2): ? | | PROPOSED WORDS: ? SQ. FT. | | | | PERMITTED SOUTH FACADE? | | PROPOSED RED BRICK GRILL SIGN: ? | | PROPOSED R: 15.46 SQ. FT. | | | | 2) RED BRICK GRILLE SIGNS | | | | A. THE SIGN SHOWN ON THE SOUTH FACADE IS IS NOT A | | DESIGNATED SIGN ZONE LOCATION IN THE CITYPLACE MASTER | | SIGN PLAN. THE CITYPLACE MASTER SIGN PLAN ALLOWS | | VARIANCES FROM THIS PROVISION. PROVIDE A NOTARIZED | | LETTER FROM CITYPLACE THAT THEY HAVE GRANTED THE | | VARIANCES TO LOCATE THE PROPOSED SIGN IN AN ALTERNTIVE | | HORIZONTAL PLACEMENT. | | | | B. PLEASE EXPLAIN WHY THE SIZE OF THE SIGN IS LISED AT | | 28.06 SQ. FT., BUT MULTIPYING THE DIMENSIONS RESULTS IN | | A 13.33 SQ. FT. SIGN. | | | | 3) VERTICAL BUILDING SIGNS | | | | A. THE CITYPLACE MASTER SIGN PLAN PROHIBITS MECHANICAL | | ANIMATION OR COMPONENTS. THE ROTATING DISC WITH "R" IS | | NOT PERMITTED. | | | | B.PROVIDE A NOTARIZED LETTER FROM CITYPLACE THAT THEY | | HAVE GRANTED THE VERTICAL BUILDING SIGN. | | | | C. THE FULL VERTICAL SIGN DIMENSION WAS NOT PROVIDED. | | STAFF IS UNABLE TO VERIFY DIMENSIONS, BUT THE SIGN FACE | | LISTED DIMENSION OF 90.72 SQ. FT. EXCEEDS THE CITYPLACE | | MASTER PLAN PERMITTED 75 SQ. FT. | | | | D. PROVIDE THE DIMENSION FROM THE WALL TO THE EDGE OF | | THE SIGN. | | | | 4) EAT, ETC TEXT | | | | A. WHY ARE DIFFERING DIMENSIONS GIVEN ON THE VARIOUS | | PLANS. | | | | CONTACT ERIKC SCHNEIDER @ (561) 822-1446. | 2013-09-30 08:37:29 | ZONING RECEIVED. SENT TO ES FOR REVIEW. |
|
|